73
S 07
MAINTENANCE
electrolyte level.
Specific gravity varies slightly with temperature. To be
exact, specific gravity decreases by 0.0007 with a 1°C in
-
crease (0.0004 with a 1°F increase) in temperature, and
increases by 0.0007 with a 1°C decrease (0.0004 with a
1°F decrease).
Therefore, using 20 °C (68 °F) as a reference, the specific
gravity reading must be corrected by the following for-
mula:
Specific gravity at 20 °C = Measured value + 0.0007 ×
(electrolyte temperature - 20 °C).
Specific gravity at 68 °F = Measured value + 0.0004 ×
(electrolyte temperature - 68 °F).
Specific gravity
Load status
1.260 Sp. Gr.
100% loaded
1.230 Sp. Gr.
75% loaded
1.200 Sp. Gr.
50% loaded
1.170 Sp. Gr.
25% loaded
1.140 Sp. Gr.
Very low capacity
1.110 Sp. Gr.
Unloaded
At an electrolyte temperature of 20°C (68°F)