WI1372 XP-600 Installation Instructions
Keypad Beeps or
H
SYSTEM
Flashes
Zone LED
ON
System Trouble
Condition
Cause/Action
1
Beep
1
AC Power Failure
This trouble will occur if AC power is not present. Ensure that the transformer is connected to an
unswitched power source.
2
Low Battery
If there has been a recent power failure, the battery may be partially depleted and must be recharged by
the control panel. If the trouble does not go away in 24 hours, replace the battery.
3
Communication
Failure/PCPreset Fail
The system was not able to report to central station. Check panel programming and telephone line wiring.
The trouble will clear after it has been acknowledged by viewing the system trouble as long as the
telephone line has passed a line cut test (tested automatically by the panel). The Panel did not
sucsessfully connect and download/upload with the commputer running PCPreset - check Auto Download
ID number, Callback Number or PCPreset Setup.
4
Telephone Line Cut
The telephone line has failed. If telephone service has been temporarily interrupted, the trouble will clear
when restored and acknowledged by viewing the system trouble.
2
Beeps
1
Bell/Siren line Cut
There is a problem with the Bell or Siren wiring. EOL2.2K resistor must be installed.
2
2-wire Fire Trouble
There is a problem with the wiring of the Fire Zone.
3
Rcvr Fail-to-Respond/Rcvr
Tamper
The receiver is not responding to the panel. The red LED on the receiver should be flashing, refer to
WI848. The cover is off the receiver causing a tamper signal to be transmitted.
4
Receiver Jam
A signal is blocking the normal reception of transmissions from the wireless devices. Ensure that the
green LED on the receiver is not on continuously, refer to receiver manual WI848.
3
Beeps
1-6
Wireless
Transmitter Low Battery
The battery in the wireless transmitter is low and should be replaced. This transmitter is on the zone corresponding
to the number of the zone light flashing. The replacement battery for the GEM Trans2 door/window transmitter and
the GEM PIR wireless motion detector is the Duracell DL123A. (2 required for the GEM-PIR) WARNING: Replace
batteries only with the same type as specified above. Use of another battery may present a risk of fire or explosion.
Do not recharge or disassemble battery or dispose of in fire.
4
Beeps
1-6
Wireless
Transmitter
Supervisory Failure
The panel has not received a supervisory signal from the transmitter within the time programmed. Check
Wireless Supervisory Timer
[16] Programming. Check the placement of the transmitter and receiver, refer
to WI848.
5
Beeps
1-4
Wireless Smoke Detector
Low Battery
The battery in the wireless smoke detector is low and should be replaced. This wireless smoke detector
should be marked with a number corresponding to the number of the zone light flashing. The
replacement batteries required are *Duracell 9 Volt Alkaline (2).
6
Beeps
1-4
Wireless Smoke Detector
Supervisory
The panel has not received a supervisory signal from the wireless smoke detector within the programmed
time. Check
Wireless Smoke Supervisory Timer
[17] Programming. Check the placement of the wireless
smoke detector and receiver, refer to WI848.
7
Beeps
1-6
Zone Trouble
The panel has one or more of the following 3 possible troubles: Zone Short, Transmitter Tamper or Dual
Tech Self Test Fail.
System Troubles