X
GEM-P3200 Installation Instructions
L
NAPCO Security Systems
WI817F 10/05
Page 14
WIRING CONNECTIONS
AUXILIARY ALARM OUTPUT
Auxiliary Output can be activated depending on the programming options selected (see GEM-
P3200 Programming Instructions). Connect the device controlled by the programmable output
between terminal 8 (+) and terminal 14 (-). A programming option “AuxOut Chirp on Key-fob
Arm/Disarm” is available. If selected, an external siren driver can be connected to these termi-
nals.
TRANSFORMER
Connect a 16.5 VAC Transformer to Terminals 1 and 2, using a wire of #18 AWG. or
less at a distance of 15 ft. or less from the control panel.
NOTE:
Do not connect to a
switched outlet.
AC IN, 16.5V/60HZ VIA
TRF11 OR TRF14
CLASS 2 TRANSFORMER
DO NOT CONNECT TO
SWITCHED OUTLET
1
2
The RED (+) and BLACK (-) flying leads must be connected to
a 12VDC 4, 6 or 7 AH Rechargeable Battery, to serve as
backup power in the event of AC Power Failure.
NOTE:
To
calculate the available standby time refer to the Standby-
Battery Calculation Worksheet at the back of this manual.
Connect the alarm sounding devices (self-contained sirens, speakers or a mechanical bells) to
terminals 5 (+) and 14 (-). Any self-contained siren requiring a 12 VDC input can be connected.
When connecting a mechanical bell, it must be supervised using a 2.2k Ohm resistor. To con-
nect 8 Ohm Speakers use a Siren Driver with the proper polarity observed.
NOTE:
Refer to the
Wiring Diagram for alarm current specification, bell supervision and burglary output relay.
Note:
In NFPA Household Fire Installations. only a single siren or bell can be used on this bell
circuit.
SIREN/BELL BURG/FIRE ALARM OUTPUT
WIRIN
G
CONNECTIO
N
S
BATTERY
4 AH, 6 AH OR 7 AH
RECHARGEABLE
BATTERY 12 VDC
BLACK
RED
(–)
(+)
E1
E2
12VDC
Содержание Gemini GEM-P3200
Страница 58: ...X GEM P3200 Installation Instructions L NAPCO Security Systems WI817F 10 05 Page 58 NOTES...
Страница 60: ...X GEM P3200 Installation Instructions L NAPCO Security Systems WI817F 10 05 Page 60 GEM P3200 WIRING DIAGRAM...
Страница 66: ...X GEM P3200 Installation Instructions L NAPCO Security Systems WI817F 10 05 Page 66 Notes...
Страница 67: ...L NAPCO Security Systems X GEM P3200 Installation Instructions WI817F 10 05 Page 67 Notes...