OUTPUT TERMINAL PANEL FAMILIARIZATION
Connecting Loads
Loads can be connected to the generator by the
Output
Terminal Lugs
, convenience receptacles, or optional
camlocks (Figure 17). Make sure to read the operation
manual before attempting to connect a load to the generator.
To protect the output terminals from overload, a 3-pole,
1000-amp,
main
circuit breaker is provided. Make sure to
switch
ALL
circuit breakers to the
OFF
position prior to
starting the engine.
Figure 17. Connecting Loads
LOAD
GFCI
RECEPTACLES
LOAD
CS-6369
TWIST-LOCK
RECEPTACLES
CAMLOCKS (OPTION)
O
U
V
W
BLACK
RED
BLUE
WHITE
GREEN
LOAD
NEUTRAL
GROUND
HARD WIRE
HOOKUP PANEL
Overcurrent Relay
An
overcurrent relay
(Figure 18) is connected to the
main circuit breaker. In the event of an overload, both the
circuit breaker and the overcurrent relay may trip. If the
circuit breaker cannot be reset, the
reset button
on the
overcurrent relay must be pressed. The overcurrent relay
is located inside the control box.
Figure 18. Overcurrent Relay
RESET
BUTTON
NOTICE
Remember the
overcurrent relay
monitors the current
flowing from the
U,V, and W Output Terminal Lugs
to the load.
In the event of a short circuit or overcurrent condition,
it will automatically trip the 1000-amp main breaker.
To restore power to the
Output Terminal Panel
, press
the reset button on the overcurrent relay and place the
main
circuit breaker in the
closed
position
(ON)
.