![Neomeris CONTROL DES Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/neomeris/control-des/control-des_manual_719137018.webp)
NEOMERIS CONTROL DES
Specifications
Build:20211025-094624-9873335NSt
All information and technical data are subject to
change
Page 11
Information
Voltage
like incoming main supply
max. Current
5A AC
max. Power
nom. 1100VA
Remark
reduced wit inductive load
Description
Supply sourcing 24V DC for externals
Information
Voltage
24V DC
max. Current
600mA DC
max. Power
15W
Remark
4.1.5 Digital Inputs
The control unit has the following digital inputs / switch inputs:
Identifier
DosProp.1 Tank empty
Information
Type
Input for ext. isolated contact, npn-switching against GND
Low Volt.
> 1MOhm
High Volt.
< 100Ohm
Input Current
< 5mA @ 24V
Component
-
Remark
Input is supplied internal
Identifier
System enable
Information
Type
Input for ext. isolated contact, npn-switching against GND
Low Volt.
> 1MOhm
High Volt.
< 100Ohm
Input Current
< 5mA @ 24V
Component
-
Remark
Input is supplied internal
Identifier
TimeDosing Tank empty
Information
Type
Input for ext. isolated contact, npn-switching against GND
Low Volt.
> 1MOhm
High Volt.
< 100Ohm
Input Current
< 5mA @ 24V
Component
-
Remark
Input is supplied internal
4.1.6 Digital Outputs
The control unit has the following digital outputs / switching outputs:
Identifier
Alarm signal
Information
Alarm signal
Type
Relay, change over contact, isolated