FlexPAK 800/1000
29
EN
4.2.25 CoolTmp
Menu for setting CoolTmp
. See section ‘4.2.5 CoolTmr’.
The default settings for CoolTmp:
ESC
OK
CoolTmp
1/1
On = 97
Off = 96
On=97: The default temperature limit that is set to open Cleaning Valve
V1 “SCV”. The default setting is 97°C (207ºF).
Off= 96: This parameter is set to (CoolTmp On -1), The default setting is
96°C (205ºF). Always set Off to On minus 1°C (On = 97-1 = 96).
Ax=00:00: The current temperature of air exiting the system.
4.2.26 TVFD-Al-Tmr
Menu for setting the maximum closing and opening times both the upper and lower TVFD
slides. If the upper or lower TVFD slides do not close or open within the set time, an alarm
is activated. This message is only used when TVFD advanced is activated.
See sections:
•
‘3.3.9 TVFD Alarm! Upper Slide Not Closed’
•
‘3.3.10 TVFD Alarm! Upper Slide Not Open’
•
‘3.3.11 TVFD Alarm! Lower Slide Not Closed’
•
‘3.3.12 TVFD Alarm! Lower Slide Not Open’
ESC
OK
TVFD-Al-Tmr
1/1
T = 15:00s
Ta = 00:00s
T=15:00s: Maximum time for the upper and lower TVFD slides to close
or open . The default setting is 15 seconds.
Ta=00:00: The elapsed time since the closing or open cycle began.
4.2.27 BRSTmr
Menu for setting the maximum amount of time the Bag Replacement Switch (SC2) can be
activated. When this timer has elapsed, the unit turns off and goes into Off mode and an
alarm message is displayed in the PLC. See Section
‘3.3.7 Bag Replacement Switch Time
Out’.
ESC
OK
BRSTmr
1/1
T = 30:00m
Ta = 00:00m
T=30:00: The maximum amount of time set for SC2 to be activated. The
default setting is for 30 minutes.