WI1372  XP-600 Installation Instructions  

Keypad Beeps or   

H

SYSTEM  

Flashes 

Zone LED 

ON 

System Trouble 

Condition 

Cause/Action 

Beep 

AC Power Failure 

This trouble will occur if AC power is not present.  Ensure that the transformer is connected to an 
unswitched power source.  

 

Low Battery 

If there has been a recent power failure, the battery may be partially depleted and must be recharged by 
the control panel. If the trouble does not go away in 24 hours, replace the battery. 

 

Communication  
Failure/PCPreset Fail 

The system was not able to report to central station.  Check panel programming and telephone line wiring.  
The trouble will clear after it has been acknowledged by viewing the system trouble as long as the 
telephone line has passed a line cut test (tested automatically by the panel).   The Panel did not 
sucsessfully connect and download/upload with the commputer running PCPreset - check Auto Download 
ID number, Callback Number or PCPreset Setup. 

 

Telephone Line Cut 

The telephone line has failed. If telephone service has been temporarily interrupted, the trouble will clear 
when restored and acknowledged by viewing the system trouble.  

Beeps 

Bell/Siren line Cut 

There is a problem with the Bell or Siren wiring.   EOL2.2K resistor must be installed.  

 

2-wire Fire Trouble 

There is a problem with the wiring of the Fire Zone. 

 

Rcvr Fail-to-Respond/Rcvr  
Tamper 

The receiver is not responding to the panel.  The red LED on the receiver should be flashing, refer to 
WI848.  The cover is off the receiver causing a tamper signal to be transmitted.  

 

Receiver Jam 

A signal is blocking the normal reception of transmissions from the wireless devices.  Ensure that the 
green LED on the receiver is not on continuously, refer to receiver manual WI848. 

Beeps 

1-6 

Wireless 
Transmitter Low Battery 

The battery in the wireless transmitter is low and should be replaced. This transmitter is on the zone corresponding 
to the number of the zone light flashing.  The replacement battery for the GEM Trans2 door/window transmitter and 
the GEM PIR wireless motion detector is the Duracell DL123A. (2 required for the GEM-PIR) WARNING: Replace 
batteries only with the same type as specified above.  Use of another battery may present a risk of fire or explosion.  
Do not recharge or disassemble battery or dispose of in fire. 

4

 Beeps 

1-6 

Wireless  
Transmitter  
Supervisory Failure 

The panel has not received a supervisory signal from the transmitter within the time programmed.  Check 

Wireless Supervisory Timer

 [16] Programming.  Check the placement of the transmitter and receiver, refer 

to WI848. 

Beeps 

1-4 

Wireless Smoke Detector 
Low Battery 

The battery in the wireless smoke detector is low and should be replaced.  This wireless smoke detector 
should be marked with a number corresponding to the number of the zone light flashing.  The 
replacement batteries required are *Duracell 9 Volt Alkaline (2). 

Beeps 

1-4 

Wireless Smoke Detector 
Supervisory 

The panel has not received a supervisory signal from the wireless smoke detector within the programmed 
time.  Check 

Wireless Smoke Supervisory Timer 

[17] Programming.  Check the placement of the wireless 

smoke detector and receiver, refer to WI848.  

Beeps 

1-6 

Zone Trouble 
 

The panel has one or more of the following 3 possible troubles: Zone Short, Transmitter Tamper or Dual 
Tech Self Test Fail. 

System Troubles 

Содержание RPXP6GT

Страница 1: ...XP 600 RPXP6GT keypad Control Panel Communicator Installation Instructions WI1372 1 05 NAPCO 2005...

Страница 2: ...Line Cut Detection Answering Machine Override Second Call 50 Event Log Communicator 2 Telephone Numbers Backup Reporting Pager Format Point ID Format Individually Report 6 Users Opening after Alarm R...

Страница 3: ...Battery 12V 4 AH Rechargeable Change Battery every 5 years or as required Maximum Charging Current 165 mA Maximum Input Current 2 58 A Loop Characteristics Loop Voltage 5 Volts Loop Current Zones 1 2...

Страница 4: ...ss PIR Wireless Dual Technology Sensor Wireless Glass Break Detector Relay Board Audio Verification Module Downloading Software for IBM PC Compatibles Software with Interface for IBM PC Compatibles in...

Страница 5: ...ng PCPreset For Site Initiated Downloaded see Auto Download ID Number 93 Local Downloading Wire as shown in Figure 1 Use the power up or A6 method of establishing a connection The power up method is r...

Страница 6: ...eat detectors rather than smoke detectors are recommended in kitchens attics and garages due to conditions that may result in false alarms and improper operation Refer to NFPA Standard 74 National Fir...

Страница 7: ...mA Keypad Operation Keypad zone LEDs indicate zone status W ARMED X READY and HSYSTEM LEDs provide system status The keypad sounder provides feedback beeps for correct and incorrect entries Keypad So...

Страница 8: ...y Follower Zones can be bypassed when the M or N keys on the Keyfob have been programmed for Interior 81 84 Zones programmed as Home Away with Delay Zones can be armed regardless of the state of the E...

Страница 9: ...omatic Bypassing Home Away with Delay Zones From the Keypad Press C B to return protection to Home Away with Delay Zones that have been automatically bypassed Three minutes are allowed to walk through...

Страница 10: ...rogram Mode press the b key XP 600 Commands User Commands A 1 Bell Test Enter this command to turn on the Bell keypad sounder and keypad LEDs for 2 seconds The battery is tested during a Bell Test and...

Страница 11: ...ds when hardwired zones are faulted and for 1 second when zones are restored Wireless Operation Signal Strength While in Fault Find mode the keypad will provide an audible Table 6 and visual Figure 5...

Страница 12: ...lows exit after the panel is armed without setting off an immediate alarm and allows entry only if an Exit Entry Zone 00 has been violated first Zones of this type have a three 3 minute power up delay...

Страница 13: ...it through an Exit Entry Zone 00 after the system is armed allows a user to leave the premises without setting off an immediate alarm Exit Delay may be programmed for up to 255 seconds 4 minutes a val...

Страница 14: ...000 Downloading Software On power up the test timer is sent immediately Follow the commands below to offset the test timer using Quickloader Software From the Status Screen Press F6 Select Miscellaneo...

Страница 15: ...armed or 2 two times when the panel is disarmed Wire as shown in Figure 7 24 Programmable Output Features 2 1 I Fire Program to activate the PGM on a Fire alarm 2 AUX Program to activate the PGM on a...

Страница 16: ...orrect data the panel sends a Sumcheck digit after sending the Subscriber ID and Alarm Code 3 Single Digit 3 1 Format 3 digit Subscriber ID number and a 1 digit Alarm Code will be transmitted 4 No Han...

Страница 17: ...icator Enabled Program to enable the communicator 2 DTMF with Rotary Backup The first attempt to communicate is dialed using the TouchTone method of dialing subsequent attempts are dialed using the pu...

Страница 18: ...st digit of the report code sent the second digit is the zone number of the reporting zone For example if zone 2 has a report code of 3 the report code would be 32 3 1 format Sends only the report Cod...

Страница 19: ...de 62 2 is used to report zones that have been bypassed at the time of the closing report 3 Reserved 4 Reserved 68 Telephone Number 3 1 Opening after Alarm Cancel Code see 67 1 2 Conditional Closing T...

Страница 20: ...1 36 2 and or Telco 3 56 3 Audible Panic Optional 21 1 2 AUX Program a 2 in the AUX 1 and or AUX 2 option to initiate a AUX alarm when the M or N buttons on the Keyfob are pressed Additional programm...

Страница 21: ...s 1 Ring Method Enable the ring method of downloading The panel will pick up on the number of rings programmed in Ring Count 91 2 Answering Machine Override Using the downloading computer call the pan...

Страница 22: ...ollowing UL required features There is a 4 hour re sound of wireless Smoke Low Battery and wireless Smoke Supervisory system troubles An active System Battery test performed every 4 hours instead of 2...

Страница 23: ...e keypad will beep once every 10 seconds The keypad will continue to beep until the reset button is pressed or the trouble has been acknowledged by pressing the i key System Trouble Reporting The foll...

Страница 24: ...A signal is blocking the normal reception of transmissions from the wireless devices Ensure that the green LED on the receiver is not on continuously refer to receiver manual WI848 3 Beeps 1 6 Wireles...

Страница 25: ...flowing through the Bell circuit for supervision To eliminate the buzzing cut resistor R26 which is located directly above Terminal 9 just below the heat sink 5 Where are the fuses The control panel...

Страница 26: ...1 and point 2 is jumped out If using internal reed make sure J1 is cut and both Point 1 and Point 2 terminals are jumped out 10 Keypad LEDs Flicker The Keypad is not receiving a POLL from the Panel Ch...

Страница 27: ...Out Power In Fire Loop Out RED BLACK BROWN BROWN FT2200 8 7 8 9 Power In Fire Power Ground Fire Power Fire 2 2K 2 2K Normally Open Zone Wiring Wire the normally open contact as shown Zone 4 Program t...

Страница 28: ...Despite frequent testing and due to but not limited to any or all of the following criminal tampering electrical or communications disruption it is possible for the system to fail to perform as expec...

Отзывы: