PAGE 64 — DCA400SSI4F/DCA400SSI4F3 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (04/18/22)
REGENERATION (BASLER CONTROLLER)
If a manual regen is needed, the Basler DGC-2020HD
controller (Figure 94) will announce a pre-alarm on the
controller. The pre-alarm will state
“NEED MAN REGEN”
and
“PRESS RUN BUTTON.”
While in this condition,
pressing the RUN button for 5 seconds will initiate the
Stationary Forced Regen. It will then display a new
pre-alarm
“MAN REGEN ACTIVE.”
Once the regen
completes, it will automatically shut down and display
“MAN REGEN COMPLT.”
DIAGNOSTIC MODE
There is a feature to put the controller in diagnostic mode.
Diagnostic mode will keep the key switch on for service tool
purposes. To place in diagnostic mode the engine must be
in the off mode.
Press the “Alarm Silence” and the “Lamp Test” buttons at
the same time for 5 seconds. To exit diagnostic mode you
can press reset, start the engine or turn control power off.
Figure 94. Basler DGC-2020HD Controller
MAINTENANCE
AUTOMATIC SHUTDOWN SYSTEM
This generator is equipped with safety devices to shut down
the engine in the event of the following conditions:
Low Oil Pressure
— Engine oil pressure has fallen
below 14.2 psi (98 kPa). The oil pressure is detected
using variable resistive values from the oil pressure
sending unit. This is considered a major fault and the
engine will be shut down.
High Coolant Temperature
— Engine temperature
has exceeded 212°F (100°C). The engine temperature
is detected using variable resistive values from the
temperature sending unit. This is considered a major
fault and the engine will be shut down.
Low Coolant Level
— Engine coolant level is low. This
is considered a major fault and the engine will be shut
down.
Overspeed Shutdown
— Engine is running at an unsafe
speed (+15%). This is considered a major fault and the
engine will be shut down.
NOTICE
Before inspecting the cause of the engine shutdown
be sure to place the
Auto Off/Reset Manual
Switch
in the
OFF/RESET
position and also place all circuit
breakers and the battery switch in the
OFF
position.
NOTICE
Although the unit is equipped with engine protection
devices, regularly scheduled
preventative
maintenance
is strongly advised.