Configuration/settings
User manual 55530_hdb_en_16
87 / 156
According to IO-Link integration guideline Edition 1
This type of depiction only provides rudimentary diagnostic options be-
cause several different IO-Link event codes are depicted on the same
PROFINET Channel Error Type.
The PROFINET Channel Error Type therefore only occasionally permits a
conclusion to be drawn about the original IO-Link event code.
"Error"-type IO-Link events are reported as PROFINET diagnostics with
"Fault" maintenance.
Events of the "Warning" type are reported with "Maintenance demanded".
Events of the "Notification" type are not reported as PROFINET diagnos-
tics but are instead handled as "Notifications from the device" in accor-
dance with the parameterization.
The diagnostics do not include any channel numbers.
NOTE
The illustration and overview of the IO-Link event codes on PROFINET diag-
nostics can be found in chap. 9.3.3.1 "According to IO-Link integration guide-