background image

3

Contents

Contents

1. CERTIFICATION

 

5

1.1    BTL Mark – BACnet® Testing Laboratory 

5

2. INTRODUCTION

 

6

2.1    Gateway

 

6

3. GATEwAy SETUP

 

7

3.1    Record Identification Data

 

7

3.2    Point Count Capacity and Registers per Device

 

7

3.3    Configuring Modbus Device Communications

 

7

3.3.1    Input COM Settings on Any Device Connected to the 

Gateway

 

7

3.3.2    Set Node-ID for Any Device Attached to the Gateway

 

7

3.4    Attaching the Antenna

 

7

4. INTERFACING GATEwAy TO DEVICES 

8

4.1    NFB-301C/399C boiler Connections to Gateway

 

8

4.2    Wiring Field Port to RS-485 Serial Network

 

8

4.3    Bias Resistors

 

8

4.4    Termination Resistor

 

9

4.5    Power-Up Gateway

 

9

4.5.1    Power Up Using the PCB

 

9

4.5.2    Power Up Using the Power Supply

 

9

5. CONNECT THE PC TO THE GATEwAy

10

5.1    Connecting to the Gateway via Ethernet

 

10

5.1.1    Enable Access Through the Local Browser

 

10

5.2    Connecting to the Gateway Over Wi-Fi Access Point 

11

6. CONFIGURE THE GATEwAy

12

6.1    Accessing the Gateway Web Configurator 

12

6.2    Setting Gateway Configuration Parameters

 

13

6.2.1    Verify Device Communications

 

13

6.3    BACnet: Setting Node_Offset to Assign Specific Device 

Instances

 

14

6.4    How to Start the Installation Over: Clearing Profiles

 

14

7. NETwORK SETTINGS

 

15

7.1    Navigate to the FS-GUI Network Settings

 

15

7.2    Change the Gateway IP Address

 

16

7.2.1    Update Wired Network Settings

 

16

7.2.2    Update Wi-Fi Client Settings

 

16

7.2.3    Common Settings

 

17

Appendix A.    Troubleshooting 

18

Appendix A.1    Lost or Incorrect IP Address

 

18

Appendix A.2    Viewing Diagnostic Information

 

18

Appendix A.3    Checking Wiring and Settings

 

18

Appendix A.4    LED Diagnostics for Communications 

Between Gateway and Devices

 

19

Appendix A.5    Taking a FieldServer Diagnostic Capture

 

19

Appendix A.5.1    Using the FieldServer Toolbox

 

19

Appendix A.5.2    Using FS-GUI

 

20

Appendix A.6    Wi-Fi Signal Strength

 

21

Appendix B.    Additional Information

 

22

Appendix B.1    Updating Firmware

 

22

Appendix B.2    BACnet: Setting Network_Number for More 

Than One Gateway on the Subnet

 

22

Appendix B.3    Securing Gateway with Passwords

 

22

Appendix B.4    Wi-Fi Access Point Network Settings

 

23

Appendix B.5    Mounting

 

23

Appendix B.6    Physical Dimension Drawing

 

24

Appendix C.    Vendor Information – Navien

 

25

Appendix C.1    NFB-C Single Boiler Modbus RTU Mappings 

to BACnet/IP and BACnet MS/TP

 

25

Appendix C.2    NFB-C Main 1 Sub 1 - Sub 31 Modbus RTU 

Mappings to BACnet/IP and BACnet MS/TP

 

26

Appendix D.    Reference

 

35

Appendix D.1    Specifications

 

35

Appendix D.1.1    Compliance with UL Regulations

 

35

Appendix E.    Limited 2 year warranty

 

36

Содержание Modbus/BACnet Gateway

Страница 1: ...e For Interfacing Navien Products To Building Automation Systems and SMC Cloud BACnet MS TP BACnet IP and Modbus TCP IP APPLICABILITY EFFECTIVITY Explains Modbus BACnet gateway and how to install it T...

Страница 2: ...RS 485 R2 port to the field protocol cabling Section 4 2 5 Connect power to gateway s 3 pin connector Section 4 5 6 Connect a PC to the gateway via Ethernet cable or by the gateway s Wi Fi Access Poi...

Страница 3: ...ver Clearing Profiles 14 7 NETWORK SETTINGS 15 7 1 Navigate to the FS GUI Network Settings 15 7 2 Change the Gateway IP Address 16 7 2 1 Update Wired Network Settings 16 7 2 2 Update Wi Fi Client Sett...

Страница 4: ...Resistor DIP Switch 9 Figure 9 Required Current Draw for the Gateway 9 Figure 10 PCB Power Connections 9 Figure 11 External Power Connections 9 Figure 12 Ethernet Port Location 10 Figure 13 Web App S...

Страница 5: ...by an independent laboratory which verifies that the product correctly implements the BACnet features claimed in the listing The mark is a symbol of a high quality BACnet product Go to www BACnetInter...

Страница 6: ...Navien s devices hereafter simply called device connected to the gateway and automatically configures them for BACnet IP BACnet MS TP and Modbus TCP IP It is not necessary to download any configurati...

Страница 7: ...nected serial device MUST have the same baud rate data bits stop bits and parity settings as the gateway Figure 4 specifies the device serial port settings required to communicate with the gateway Por...

Страница 8: ...res and notes The R1 and R2 DIP Switches apply settings to the respective serial port If the gateway is already powered on DIP switch settings will not take effect unless the unit is power cycled 4 1...

Страница 9: ...ment for Gateway Current DrawType Navien Gateway Family 12 VDC 24 V DC AC GXXX001932 Typical 250 mA 125 mA Note These values are nominal and a safety margin should be added to the power supply of the...

Страница 10: ...the Subnet of the Connected PC The default IP Address for the gateway is 192 168 1 24 Subnet Mask is 255 255 255 0 If the PC and gateway are on different IP networks assign a static IP Address to the...

Страница 11: ...ay with Wi Fi To connect to the gateway Wi Fi Access Point 1 Click the icon found in the bottom right corner of the computer screen to open the available Wireless Network Connections 2 Select the desi...

Страница 12: ...eldServer Toolbox Section 5 1 1 2 click the Connect button Note 2 Once at the Web App splash page click the Login button Figure 13 Web App Splash Page 3 Enter the previously set up or default username...

Страница 13: ...g See Appendix A 4 for additional information and images 2 Confirm the software shows communication without errors Go to Appendix A 2 for instructions 6 2 Setting Gateway Configuration Parameters 1 Se...

Страница 14: ...ent value default 50 000 The values allowed for a BACnet Device Instance can range from 1 to 4 194 303 2 To assign a specific Device Instance or range change the Node_Offset value as needed using the...

Страница 15: ...igurator page click on the blue Diagnostics Debugging button in the bottom right corner of the screen Figure 23 Web Configurator Page Diagnostics Button Figure 24 FS GUI Landing Page 3 Click the orang...

Страница 16: ...ion toWi Fi Client 7 2 Change the Gateway IP Address Configure the IP settings of the gateway in the following methods When using the Ethernet port to connect to the local network Section 7 2 1 When c...

Страница 17: ...GUI Common Network Settings Note The fields below the update button show the settings as they were set in the IP Settings or Wi Fi Client pages They are not editable on the Common page Figure 27 FS GU...

Страница 18: ...Address of the gateway into the web browser or use the FieldServer Toolbox to connect to the gateway 2 Click on Diagnostics Button then click on view and then on connections 3 If there are any errors...

Страница 19: ...tion Figure 31 Diagnostic LEDs Appendix A 5 Taking a FieldServer Diagnostic Capture When there is a problem on site that cannot easily be resolved perform a diagnostic capture before contacting suppor...

Страница 20: ...ved on the PC b Choose Open to launch explorer and have it point directly at the correct folder c Send the Diagnostic zip file to technical support Appendix A 5 2 Using FS GUI Diagnostic Capture via F...

Страница 21: ...ture to be downloaded to the local PC 6 Send the diagnostic zip file to technical support Note Diagnostic captures of BACnet MS TP communication are output in a PCAP file extension which is compatible...

Страница 22: ...nected to the same subnet they must be assigned unique Network_Number values On the main Web Configuration screen update the BACnet Network Number field and click submit The default value is 50 Figure...

Страница 23: ...Fi Settings then click on the System Restart to restart the gateway and activate the Wi Fi settings Note If the FS GUI was open in a browser via Wi Fi the browser will need to be updated with the new...

Страница 24: ...24 Additional Information Appendix B 6 Physical Dimension Drawing Power Port R2 Serial Port Wi Fi Antenna Socket R1 Serial Port Figure 39 Modbus BACnet Gateway Part Number GXXX001932 Dimensions...

Страница 25: ...CH supply min temperature setting AV 16 CH supply max temperature setting AV 17 CH return min temperature setting AV 18 CH return max temperature setting AV 19 Appendix C 1 NFB C Single Boiler Modbus...

Страница 26: ...rror state BI 4006 Sub04 Boiler enable status BI 4007 Sub04 Boiler pump op Status BI 4008 Point Name BACnet ObjectType BACnet Object ID Sub05 Burner op state BI 5001 Sub05 Frozen protection mode BI 50...

Страница 27: ...mode BI 25002 Sub25 Error state BI 25006 Sub25 Boiler enable status BI 25007 Sub25 Boiler pump op Status BI 25008 Point Name BACnet ObjectType BACnet Object ID Sub12 Burner op state BI 12001 Sub12 Fr...

Страница 28: ...tatus AI 2001 Sub02 Main Error code AI 2002 Sub02 Current Heat capacity AI 2004 Sub02 Supply temperature AI 2005 Point Name BACnet ObjectType BACnet Object ID Sub26 Burner op state BI 26001 Sub26 Froz...

Страница 29: ...nt of gas AI 7013 Sub07 Total amount of gas AI 7014 Sub08 Operation Status AI 8001 Sub08 Main Error code AI 8002 Point Name BACnet ObjectType BACnet Object ID Sub02 Return temperature AI 2006 Sub02 Ma...

Страница 30: ...n AI 13011 Sub13 Total time of CH operation AI 13012 Sub13 Current amount of gas AI 13013 Sub13 Total amount of gas AI 13014 Point Name BACnet ObjectType BACnet Object ID Sub08 Current Heat capacity A...

Страница 31: ...time after installation AI 19010 Sub19 Number of CH operation AI 19011 Sub19 Total time of CH operation AI 19012 Point Name BACnet ObjectType BACnet Object ID Sub14 Operation Status AI 14001 Sub14 Ma...

Страница 32: ...Sub25 Maximum Heat capacity AI 25008 Sub25 Exhaust temperature AI 25009 Sub25 Total time after installation AI 25010 Point Name BACnet ObjectType BACnet Object ID Sub19 Current amount of gas AI 19013...

Страница 33: ...acity AI 31004 Sub31 Supply temperature AI 31005 Sub31 Return temperature AI 31006 Sub31 Maximum Heat capacity AI 31008 Point Name BACnet ObjectType BACnet Object ID Sub25 Number of CH operation AI 25...

Страница 34: ...ting AV 2 SH return setpoint setting AV 3 DHW setpoint setting AV 4 Error reset command AV 5 Boiler setpoint in DHW operation AV 7 Outdoor reset curve heatload setting AV 9 Maximum outdoor temperature...

Страница 35: ...r a special tool to gain access This device must not be connected to a LAN segment with outdoor wiring Appendix D 1 Specifications Gateway Part Number GXXX001932 Electrical Connections One 3 pin Phoen...

Страница 36: ...have been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables or to any damage resulting from battery leakage In all cases Sierra Monitor Corpo...

Страница 37: ...Memo...

Страница 38: ...Memo...

Страница 39: ...net MS TP BACnet IP and Modbus TCP IP protocols For technical support please contact us at 800 519 8794 800 519 8794 www NavienInc com 20 Goodyear lrvine CA 92618 Installation Operation Manual Modbus...

Отзывы: