FlexPAK 800/1000
15
EN
3.3
Alarms
If an alarm is activated, the unit goes into Off mode until the problem is corrected.
If an alarm message is displayed in the PLC display, the light in the Standby/Running
button flashes one second on, one second off. This 1/1 on/off sequence continues until the
problem is corrected and the alarm reset.
3.3.1
External Fire Alarm Explosion Detected
An external fire alarm is activated or a Relief Panel Sensor (RPS) is connected and has
detected an explosion. Press the green OK button
OK
to reset the alarm.
ESC
OK
E x t e r n a l
F i r e A l a r m o r
E x p l o s i o n
D e t e c t e d
Th 11:23
Reset OK==>
3.3.2
Frequency Conv Alarm
The frequency converter has detected a problem and that the PTC sensors in the motor
have reached the maximum temperature for the unit (140°C) so the unit has been put into
Off mode.
The following list shows the most common problems:
•
Connection problem to main power supply.
•
Motor cable problem.
•
Power supply fault.
•
There is a problem with the frequency converter.
•
PTC temp monitor detect an overheated motor.
ESC
OK
PTC Detect Hi
Motor Temp or
Inverter Fault
Th 12:23
Unit is stopped
Reset OK
3.3.3
Emergency Stop Activated
If this message appears in the display, one or more emergency stops have been activated
and the machine has been switched off.
Find out why the emergency stop has been activated and correct the problem. When all
hazards have been eliminated that activated the emergency stop, the emergency stop can
be reset. Reset the Emergency Stop Button by turning it and then pulling it outward.
When all emergency stops have been reset, the security circuit can be reset by pressing the
green OK button
OK
in the display.
If the Green OK button
OK
can not be reset even though all emergency stops are reset, it
may be due to a short circuit to ground in the emergency stop circuit or pilot signal circuit.
The emergency stop circuit and pilot signal are fed by fuse F4. If the fuse needs to be
replaced, replace the defective fuse with a 5 * 20mm, 50mAF (fast fuse).
ESC
OK
Emergency Stop
Activated
Th 11:23
Reset
E-Stop And Press
OK==>