background image

Installation Guide for NCPE Split-System Condensing Units

13

Air Flow Chart

1000, 3000, & 4000 Series

Model

Air Handler 

Tap

CFM

Static

NCPE-418

NCPAH-24-A

2

580

0.1

NCPE-418

B6VMMX24

6, 8

650

0.1

NCPE-424

NCPAH-24-A

5

830

0.1

NCPE-424

B6VMMX24

5, 7, 8

850

0.1

NCPE-430

NCPAH-36-A

1

950

0.1

NCPE-430

B6VMMX36

1, 5, 6

950

0.1

Air Flow Chart

5000 Series

Model

Air Handler 

Tap

CFM

Static

NCPE-418 NCPAH-24-A

2

580

0.1

NCPE-424 NCPAH-24-A

5

820

0.1

NCPE-430 NCPAH-36-A

1

950

0.15

NCPE-418 NCPAH-24-M

1

620

0.1

NCPE-424 NCPAH-24-M

4

860

0.1

NCPE-430 NCPAH-36-M

2

1045

0.15

Maintenance

1. 

Annually clean the inside of the unit to keep the weep holes 

in the base pan and in the fan scrolls open to assure proper 

drainage of water from the unit.

2.

 Keep the condenser coil clean and free of anything that 

restricts free air flow. On sea coast applications the condenser 

coil should be washed periodically to remove salt accumulation.

3.

 Reduced indoor air flow through a duct system will cause 

indoor coil to ice up in cooling. If this condition is allowed to 

continue, premature system failure will result. Indoor air filters 

should be cleaned and changed regularly.

4. 

Annually check units mounting to structure to ensure 

integrity. Seal between cabinet and/or sleeve for air or water 

leakage. Check exposed surfaces for corrosion. Replace or paint 

part as required. This maintenance is critical to prevent stains 

and damage to exterior surface of building.

5.

 Inspect refrigerant piping for leaks and suction line insulation. 

Improper insulation can cause condensate water damage.

6.

 Pressure and temperature readings of high and low side 

of system should be checked for proper super heat and/or 

subcooling. Correct if required.

7.

 Inspect motor mount, amps to nameplate, hubs for tightness, 

balance, and rust or corrosion.

8. 

Inspect wire connection for evidence of arcing, overheating 

and deterioration

Checkout Procedures and 

Troubleshooting

CHECKOUT PROCEDURE

After installation has been completed, it is recommended 

that the system be checked against the following list:

1. Leak check refrigerant lines.

 

2.  Properly insulate suction lines and 

fittings.

 

3.  Properly secure and isolate all 

refrigerant lines.

 

4.  Seal passages through masonry. 

If mortar is used, prevent mortar 

from coming into direct contact with 

copper tubing.

 

5.  Verify that all electrical connections 

are tight.

 

6.  Observe outdoor fan during on cycle 

for clearance and smooth operation.

 

7.  Be sure that indoor line drains freely. 

Pour water into drain pan.

 

8.  Be sure that supply registers 

and return grilles are open and 

unobstructed.

 

9.  Be sure that a return air filter is 

installed.

 

10.  Be sure that the correct airflow 

setting is used. (Indoor blower motor)

 

11.  Operate complete system in each 

mode to ensure safe operation.

 

Содержание 1000 SERIES

Страница 1: ...639 1674 HEATING A C EQUIPMENT NATIONAL COMFORT PRODUCTS Thru the Wall Condensing Units This unit should be installed in an OUTSIDE WALL FOR THRU THE WALL INSTALLATION ONLY Please read the entire inst...

Страница 2: ...gh Voltage and Power Supply Page 10 Start Up Sequence of Operations Page 11 Refrigerant Charging Page 12 Maintenance Checkout Procedure Page 13 Important Before Removing a Warranty Compressor Page 14...

Страница 3: ...ntly grounded Failure to do so can cause electrical shock resulting in severe personal injury or death WARNING These instructions are intended as an aid to qualified licensed service personnel for pro...

Страница 4: ...instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should further information be desired or should particular...

Страница 5: ...of these decorative grilles The less resistive these grilles are to air flow the better the units performance will be Outdoor louvers provided by others must be approved by NCP to maintain unit perfor...

Страница 6: ...Liquid Line Pressure Drop 50 PSI Subtract 43 PSI for each foot of Liquid Lift if any Do Not Exceed this value when selecting Liquid Line Field Installation Install the units per the manufacturer s re...

Страница 7: ...the condensing unit should not block access to major components Refrigerant lines should not be in direct contact with the floor or ceiling joists Use insulated or suspension type hangers When refrig...

Страница 8: ...l equivalent length of refrigerant lines exceeds 50 ft Leak Checking Leak checking of refrigerant line braze joints and evaporator unit using dry nitrogen 1 Install service port cap of the vapor line...

Страница 9: ...aporator coil The vacuum pump can now be disconnected Electrical Connections NOTE Make certain that the volts hertz and phase correspond to that specified on the unit rating plate and that the service...

Страница 10: ...equipment nameplate OR Make certain that the volts hertz and phase correspond to that specified on the unit rating plate and that the service provided by the utility is sufficient to handle the additi...

Страница 11: ...ubcooling in cooling mode is the only recommended method of charging above 55 F ambient outdoor temperature For best results the indoor temperature should be kept between 70 F to 80 F Note It is impor...

Страница 12: ...lar CAUTION Low Suction Pressure Operation Compressor Damage Do not operate with a restricted suction Do not operate with the low pressure cut out bridged Do not operate compressor without enough syst...

Страница 13: ...age Check exposed surfaces for corrosion Replace or paint part as required This maintenance is critical to prevent stains and damage to exterior surface of building 5 Inspect refrigerant piping for le...

Страница 14: ...HM Reading between Terminals C R __________ 5 Compressor Winding OHM Reading between Terminals R S __________ 6 Compressor Winding OHM Reading between Terminals C Ground __________ 7 Compressor Windin...

Страница 15: ...Installation Guide for NCPE Split System Condensing Units 15...

Страница 16: ...Installation Guide for NCPE Split System Condensing Units 16...

Страница 17: ...Installation Guide for NCPE Split System Condensing Units 17...

Страница 18: ...10 15 3 25 208 230 60 1 10 17 75 30 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 9 0 56 3 10 9 62 9 12 8 67 8 RLA Amps LRA Amps FAN MOTOR 0 25 1500 1 4 0 25 1500 1 4 0 25 1500...

Страница 19: ...12 13 20 208 230 60 1 10 15 3 25 208 230 60 1 10 18 56 30 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 9 0 56 3 10 9 62 9 13 5 72 5 RLA Amps LRA Amps FAN MOTOR 0 25 1500 1 4 0...

Страница 20: ...NOMINAL CAPACITY B HR 18 000 23 000 27 200 ELECTRICAL 208 230 60 1 12 13 20 208 230 60 1 10 15 3 25 208 230 60 1 10 17 75 30 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 9 0 56...

Страница 21: ...00 28 400 ELECTRICAL 208 230 60 1 12 13 47 20 208 230 60 1 12 15 13 20 208 230 60 1 10 19 08 30 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 9 0 56 3 10 3 61 6 13 50 72 5 RLA Am...

Страница 22: ...ondenser Coil 14208361 14208360 14208360 9 Motor 0 25 HP 1500 RPM 14270049 14270049 14270049 10 14 Prop Fan 14214033 14214033 14214033 11 Motor Mount 14270102 14270102 14270102 12 Access Panel 1000 14...

Страница 23: ...denser Coil 14208356 14208357 14208357 9 Motor 0 25 HP 1500 RPM 14270049 14270049 14270049 10 14 Prop Fan 14214033 14214033 14214033 11 Motor Mount 14270102 14270102 14270102 12 Access Panel 3000 1425...

Страница 24: ...High Pressure Switch 14265027 14265027 14265027 5 Compressor 14210241 14210242 14210243 6 Liquid Service Valve 14258603A 14258603A 14258603A 7 Vapor Service Valve 14258606A 14258606A 14258606A 8 Conde...

Страница 25: ...8603A 14258603A 14258603A 7 Vapor Service Valve 14258612 14258612 14258612 8 Condenser Coil 14208372 14208371 14208371 9 Motor 14270056 14270056 14270056 10 Prop Fan 14214038 14214038 14214038 11 Moto...

Страница 26: ...As an option we offer an Insulated Sound Cover for installation over the inside cover of the unit Sound Without Indoor Cover 70 4 dba Standard AHRI 350 2008 Sound With Indoor Cover 68 3 dba Standard...

Страница 27: ...tional Comfort in specifications drawings or otherwise and whether or not National Comfort s goods are specifically designed and or manufactured by National Comfort for Customer s use or purpose 4 LIM...

Страница 28: ...ort after one year from the date of installation or after 20 months from the date of manufacture of the compressor as determined by the compressor serial number whichever occurs first but before the e...

Страница 29: ...essure with service door reattached ENGINEERING SPECIFICATION GUIDE 4 Technical Data Limitations All installations should factor a proper building heat gain along with appropriate duct sizing and elec...

Страница 30: ..._______________________ ________________________________________________________________________ ________________________________________________________________________ ______________________________...

Страница 31: ...______________________ ________________________________________________________________________ ________________________________________________________________________ _______________________________...

Страница 32: ...Comfort Products 539 Dunksferry Road Bensalem PA 19020 5908 800 523 7138 Fax 215 639 1674 HEATING A C EQUIPMENT NATIONAL COMFORT PRODUCTS Manual NCPE Condensing Unit Installation Instructions 14299118...

Отзывы: