NEOMERIS CONTROL DES
Appendix
Build:20211025-094624-9873335NSt
All information and technical data are subject to
change
Page 75
»Min(Warn.)
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Conductivity Sensor, Temp.Sensor
Range:
0.0 ... 99.9 °C
Default:
10.0 °C
»Min(Alarm)
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Conductivity Sensor, Temp.Sensor
Alarm low limit
Range:
0.0 ... 99.9 °C
Default:
3.0 °C
»Max(Warn.)
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Conductivity Sensor, Temp.Sensor
Warning high limit
Range:
0.0 ... 99.9 °C
Default:
60.0 °C
»Max(Alarm)
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Conductivity Sensor, Temp.Sensor
Alarm high limit
Range:
0.0 ... 99.9 °C
Default:
80.0 °C
»Hysther.(Warn.)
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Conductivity Sensor, Temp.Sensor
Hysteresis, used as +/- from threshold
Range:
0.0 ... 99.9 °C
Default:
5.0 °C
»Hysther.(Alarm)
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Conductivity Sensor, Temp.Sensor
Hysteresis, used as +/- from threshold
Range:
0.0 ... 99.9 °C
Default:
5.0 °C
»Prio Warn.
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Conductivity Sensor, Temp.Sensor
Set warning priority
Range:
0 ... 99
Default:
50
»Prio Alarm
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Conductivity Sensor, Temp.Sensor
Set alarm priority
Range:
0 ... 99
Default:
20
»Delay Warn.
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Conductivity Sensor, Temp.Sensor
Delay of warning triggering
Range:
0 ... 999 s
Default:
0 s
»Delay Alarm
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Conductivity Sensor, Temp.Sensor
Delay of alarm triggering
Range:
0 ... 999 s
Default:
0 s
»Reac. Sys.
(Sel.)
NEOMERIS CONTROL DES, Device, Bleed
off, Conductivity Sensor, Temp.Sensor
Reaction of the system to an alarm-type mes-
sage
Default:
Continue
0 Continue
No shutdown
1 Shutdown
Shutdown with permanent re-
tries
2 Cycl.shutdown
Shutdown with defined num-
ber of retries
3 Dur. shutdown Durable shutdown
Kind of contact (energised/off)
Default:
active=energized