National Comfort Product 1000 SERIES Скачать руководство пользователя страница 7

Installation Guide for NCPE Split-System Condensing Units

7

Step 3:

Flux the copper tube and insert into the stub. Braze 

the joint. No flux is necessary if a low to zero-silver 

braze alloy is used.

Step 4:

After brazing, quench with a wet rag to cool the 

joint and remove any flux residue. Evacuate, 

purge or charge the connecting lines per the unit 

manufacturer’s instructions.

Step 5:

This is not a back seating valve.  To open the valve 

remove the valve cap with an adjustable wrench. 

Insert a 3/16” or 5/16” hex wrench into the stem.  

Back out counter-clockwise until the valve stem just 

touches the retaining ring.

Step 6:

Replace the valve cap finger tight then tighten an 

additional 1/12 turn or 1/2 hex flat. A metal-to-metal 

seal is now complete. Complete normal factory 

recommended procedure

s.

1.

 The unit has internally mounted service valves. Field tubing 

may be routed through the locations provided in either the top or 

rear flange. Care should be taken not to block access to internal 

components. Seal unused knockouts with high grade sealant. 

Gaskets are provided for liquid and suction lines.

Note: Always use refrigeration grade copper 

tubing that is internally clean and dry for 

refrigerant lines. Use clean hard drawn copper 

tubing if no appreciable amount of bending is 

necessary. If soft copper is used, avoid sharp 

bends which may cause a restriction. Always 

use heat sink materials during brazing to 

prevent damage to service valves (See Page 6).

2.

 Run refrigerant lines as directly as possible. Field piping 

inside the condensing unit should not block access to major 

components. Refrigerant lines should not be in direct contact 

with the floor or ceiling joists. Use insulated or suspension type 

hangers. When refrigerant lines run through a wall, seal openings 

around the lines with a flexible material to avoid vibration to the 

structure.

3

. Insulate the vapor line with a minimum 1/2

"

 foam rubber 

or other type insulation having an adequate vapor barrier. For 

indoor units with a TXV, a liquid line filter drier must be installed 

(SPORLAN #C-083-S or similar).

Caution: Dry nitrogen should always be supplied 

through the tubing while it is being brazed, 

as the high temperature required for brazing 

will cause oxidation of the copper unless an 

inert  atmosphere  is  provided.  The  flow  of  dry 

nitrogen should continue until the joints have 

cooled. Always use a pressure regulator and 

safety valve to ensure that only low pressure 

nitrogen is introduced into the tubing. Only a 

small  flow  is  necessary  to  displace  air  and 

prevent oxidation.

4.

 When tubing installation is completed, seal openings around 

tubing where tubing enters the unit cabinet.

5.

 Standard refrigeration piping practices must be employed 

when installing traps. When installing the condenser below the 

evaporator, the suction line must be trapped with an inverted 

trap the height of the evaporator coil. Consult the factory when 

total equivalent length of refrigerant lines exceeds 50 ft.

6.

 Install the refrigerant lines using the following procedure (See 

Page 5).
 

a

.  Remove the service port caps and Schrader Cores of the 

liquid line service valve and the vapor line service valve of 

the condensing unit. Connect low pressure dry nitrogen 

to the liquid line valve service port.

Содержание 1000 SERIES

Страница 1: ...639 1674 HEATING A C EQUIPMENT NATIONAL COMFORT PRODUCTS Thru the Wall Condensing Units This unit should be installed in an OUTSIDE WALL FOR THRU THE WALL INSTALLATION ONLY Please read the entire inst...

Страница 2: ...gh Voltage and Power Supply Page 10 Start Up Sequence of Operations Page 11 Refrigerant Charging Page 12 Maintenance Checkout Procedure Page 13 Important Before Removing a Warranty Compressor Page 14...

Страница 3: ...ntly grounded Failure to do so can cause electrical shock resulting in severe personal injury or death WARNING These instructions are intended as an aid to qualified licensed service personnel for pro...

Страница 4: ...instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should further information be desired or should particular...

Страница 5: ...of these decorative grilles The less resistive these grilles are to air flow the better the units performance will be Outdoor louvers provided by others must be approved by NCP to maintain unit perfor...

Страница 6: ...Liquid Line Pressure Drop 50 PSI Subtract 43 PSI for each foot of Liquid Lift if any Do Not Exceed this value when selecting Liquid Line Field Installation Install the units per the manufacturer s re...

Страница 7: ...the condensing unit should not block access to major components Refrigerant lines should not be in direct contact with the floor or ceiling joists Use insulated or suspension type hangers When refrig...

Страница 8: ...l equivalent length of refrigerant lines exceeds 50 ft Leak Checking Leak checking of refrigerant line braze joints and evaporator unit using dry nitrogen 1 Install service port cap of the vapor line...

Страница 9: ...aporator coil The vacuum pump can now be disconnected Electrical Connections NOTE Make certain that the volts hertz and phase correspond to that specified on the unit rating plate and that the service...

Страница 10: ...equipment nameplate OR Make certain that the volts hertz and phase correspond to that specified on the unit rating plate and that the service provided by the utility is sufficient to handle the additi...

Страница 11: ...ubcooling in cooling mode is the only recommended method of charging above 55 F ambient outdoor temperature For best results the indoor temperature should be kept between 70 F to 80 F Note It is impor...

Страница 12: ...lar CAUTION Low Suction Pressure Operation Compressor Damage Do not operate with a restricted suction Do not operate with the low pressure cut out bridged Do not operate compressor without enough syst...

Страница 13: ...age Check exposed surfaces for corrosion Replace or paint part as required This maintenance is critical to prevent stains and damage to exterior surface of building 5 Inspect refrigerant piping for le...

Страница 14: ...HM Reading between Terminals C R __________ 5 Compressor Winding OHM Reading between Terminals R S __________ 6 Compressor Winding OHM Reading between Terminals C Ground __________ 7 Compressor Windin...

Страница 15: ...Installation Guide for NCPE Split System Condensing Units 15...

Страница 16: ...Installation Guide for NCPE Split System Condensing Units 16...

Страница 17: ...Installation Guide for NCPE Split System Condensing Units 17...

Страница 18: ...10 15 3 25 208 230 60 1 10 17 75 30 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 9 0 56 3 10 9 62 9 12 8 67 8 RLA Amps LRA Amps FAN MOTOR 0 25 1500 1 4 0 25 1500 1 4 0 25 1500...

Страница 19: ...12 13 20 208 230 60 1 10 15 3 25 208 230 60 1 10 18 56 30 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 9 0 56 3 10 9 62 9 13 5 72 5 RLA Amps LRA Amps FAN MOTOR 0 25 1500 1 4 0...

Страница 20: ...NOMINAL CAPACITY B HR 18 000 23 000 27 200 ELECTRICAL 208 230 60 1 12 13 20 208 230 60 1 10 15 3 25 208 230 60 1 10 17 75 30 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 9 0 56...

Страница 21: ...00 28 400 ELECTRICAL 208 230 60 1 12 13 47 20 208 230 60 1 12 15 13 20 208 230 60 1 10 19 08 30 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 9 0 56 3 10 3 61 6 13 50 72 5 RLA Am...

Страница 22: ...ondenser Coil 14208361 14208360 14208360 9 Motor 0 25 HP 1500 RPM 14270049 14270049 14270049 10 14 Prop Fan 14214033 14214033 14214033 11 Motor Mount 14270102 14270102 14270102 12 Access Panel 1000 14...

Страница 23: ...denser Coil 14208356 14208357 14208357 9 Motor 0 25 HP 1500 RPM 14270049 14270049 14270049 10 14 Prop Fan 14214033 14214033 14214033 11 Motor Mount 14270102 14270102 14270102 12 Access Panel 3000 1425...

Страница 24: ...High Pressure Switch 14265027 14265027 14265027 5 Compressor 14210241 14210242 14210243 6 Liquid Service Valve 14258603A 14258603A 14258603A 7 Vapor Service Valve 14258606A 14258606A 14258606A 8 Conde...

Страница 25: ...8603A 14258603A 14258603A 7 Vapor Service Valve 14258612 14258612 14258612 8 Condenser Coil 14208372 14208371 14208371 9 Motor 14270056 14270056 14270056 10 Prop Fan 14214038 14214038 14214038 11 Moto...

Страница 26: ...As an option we offer an Insulated Sound Cover for installation over the inside cover of the unit Sound Without Indoor Cover 70 4 dba Standard AHRI 350 2008 Sound With Indoor Cover 68 3 dba Standard...

Страница 27: ...tional Comfort in specifications drawings or otherwise and whether or not National Comfort s goods are specifically designed and or manufactured by National Comfort for Customer s use or purpose 4 LIM...

Страница 28: ...ort after one year from the date of installation or after 20 months from the date of manufacture of the compressor as determined by the compressor serial number whichever occurs first but before the e...

Страница 29: ...essure with service door reattached ENGINEERING SPECIFICATION GUIDE 4 Technical Data Limitations All installations should factor a proper building heat gain along with appropriate duct sizing and elec...

Страница 30: ..._______________________ ________________________________________________________________________ ________________________________________________________________________ ______________________________...

Страница 31: ...______________________ ________________________________________________________________________ ________________________________________________________________________ _______________________________...

Страница 32: ...Comfort Products 539 Dunksferry Road Bensalem PA 19020 5908 800 523 7138 Fax 215 639 1674 HEATING A C EQUIPMENT NATIONAL COMFORT PRODUCTS Manual NCPE Condensing Unit Installation Instructions 14299118...

Отзывы: