background image

Installation Guide for NCPE Split-System Condensing Units

10

Electrical - High Voltage

n

i

NOMINAL 

VOLTAGE

MINIMUM 

VOLTAGE

MAXIMUM 

VOLTAGE

208-230

197

253

Please refer to pages 15, 16 or 17 for proper 

capacitor sizing.

High Voltage Power Supply

n

i

LIVE ELECTRICAL COMPONENTS! 

During installation, testing, servicing 

and troubleshooting of this product, 

it may be necessary to work with live 

electrical components. Failure to follow 

all electrical safety precautions when 

exposed to live electrical components 

could result in death or serious injury.

!

WARNING

The high voltage power supply must agree with the 

equipment nameplate.

OR

Make certain that the volts, hertz, and phase 

correspond  to  that  specified  on  the  unit  rating 

plate, and that the service provided by the utility is 

sufficient to handle the additional load imposed by 

this equipment.
Power wiring must comply with national, state, and 

local codes.
Follow instructions on unit wiring diagram located on 

the inside of the access door, or cabinet and  in the 

wiring diagrams included with the unit.

Field line wiring by others

CC

C

S

R

COMP

CFM

C

H

F

LPS

HPS

CC

208

V

C

+

-

230

V

XFMER

*FIELD SUPPLIED

CC

L1

L2

LINE VOLTAGE

LOW VOLTAGE

C

Y

*FIELD SUPPLIED

T-STAT

ON

OFF

Disconnect 

Switch

Thru-the-Wall 

Condensing Unit

Install a separate disconnect 

switch at the location of the 

through the wall unit.

Ground the unit per national, 

state, and local code 

requirements.

Содержание 1000 SERIES

Страница 1: ...639 1674 HEATING A C EQUIPMENT NATIONAL COMFORT PRODUCTS Thru the Wall Condensing Units This unit should be installed in an OUTSIDE WALL FOR THRU THE WALL INSTALLATION ONLY Please read the entire inst...

Страница 2: ...gh Voltage and Power Supply Page 10 Start Up Sequence of Operations Page 11 Refrigerant Charging Page 12 Maintenance Checkout Procedure Page 13 Important Before Removing a Warranty Compressor Page 14...

Страница 3: ...ntly grounded Failure to do so can cause electrical shock resulting in severe personal injury or death WARNING These instructions are intended as an aid to qualified licensed service personnel for pro...

Страница 4: ...instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should further information be desired or should particular...

Страница 5: ...of these decorative grilles The less resistive these grilles are to air flow the better the units performance will be Outdoor louvers provided by others must be approved by NCP to maintain unit perfor...

Страница 6: ...Liquid Line Pressure Drop 50 PSI Subtract 43 PSI for each foot of Liquid Lift if any Do Not Exceed this value when selecting Liquid Line Field Installation Install the units per the manufacturer s re...

Страница 7: ...the condensing unit should not block access to major components Refrigerant lines should not be in direct contact with the floor or ceiling joists Use insulated or suspension type hangers When refrig...

Страница 8: ...l equivalent length of refrigerant lines exceeds 50 ft Leak Checking Leak checking of refrigerant line braze joints and evaporator unit using dry nitrogen 1 Install service port cap of the vapor line...

Страница 9: ...aporator coil The vacuum pump can now be disconnected Electrical Connections NOTE Make certain that the volts hertz and phase correspond to that specified on the unit rating plate and that the service...

Страница 10: ...equipment nameplate OR Make certain that the volts hertz and phase correspond to that specified on the unit rating plate and that the service provided by the utility is sufficient to handle the additi...

Страница 11: ...ubcooling in cooling mode is the only recommended method of charging above 55 F ambient outdoor temperature For best results the indoor temperature should be kept between 70 F to 80 F Note It is impor...

Страница 12: ...lar CAUTION Low Suction Pressure Operation Compressor Damage Do not operate with a restricted suction Do not operate with the low pressure cut out bridged Do not operate compressor without enough syst...

Страница 13: ...age Check exposed surfaces for corrosion Replace or paint part as required This maintenance is critical to prevent stains and damage to exterior surface of building 5 Inspect refrigerant piping for le...

Страница 14: ...HM Reading between Terminals C R __________ 5 Compressor Winding OHM Reading between Terminals R S __________ 6 Compressor Winding OHM Reading between Terminals C Ground __________ 7 Compressor Windin...

Страница 15: ...Installation Guide for NCPE Split System Condensing Units 15...

Страница 16: ...Installation Guide for NCPE Split System Condensing Units 16...

Страница 17: ...Installation Guide for NCPE Split System Condensing Units 17...

Страница 18: ...10 15 3 25 208 230 60 1 10 17 75 30 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 9 0 56 3 10 9 62 9 12 8 67 8 RLA Amps LRA Amps FAN MOTOR 0 25 1500 1 4 0 25 1500 1 4 0 25 1500...

Страница 19: ...12 13 20 208 230 60 1 10 15 3 25 208 230 60 1 10 18 56 30 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 9 0 56 3 10 9 62 9 13 5 72 5 RLA Amps LRA Amps FAN MOTOR 0 25 1500 1 4 0...

Страница 20: ...NOMINAL CAPACITY B HR 18 000 23 000 27 200 ELECTRICAL 208 230 60 1 12 13 20 208 230 60 1 10 15 3 25 208 230 60 1 10 17 75 30 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 9 0 56...

Страница 21: ...00 28 400 ELECTRICAL 208 230 60 1 12 13 47 20 208 230 60 1 12 15 13 20 208 230 60 1 10 19 08 30 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 9 0 56 3 10 3 61 6 13 50 72 5 RLA Am...

Страница 22: ...ondenser Coil 14208361 14208360 14208360 9 Motor 0 25 HP 1500 RPM 14270049 14270049 14270049 10 14 Prop Fan 14214033 14214033 14214033 11 Motor Mount 14270102 14270102 14270102 12 Access Panel 1000 14...

Страница 23: ...denser Coil 14208356 14208357 14208357 9 Motor 0 25 HP 1500 RPM 14270049 14270049 14270049 10 14 Prop Fan 14214033 14214033 14214033 11 Motor Mount 14270102 14270102 14270102 12 Access Panel 3000 1425...

Страница 24: ...High Pressure Switch 14265027 14265027 14265027 5 Compressor 14210241 14210242 14210243 6 Liquid Service Valve 14258603A 14258603A 14258603A 7 Vapor Service Valve 14258606A 14258606A 14258606A 8 Conde...

Страница 25: ...8603A 14258603A 14258603A 7 Vapor Service Valve 14258612 14258612 14258612 8 Condenser Coil 14208372 14208371 14208371 9 Motor 14270056 14270056 14270056 10 Prop Fan 14214038 14214038 14214038 11 Moto...

Страница 26: ...As an option we offer an Insulated Sound Cover for installation over the inside cover of the unit Sound Without Indoor Cover 70 4 dba Standard AHRI 350 2008 Sound With Indoor Cover 68 3 dba Standard...

Страница 27: ...tional Comfort in specifications drawings or otherwise and whether or not National Comfort s goods are specifically designed and or manufactured by National Comfort for Customer s use or purpose 4 LIM...

Страница 28: ...ort after one year from the date of installation or after 20 months from the date of manufacture of the compressor as determined by the compressor serial number whichever occurs first but before the e...

Страница 29: ...essure with service door reattached ENGINEERING SPECIFICATION GUIDE 4 Technical Data Limitations All installations should factor a proper building heat gain along with appropriate duct sizing and elec...

Страница 30: ..._______________________ ________________________________________________________________________ ________________________________________________________________________ ______________________________...

Страница 31: ...______________________ ________________________________________________________________________ ________________________________________________________________________ _______________________________...

Страница 32: ...Comfort Products 539 Dunksferry Road Bensalem PA 19020 5908 800 523 7138 Fax 215 639 1674 HEATING A C EQUIPMENT NATIONAL COMFORT PRODUCTS Manual NCPE Condensing Unit Installation Instructions 14299118...

Отзывы: