background image

27

 -4     +5    +6 

XP-600 Terminals 

 

1        2      +3 

          

GEM-RECV-XP8 

16 VAC 20 VA 
TRANSFORMER 
NAPCO TRF12 
(OR EQUIVALENT 
SEE WI1372). 
Class 2  
Transformer.   
DO NOT  
connect to  
switched  
outlet. 

+

 RED 

(+) 

 BLACK 

E1 

E2

 

RECHARGEABLE 

BATTERY 

12 VDC 4AH OR 7AH 

This equipment should be installed in accordance with Chapter 
2 of the National Fire Alarm Code, ANSI/NFPA 72-1996 
(National Fire Protection Association Batterymarch Park, 
Quincy MA 02269). and local codes.  Information describing 
proper installation, operation, testing, maintenance, evacuation 
planning, and repair service is to be provided with this 
equipment.  UL Listed Energy Cable is required. 

ALL OUTPUTS  ARE CURRENT LIMITED 

WARNING 

TO PREVENT RISK 

OF ELECTRIC SHOCK 

DISCONNECT TELEPHONE  

LINES PRIOR TO 

SERVICING 

EARTH  

GROUND 

FIRE 

BELL 

P

ro

gr

am

m

abl
e  

Ou
tp

ut

 

PGM 

(-) 

12 

+PWR

 

+10   -11   +12  -13     14    15    16     17    18    19 

 -7    +8      -9 

 GND  +PWR   GND  GREEN 

 TIP   RING 

 TIP 

RING 

PHONE 

(Supervised) 

To RJ31X 

2.2K EOLR 

2.2K EOLR 

(SUPERVISED) 

(E) 

COLD WATER GROUND CONNECTION  
USE ONLY COLD-WATER PIPE OR 
BURIED GROUND ROD.  USE AT LEAST 
#16 AWG WIRE. 

TELCO 

RE
D

 

GR
N

 

GR
AY
 

BR
N

 

FIRE 
PWR 

LO

A

D  

50 mA

 M

AX

REMOTE BUS 

ZONE 3 

(E) 

2.

2K

 

(E) 

2.

2K

 

ZONE 6 

ZONE 5 

(Z)

 

ZONE 1 

(E) 

2.

2K

 

ZONE 4 

(Z)

 

(E) 

RED

 

BL

GRN

 

Fire Loop 
      In 

4-Wire Fire Wiring 

Power  
Out (+) 
Power  
Out (-) 

Power  
In (-) 

Fire Loop 
    Out 

RED  

BLACK  

BROWN 

 

BROWN  

FT2200 

 

Power  
In (+) 

Fire Power 
Ground 

Fire Power 

Fire 

2.2K 

2.2K 

Normally Open  
Zone Wiring

 

Wire the normally open  
contact as shown  
(Zone 4). Program  
the zone for  

Open Circuit

 [06]  

operation. 

ZONE 2 

3.

9K

 

(Z)

 

ZONE 1 

(E) 

2.

2K

 

ZONE 4 

A

U

X

 P

O

W

E

R O

U

T

P

UT 1

0

-1

2

.5

 V

DC 

(1) ALL ZONE RESISTORS MUST BE INSTALLED, EVEN IF 

ZONE IS NOT USED. 

(2) COMBINED STANDBY = KEYPAD C AUX POWER 

C FIRE POWER + PGM CURRENT. 

(3) RESIDENTIAL FIRE REQUIRES A  7AH BATTERY. 
(4) UNIT INTENDED TO BE MOUNTED VERTICALLY ON WALL. 
(5) REFER TO WI1372 FOR COMPATIBLE TWO WIRE SMOKE 

DETECTORS.  DO NOT MIX DIFFERENT MODELS. 

(6) THIS PANEL SHALL BE CHECKED BY A QUALIFIED 

TECHNICIAN AT LEAST ONCE EVERY THREE YEARS. 

(7) THIS PANEL SUPPORTS ONLY ONE SMOKE DETECTOR IN 

ALARM. 

(8) USE ONLY ONE BELL IN RESIDENTIAL FIRE APPLICATION. 
(9) SYSTEM MUST BE TESTED AT LEAST ONCE A WEEK IN THE 

AC/BATTERY MODE AND IN THE BATTERY-ONLY MODE.  
(CONTACT CENTRAL STATION PRIOR TO TESTING) AC MUST 
BE RESTORED AFTER TEST. 

XP-600 WIRING DIAGRAM

 

  (REFER TO PROGRAMMING INSTRUCTIONS WI1373) 

RESIDENTIAL BURG (4 HOUR STANDBY) 

COMBINED STANDBY = 500 mA        BELL = 2.0 AMP 

 

RESIDENTIAL FIRE (24 HOUR STANDBY) 

(3)

 

 

COMBINED STANDBY = 120 mA      BELL = 95 mA 

(1) 

(Z)

 

3.

9K

 

3.

9K

 

3.

9K

 

RPXP6GT 

GOLD 

RED

 

RED

 

RED 

2.2K 

(E) 

EZ

 

Zone 
Doubling

TM

 

Resistors 

(Z) 

GOLD 

WHITE

 

RED

 

3.9K 

ORANGE 

DS1 

TELE LINE IN USE 

RECOMMENDED BATTERIES YUASA 
NP4-12 AND NP7-12 
REPLACE EVERY FIVE YEARS 

Содержание RPXP6GT

Страница 1: ...XP 600 RPXP6GT keypad Control Panel Communicator Installation Instructions WI1372 1 05 NAPCO 2005...

Страница 2: ...Line Cut Detection Answering Machine Override Second Call 50 Event Log Communicator 2 Telephone Numbers Backup Reporting Pager Format Point ID Format Individually Report 6 Users Opening after Alarm R...

Страница 3: ...Battery 12V 4 AH Rechargeable Change Battery every 5 years or as required Maximum Charging Current 165 mA Maximum Input Current 2 58 A Loop Characteristics Loop Voltage 5 Volts Loop Current Zones 1 2...

Страница 4: ...ss PIR Wireless Dual Technology Sensor Wireless Glass Break Detector Relay Board Audio Verification Module Downloading Software for IBM PC Compatibles Software with Interface for IBM PC Compatibles in...

Страница 5: ...ng PCPreset For Site Initiated Downloaded see Auto Download ID Number 93 Local Downloading Wire as shown in Figure 1 Use the power up or A6 method of establishing a connection The power up method is r...

Страница 6: ...eat detectors rather than smoke detectors are recommended in kitchens attics and garages due to conditions that may result in false alarms and improper operation Refer to NFPA Standard 74 National Fir...

Страница 7: ...mA Keypad Operation Keypad zone LEDs indicate zone status W ARMED X READY and HSYSTEM LEDs provide system status The keypad sounder provides feedback beeps for correct and incorrect entries Keypad So...

Страница 8: ...y Follower Zones can be bypassed when the M or N keys on the Keyfob have been programmed for Interior 81 84 Zones programmed as Home Away with Delay Zones can be armed regardless of the state of the E...

Страница 9: ...omatic Bypassing Home Away with Delay Zones From the Keypad Press C B to return protection to Home Away with Delay Zones that have been automatically bypassed Three minutes are allowed to walk through...

Страница 10: ...rogram Mode press the b key XP 600 Commands User Commands A 1 Bell Test Enter this command to turn on the Bell keypad sounder and keypad LEDs for 2 seconds The battery is tested during a Bell Test and...

Страница 11: ...ds when hardwired zones are faulted and for 1 second when zones are restored Wireless Operation Signal Strength While in Fault Find mode the keypad will provide an audible Table 6 and visual Figure 5...

Страница 12: ...lows exit after the panel is armed without setting off an immediate alarm and allows entry only if an Exit Entry Zone 00 has been violated first Zones of this type have a three 3 minute power up delay...

Страница 13: ...it through an Exit Entry Zone 00 after the system is armed allows a user to leave the premises without setting off an immediate alarm Exit Delay may be programmed for up to 255 seconds 4 minutes a val...

Страница 14: ...000 Downloading Software On power up the test timer is sent immediately Follow the commands below to offset the test timer using Quickloader Software From the Status Screen Press F6 Select Miscellaneo...

Страница 15: ...armed or 2 two times when the panel is disarmed Wire as shown in Figure 7 24 Programmable Output Features 2 1 I Fire Program to activate the PGM on a Fire alarm 2 AUX Program to activate the PGM on a...

Страница 16: ...orrect data the panel sends a Sumcheck digit after sending the Subscriber ID and Alarm Code 3 Single Digit 3 1 Format 3 digit Subscriber ID number and a 1 digit Alarm Code will be transmitted 4 No Han...

Страница 17: ...icator Enabled Program to enable the communicator 2 DTMF with Rotary Backup The first attempt to communicate is dialed using the TouchTone method of dialing subsequent attempts are dialed using the pu...

Страница 18: ...st digit of the report code sent the second digit is the zone number of the reporting zone For example if zone 2 has a report code of 3 the report code would be 32 3 1 format Sends only the report Cod...

Страница 19: ...de 62 2 is used to report zones that have been bypassed at the time of the closing report 3 Reserved 4 Reserved 68 Telephone Number 3 1 Opening after Alarm Cancel Code see 67 1 2 Conditional Closing T...

Страница 20: ...1 36 2 and or Telco 3 56 3 Audible Panic Optional 21 1 2 AUX Program a 2 in the AUX 1 and or AUX 2 option to initiate a AUX alarm when the M or N buttons on the Keyfob are pressed Additional programm...

Страница 21: ...s 1 Ring Method Enable the ring method of downloading The panel will pick up on the number of rings programmed in Ring Count 91 2 Answering Machine Override Using the downloading computer call the pan...

Страница 22: ...ollowing UL required features There is a 4 hour re sound of wireless Smoke Low Battery and wireless Smoke Supervisory system troubles An active System Battery test performed every 4 hours instead of 2...

Страница 23: ...e keypad will beep once every 10 seconds The keypad will continue to beep until the reset button is pressed or the trouble has been acknowledged by pressing the i key System Trouble Reporting The foll...

Страница 24: ...A signal is blocking the normal reception of transmissions from the wireless devices Ensure that the green LED on the receiver is not on continuously refer to receiver manual WI848 3 Beeps 1 6 Wireles...

Страница 25: ...flowing through the Bell circuit for supervision To eliminate the buzzing cut resistor R26 which is located directly above Terminal 9 just below the heat sink 5 Where are the fuses The control panel...

Страница 26: ...1 and point 2 is jumped out If using internal reed make sure J1 is cut and both Point 1 and Point 2 terminals are jumped out 10 Keypad LEDs Flicker The Keypad is not receiving a POLL from the Panel Ch...

Страница 27: ...Out Power In Fire Loop Out RED BLACK BROWN BROWN FT2200 8 7 8 9 Power In Fire Power Ground Fire Power Fire 2 2K 2 2K Normally Open Zone Wiring Wire the normally open contact as shown Zone 4 Program t...

Страница 28: ...Despite frequent testing and due to but not limited to any or all of the following criminal tampering electrical or communications disruption it is possible for the system to fail to perform as expec...

Отзывы: