Module: MAlarmMgrDOs
6.16.1 Info:
Alarm-M DO's
6.16.2 Comment:
Alarm Manager Module which detects alerts and alarms of each module.
This allows the system to respond to warnings or alarms as follows:
- No shutdown: The system reports the error but continues to run normally.
- Shutdown with permanent retries: The system reports the error and stops the process as long as
the condition of the alarm is present. When the alarm is cleared, the process restarts.
- Shutdown with defined number of retries: Like Shutdown with permanent retries, however, the
process will only be restarted as often as it is set in the Cyclic Retry menu.
- Durable shutdown: If there is a fault, the process is stopped until the user acknowledges the er-
rors.
The behavior is usually set in the limit menu of the respective sensor.
6.16.3 Internal elements of module:
6.16.3.1 Parameters
This module contains no elements.