5. Trouble Shooting
1.
Ensure the two LED boards are correctly wired to terminal block.
White to White : White/Red to White/Red
2.
Ensure Mains input is correctly connected.
3.
Ensure Mains Input is turned on at the source
4.
On emergency variants check fuse to ensure it has not blown
5.
If LED panel fails to light is it possible to identify if problem is with LED panel or
power supply by swapping LED cables to opposite power supply to help
identify problem.
Max number of fittings allowed per MCB
(Based on 230V)
MCB Type
Rating
RF-8
RF-17
B
10A
5
2
B
16A
8
4
B
20A
12
8
B
25A
17
8
C
10A
12
6
C
16A
17
8
C
20A
24
12
C
25A
29
14
RF
9
-
1
2
www.nemalux.com | [email protected] | Tel 403•242•7475 | Fax 403•243•6190
SUBJECT TO CHANGE WITHOUT NOTICE