25
Vendor Information – Navien
Point Name
BACnet
Object Type
BACnet
Object ID
Maximum Heat capacity
AI
13
Total time of CH operation
AI
14
Number of CH operation
AI
15
Total time after installation
AI
16
Maximum outdoor temperature status
AI
27
Minimum outdoor temperature status
AI
28
CH supply minimum temperature
AI
29
CH supply maximum temperature
AI
30
CH return minimum temperature
AI
31
CH return maximum temperature
AI
32
DHW minimum temperature
AI
33
DHW maximum temperature
AI
34
SH control method
AI
35
DHW control method
AI
36
Gas type
AI
38
Current amount of gas
AI
41
Total amount of gas
AI
42
Boiler On/Off command
AV
1
SH supply setpoint setting
AV
2
SH return setpoint setting
AV
3
DHW setpoint setting
AV
4
Error reset command
AV
5
Boiler setpoint in DHW operation
AV
7
Outdoor reset curve heatload setting
AV
9
Maximum outdoor temperature
setting
AV
10
Minimum outdoor temperature setting
AV
11
WWSD temperature setting
AV
12
WWSD On differential setting
AV
13
Boost interval time setting
AV
14
Cascade Initial op units setting
AV
15
CH supply min temperature setting
AV
16
CH supply max temperature setting
AV
17
CH return min temperature setting
AV
18
CH return max temperature setting
AV
19
Appendix C.1 NFB-C Single Boiler Modbus
RTU Mappings to BACnet/IP and BACnet MS/TP
Point Name
BACnet
Object Type
BACnet
Object ID
SH operation on/off control
BV
1
Outdoor reset curve usage enable
BV
2
WWSD enable
BV
3
DHW operation ON/OFF control
BV
4
Burner operation state
BI
1
SH operation state
BI
2
DHW tank mode operation state
BI
4
Error state
BI
5
Boiler enable status
BI
7
Boiler pump Operation Status
BI
8
DHW/Zone1 pump Operation Status
BI
9
Zone2 pump status Operation Status
BI
10
System/Zone3 pump Operation Status
BI
11
SH1 Thermostat input Status
BI
12
SH2 Thermostat input Status
BI
13
SH3 Thermostat input Status
BI
14
DHW call signal
BI
15
DHW Thermostat input Status
BI
16
LWCO input status
BI
17
Frozen protection mode
BI
24
Main Error code
AI
1
Sub Error code
AI
2
Current Heat capacity
AI
3
Supply temperature
AI
4
Return temperature
AI
5
System Supply temperature
AI
6
System Return temperature
AI
7
Water pressure
AI
8
Exhaust temperature
AI
9
DHW Tank temperature
AI
10
Outdoor temperature
AI
11
Boiler Operation Status
AI
12
Appendix C. Vendor Information – Navien