3. Open the rear compartment to access terminal block. Wire the Mains cable into 

the terminal block. Provision has been made for this and identified as the E 

(Earth), L1 (swiched live) and L2 (permanent live) and N (Neutral) terminals. There 

are two pairs of contacts for each of these to facilitate a mains cable that can be 

looped in and out of the unit. The L2 terminals on a standard unit is not 

electrically connected but allows them to be used on the same circuits as 

emergency floodlights

.

4. Installer should earth the unit separately – an internal and external earth point are 

provided as standard.

5. Connect wires to mains supply.

6. If the unit is opened for any reason, disconnect mains – 

On emergency 

luminaires there may be more than one mains supply.

7. All RF floodlights have terminal blocks suitable for looping 4mm2 cable, only one

cable should be connected to each terminal block connection.

8.

Emergency RF floodlights may have a single green LED fitted adjacent to the 

incoming cable glands, when illuminated the green LED indicates that the 

emergency system is healthy.

9.

The battery fuse located in the power supply lid on emergency variants is 

disconnected after final manufacturing testing. When installing the 

floodlight the battery fuse will need to be reconnected and the unit charged 

for 24 hours and then discharged (repeated 3 times) to bring the battery up 

to peak capacity.

10.

If a 4 core cable is used on emergency luminaires – L1, L2, N and E the link 

cable at the front of the terminal block between L1 and L2 should be 

removed.

11.

During emergency operation the light output and duration will be 

determined by the variant purchased.

12.

 

Once wiring is complete replace rear cover. Ensure gasket is located neatly 

in channel and no wires are trapped between cover and body. Tighten cover 

screws to 3Nm.

13.

 

If carrying out Insulation Resistance tests the normal method of insulation testing 

is to connect Live and Neutral together and test between this point and Earth to 

prevent the risk of damage to the electronic control gear.

6

-

1

2

www.nemalux.com  |   [email protected]  |   Tel 403•242•7475  |   Fax 403•243•6190 

SUBJECT TO CHANGE WITHOUT NOTICE

MADE IN 

UK

Содержание RF Series

Страница 1: ...ist devices certified for use in specific operating environments The units must be installed in accordance with these instructions must be correctly certified for the specific operating environment an...

Страница 2: ...pper plugs these must be parallel thread have a minium of 5 full thread engagement and be of a medium fine tolerance to ISO965 1 and ISO965 3 The cable entry devices selected must maintain the IP rati...

Страница 3: ...the fixing points must be suitable for the conditions of use Nemalux recommend using M8 Marine Grade A4 Stainless Steel fixings not supplied RF Series 12 Floodlight RF Series 24 Emergency Variant Show...

Страница 4: ...e floodlight It is very important that the red fibre washers are fitted between the RF housing and the mounting bracket The unit must be aligned first before securing the bracket and bolts tightened t...

Страница 5: ...standard luminaires Typical wiring diagram emergency luminaires WHITE RED WHITE RED WHITE RED WHITE RED 5 12 www nemalux com sales nemalux com Tel 403 242 7475 Fax 403 243 6190 SUBJECT TO CHANGE WITH...

Страница 6: ...g cable glands when illuminated the green LED indicates that the emergency system is healthy 9 The battery fuse located in the power supply lid on emergency variants is disconnected after final manufa...

Страница 7: ...RF unit from the mains supply and allow to cool before carrying out any maintenance work 4 The unit has 2 independent power supplies in the event that a power supply needs to be replaced the cables t...

Страница 8: ...TEX and IECEx and UKEX Rating See below CML17ATEX4231 or IECEx CML 17 0135 or CML 21UKEX4106 II 3 GD Ex ec mc IIC T4 Gc Ta 50 C to 55 C standard variants II 3 GD Ex ec mc IIC T4 Gc Ta 20 C to 55 C eme...

Страница 9: ...blown 5 If LED panel fails to light is it possible to identify if problem is with LED panel or power supply by swapping LED cables to opposite power supply to help identify problem Max number of fitt...

Страница 10: ...Zone 1 CML13ATEX3007 IEC Ex CML14 0001 CML21UKEX3099 Zone 2 CML17ATEX4231 IEC Ex CML17 0135 CML21UKEX4106 ATEX Quality Assurance Notification CSA BV 2813 UKCA Quality Assurance Notification CSA UK 05...

Страница 11: ...60079 0 2018 EN 60079 7 2015 A1 2018 EN 60079 18 2015 A1 2017 EN 60079 31 2014 EN 60079 1 2014 And also 2014 35 EU Low Voltage Directive 2014 30 EU EMC Directive Signed 11 12 www nemalux com sales nem...

Страница 12: ...2589 P 1 403 242 7475 F F 1 403 243 6190 E info nemalux com W www nemalux com Industrial LED Lighting designed to solve harsh and hazardous lighting challenges 12 12 www nemalux com sales nemalux com...

Отзывы: