28 Vendor Information – Navien
Point Name
BACnet
Object Type
BACnet
Object ID
Primary total flow
AI
106
Average primary Supply temperature
AI
107
Average primary return temperature
AI
108
System Supply temperature
AI
109
System Return temperature
AI
110
Error occurrence unit number
AI
111
Main Error code
AI
112
Main Operation Status
AI
1
Main Error code
AI
2
Main Current Heat capacity
AI
4
Main Supply temperature
AI
5
Main Return temperature
AI
6
Main Maximum Heat capacity
AI
8
Main Exhaust temperature
AI
9
Main Total time after installation
AI
10
Main Number of CH operation
AI
11
Main Total time of CH operation
AI
12
Main Current amount of gas
AI
13
Main Total amount of gas
AI
14
Sub01 Operation Status
AI
1001
Sub01 Main Error code
AI
1002
Sub01 Current Heat capacity
AI
1004
Sub01 Supply temperature
AI
1005
Sub01 Return temperature
AI
1006
Sub01 Maximum Heat capacity
AI
1008
Sub01 Exhaust temperature
AI
1009
Sub01 Total time after installation
AI
1010
Sub01 Number of CH operation
AI
1011
Sub01 Total time of CH operation
AI
1012
Sub01 Current amount of gas
AI
1013
Sub01 Total amount of gas
AI
1014
Sub02 Operation Status
AI
2001
Sub02 Main Error code
AI
2002
Sub02 Current Heat capacity
AI
2004
Sub02 Supply temperature
AI
2005
Point Name
BACnet
Object Type
BACnet
Object ID
Sub26 Burner op state
BI
26001
Sub26 Frozen protection mode
BI
26002
Sub26 Error state
BI
26006
Sub26 Boiler enable status
BI
26007
Sub26 Boiler pump op Status
BI
26008
Sub27 Burner op state
BI
27001
Sub27 Frozen protection mode
BI
27002
Sub27 Error state
BI
27006
Sub27 Boiler enable status
BI
27007
Sub27 Boiler pump op Status
BI
27008
Sub28 Burner op state
BI
28001
Sub28 Frozen protection mode
BI
28002
Sub28 Error state
BI
28006
Sub28 Boiler enable status
BI
28007
Sub28 Boiler pump op Status
BI
28008
Sub29 Burner op state
BI
29001
Sub29 Frozen protection mode
BI
29002
Sub29 Error state
BI
29006
Sub29 Boiler enable status
BI
29007
Sub29 Boiler pump op Status
BI
29008
Sub30 Burner op state
BI
30001
Sub30 Frozen protection mode
BI
30002
Sub30 Error state
BI
30006
Sub30 Boiler enable status
BI
30007
Sub30 Boiler pump op Status
BI
30008
Sub31 Burner op state
BI
31001
Sub31 Frozen protection mode
BI
31002
Sub31 Error state
BI
31006
Sub31 Boiler enable status
BI
31007
Sub31 Boiler pump op Status
BI
31008
Cascade total units
AI
101
Cascade Operating units
AI
102
Cascade On/Off state
AI
103
CC Average Heating capacity
AI
104
CC Maximum Heating capacity
AI
105