Troubleshooting 

Appendix A.4    LED Diagnostics for 

Communications Between Gateway and 

Devices

See the diagram below for gateway LED Locations.

Diagnostic LEDs

Tag

Description

SS

The SS LED will light if the unit is not getting a response 

from one or more of the configured devices.

ERR

The SYS ERR LED will go on solid indicating there is 

a system error. If this occurs, immediately report the 

related “system error” shown in the error screen of the 

FS-GUI interface to support for evaluation.

PWR

This is the power light and should always show steady 

green when the unit is powered.

TX

The TX LED will flash when a message is received on 

the serial port on the 3-pin connector. 

If the serial port is not used, this LED is non-

operational

. TX1 applies to the R1 connection while 

TX2 applies to the R2 connection.

RX

The RX LED will flash when a message is sent on the 

serial port on the 3-pin connector.

If the serial port is not used, this LED is non-

operational

. RX1 applies to the R1 connection while 

RX2 applies to the R2 connection.

Figure 31: Diagnostic LEDs

Appendix A.5    Taking a FieldServer 

Diagnostic Capture

When there is a problem on-site that cannot easily be resolved, 

perform a diagnostic capture before contacting support so that 

support can quickly solve the problem. There are two methods for 

taking diagnostic captures:

 

FieldServer Toolbox:

This method requires installation of the FS Toolbox program. A 

FS Toolbox diagnostic capture takes a snapshot of the loaded 

configuration files and a log of all the communications on the 

serial ports over a specified period of time. If the problem occurs 

over an Ethernet connection, then take a Wire Shark capture.

 

Gateway’s FS-GUI Page:

This method doesn’t require downloading software. The 

diagnostic capture utilities are embedded in the FS-GUI web 

interface. Starting a diagnostic capture takes a snapshot of the 

loaded configuration files and a log of all the communications 

over a specified period of time. This works for both serial and 

Ethernet connections. 

Note

The information in the zipped files contains everything 

support needs to quickly resolve problems that occur 

on-site.

1.  

Ethernet Port

Figure 32: Ethernet Port Location

3.  Connect a standard Cat-5 Ethernet cable between the PC and 

gateway.

Содержание Modbus/BACnet Gateway

Страница 1: ...e For Interfacing Navien Products To Building Automation Systems and SMC Cloud BACnet MS TP BACnet IP and Modbus TCP IP APPLICABILITY EFFECTIVITY Explains Modbus BACnet gateway and how to install it T...

Страница 2: ...RS 485 R2 port to the field protocol cabling Section 4 2 5 Connect power to gateway s 3 pin connector Section 4 5 6 Connect a PC to the gateway via Ethernet cable or by the gateway s Wi Fi Access Poi...

Страница 3: ...ver Clearing Profiles 14 7 NETWORK SETTINGS 15 7 1 Navigate to the FS GUI Network Settings 15 7 2 Change the Gateway IP Address 16 7 2 1 Update Wired Network Settings 16 7 2 2 Update Wi Fi Client Sett...

Страница 4: ...Resistor DIP Switch 9 Figure 9 Required Current Draw for the Gateway 9 Figure 10 PCB Power Connections 9 Figure 11 External Power Connections 9 Figure 12 Ethernet Port Location 10 Figure 13 Web App S...

Страница 5: ...by an independent laboratory which verifies that the product correctly implements the BACnet features claimed in the listing The mark is a symbol of a high quality BACnet product Go to www BACnetInter...

Страница 6: ...Navien s devices hereafter simply called device connected to the gateway and automatically configures them for BACnet IP BACnet MS TP and Modbus TCP IP It is not necessary to download any configurati...

Страница 7: ...nected serial device MUST have the same baud rate data bits stop bits and parity settings as the gateway Figure 4 specifies the device serial port settings required to communicate with the gateway Por...

Страница 8: ...res and notes The R1 and R2 DIP Switches apply settings to the respective serial port If the gateway is already powered on DIP switch settings will not take effect unless the unit is power cycled 4 1...

Страница 9: ...ment for Gateway Current DrawType Navien Gateway Family 12 VDC 24 V DC AC GXXX001932 Typical 250 mA 125 mA Note These values are nominal and a safety margin should be added to the power supply of the...

Страница 10: ...the Subnet of the Connected PC The default IP Address for the gateway is 192 168 1 24 Subnet Mask is 255 255 255 0 If the PC and gateway are on different IP networks assign a static IP Address to the...

Страница 11: ...ay with Wi Fi To connect to the gateway Wi Fi Access Point 1 Click the icon found in the bottom right corner of the computer screen to open the available Wireless Network Connections 2 Select the desi...

Страница 12: ...eldServer Toolbox Section 5 1 1 2 click the Connect button Note 2 Once at the Web App splash page click the Login button Figure 13 Web App Splash Page 3 Enter the previously set up or default username...

Страница 13: ...g See Appendix A 4 for additional information and images 2 Confirm the software shows communication without errors Go to Appendix A 2 for instructions 6 2 Setting Gateway Configuration Parameters 1 Se...

Страница 14: ...ent value default 50 000 The values allowed for a BACnet Device Instance can range from 1 to 4 194 303 2 To assign a specific Device Instance or range change the Node_Offset value as needed using the...

Страница 15: ...igurator page click on the blue Diagnostics Debugging button in the bottom right corner of the screen Figure 23 Web Configurator Page Diagnostics Button Figure 24 FS GUI Landing Page 3 Click the orang...

Страница 16: ...ion toWi Fi Client 7 2 Change the Gateway IP Address Configure the IP settings of the gateway in the following methods When using the Ethernet port to connect to the local network Section 7 2 1 When c...

Страница 17: ...GUI Common Network Settings Note The fields below the update button show the settings as they were set in the IP Settings or Wi Fi Client pages They are not editable on the Common page Figure 27 FS GU...

Страница 18: ...Address of the gateway into the web browser or use the FieldServer Toolbox to connect to the gateway 2 Click on Diagnostics Button then click on view and then on connections 3 If there are any errors...

Страница 19: ...tion Figure 31 Diagnostic LEDs Appendix A 5 Taking a FieldServer Diagnostic Capture When there is a problem on site that cannot easily be resolved perform a diagnostic capture before contacting suppor...

Страница 20: ...ved on the PC b Choose Open to launch explorer and have it point directly at the correct folder c Send the Diagnostic zip file to technical support Appendix A 5 2 Using FS GUI Diagnostic Capture via F...

Страница 21: ...ture to be downloaded to the local PC 6 Send the diagnostic zip file to technical support Note Diagnostic captures of BACnet MS TP communication are output in a PCAP file extension which is compatible...

Страница 22: ...nected to the same subnet they must be assigned unique Network_Number values On the main Web Configuration screen update the BACnet Network Number field and click submit The default value is 50 Figure...

Страница 23: ...Fi Settings then click on the System Restart to restart the gateway and activate the Wi Fi settings Note If the FS GUI was open in a browser via Wi Fi the browser will need to be updated with the new...

Страница 24: ...24 Additional Information Appendix B 6 Physical Dimension Drawing Power Port R2 Serial Port Wi Fi Antenna Socket R1 Serial Port Figure 39 Modbus BACnet Gateway Part Number GXXX001932 Dimensions...

Страница 25: ...CH supply min temperature setting AV 16 CH supply max temperature setting AV 17 CH return min temperature setting AV 18 CH return max temperature setting AV 19 Appendix C 1 NFB C Single Boiler Modbus...

Страница 26: ...rror state BI 4006 Sub04 Boiler enable status BI 4007 Sub04 Boiler pump op Status BI 4008 Point Name BACnet ObjectType BACnet Object ID Sub05 Burner op state BI 5001 Sub05 Frozen protection mode BI 50...

Страница 27: ...mode BI 25002 Sub25 Error state BI 25006 Sub25 Boiler enable status BI 25007 Sub25 Boiler pump op Status BI 25008 Point Name BACnet ObjectType BACnet Object ID Sub12 Burner op state BI 12001 Sub12 Fr...

Страница 28: ...tatus AI 2001 Sub02 Main Error code AI 2002 Sub02 Current Heat capacity AI 2004 Sub02 Supply temperature AI 2005 Point Name BACnet ObjectType BACnet Object ID Sub26 Burner op state BI 26001 Sub26 Froz...

Страница 29: ...nt of gas AI 7013 Sub07 Total amount of gas AI 7014 Sub08 Operation Status AI 8001 Sub08 Main Error code AI 8002 Point Name BACnet ObjectType BACnet Object ID Sub02 Return temperature AI 2006 Sub02 Ma...

Страница 30: ...n AI 13011 Sub13 Total time of CH operation AI 13012 Sub13 Current amount of gas AI 13013 Sub13 Total amount of gas AI 13014 Point Name BACnet ObjectType BACnet Object ID Sub08 Current Heat capacity A...

Страница 31: ...time after installation AI 19010 Sub19 Number of CH operation AI 19011 Sub19 Total time of CH operation AI 19012 Point Name BACnet ObjectType BACnet Object ID Sub14 Operation Status AI 14001 Sub14 Ma...

Страница 32: ...Sub25 Maximum Heat capacity AI 25008 Sub25 Exhaust temperature AI 25009 Sub25 Total time after installation AI 25010 Point Name BACnet ObjectType BACnet Object ID Sub19 Current amount of gas AI 19013...

Страница 33: ...acity AI 31004 Sub31 Supply temperature AI 31005 Sub31 Return temperature AI 31006 Sub31 Maximum Heat capacity AI 31008 Point Name BACnet ObjectType BACnet Object ID Sub25 Number of CH operation AI 25...

Страница 34: ...ting AV 2 SH return setpoint setting AV 3 DHW setpoint setting AV 4 Error reset command AV 5 Boiler setpoint in DHW operation AV 7 Outdoor reset curve heatload setting AV 9 Maximum outdoor temperature...

Страница 35: ...r a special tool to gain access This device must not be connected to a LAN segment with outdoor wiring Appendix D 1 Specifications Gateway Part Number GXXX001932 Electrical Connections One 3 pin Phoen...

Страница 36: ...have been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables or to any damage resulting from battery leakage In all cases Sierra Monitor Corpo...

Страница 37: ...Memo...

Страница 38: ...Memo...

Страница 39: ...net MS TP BACnet IP and Modbus TCP IP protocols For technical support please contact us at 800 519 8794 800 519 8794 www NavienInc com 20 Goodyear lrvine CA 92618 Installation Operation Manual Modbus...

Отзывы: