19
System Report Code [63]. For example, if a
Low Battery System Report Code is F8 the
Battery Restore would be E8 (4/2 format).
[65]Opening and Closing Codes
Program Opening and Closing Codes for
Users 1 through 6. The second digit of the
report code is the number of the user that
armed or disarmed the system. For
example, if the Closing Code [65] is
programmed
with a
C
, the closing code for User 2 would
be
C2
(4/2 format).
[66]Ambush Report Code
Program a 2-digit report code for Ambush.
To send an ambush report, program a User
Code for User 6, Program report User 6 as
Ambush [20-4] and Select reporting for
Telco 1 [36-2] and/or Telco 3 [56-2].
Enhanced Communicator Features
[67]Telephone Number 1
(
1) Opening After Alarm (Cancel Code)
-
When enabled, all users that are not
selected to report on
Opening/Closing
[39]
will report an Opening only when opening
after an alarm has occurred.
(2) Conditional Closing Telephone 1
-
When enabled, all users that are not
selected to report an Opening/Closing ([39],
[59]) will report a Closing only when zones
have been bypassed. The Zone Trouble
Code [62-2] is used to report zones that
have been bypassed at the time of the
closing report.
(3) Reserved
(4) Reserved
[68]Telephone Number 3
(1) Opening after Alarm (Cancel Code)
-
see [67-1].
(2) Conditional Closing Telco 3
- see [67-1].
(3) Reserved
(4) Reserved
Wireless
Up to two receivers can be wired to the XP-
600. Each wireless transmitter can be
mapped to a zone. Only 1 wireless device
is permitted per zone, however, the use of
both hardwired and wireless on a zone is
permitted.
To Map a transmitter to a zone:
1. Enter the Programming Block Number
that the transmitter is to be mapped to.
2. Enter the 7-digit RF ID number directly,
just as it is shown on the device label.
After the 7th digit is entered the keypad
will beep.
A transmitter will send a transmission every
time it is tripped. The transmitter also sends
a supervisory transmission about once
every hour. If the receiver does not receive
a signal from a transmitter in the time
programmed in Wireless Supervisory Timer,
a system trouble ’RF Supervisory Failure'
will be indicated at the keypad.
Program Wireless Supervisory Timer [16] to
change the supervisory time from the default
of 12 hours.
The Signal strength of a transmitter can be
checked at the keypad (see
A
7
Fault
Find Mode) or saved to the LOG (see Signal