Installation
User manual 55530_hdb_en_16
50 / 156
Sensor supply
Please note:
Sensors can be supplied via
pin 1
(24 V) and
pin 3
(0 V) of the M12 female
connectors.
The maximum permissible current for the power supply of the sensors is
0.2 A
for the digital I/O port and
1.0 A
for the IO-Link port.
In case of overcurrent or short circuit, the connected cable or sensor must
be
disconnected
from the M12 female connector.
Supported IO-Link
communication
The module supports the IO-Link communication using the following speeds:
4,800 baud (COM 1)
38,400 baud (COM 2)
230,400 baud (COM 3)
NOTE
The MVK module automatically selects the appropriate communication speed
for the IO-Link device.
NOTE
The cable length is limited to 20 m for IO-Link connection.