Configuration/settings
User manual 55530_hdb_en_16
89 / 156
Notifications from the
device
Fig. 8-25: Processing of the "Notification" events
Processing the "Notification" IO-Link events
Tab. 8-22: Processing of the "Notification" events
Property of the generated PROFINET process alarm:
User Structure Identifier (Format): 0x8320
Process alarm data
Tab. 8-23: Process alarm data
Selection
Meaning
D
= Default
Discard
D
IO-Link events of the "Notification" type are dis-
carded and are not forwarded.
Greate process alarm
For every "Notification" IO-Link event that is
sent by the IO-Link device, a PROFINET pro-
cess alarm is generated.
Byte Meaning
Value
0
Channel number
MSB == 0x8000: No channel information available
!= 0x8000: Channel number (only for parameteriza-
tion of the
extended integration of the Murrelektronik
IO-Link
)
1
LSB
2
Channel properties MSB 0x0000
3
LSB
4
Reason for alarm
MSB 0x9500: IO-Link event code 0x0000 (0) - 0x7FFF
(32767)
0x9501: IO-Link event code 0x8000 (32768) -
0xFFFF (65535)
5
LSB
6
Reason for alarm
extended
MSB With reason for alarm 0x9500: IO-Link event code
With reason for alarm 0x9501: IO-Link event code
minus 0x8000 (32768)
7
LSB
8
Reason for alarm
Additional value
MSB 0x00000000
9
10
11
LSB