PAGE 22 — DCA400SSI4F/DCA400SSI4F3 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (04/18/22)
ENGINE/GENERATOR CONTROL PANEL (DCA400SSI4F)
The definitions below describe the controls and functions
of the DCA400SSI4F Engine/Generator Control Panel
(Figure 9).
1.
ECU 650 Gauge Unit Assembly
— This assembly
houses the various engine monitoring gauges: oil
pressure, water temperature, charging voltmeter, fuel
level, and engine speed (tachometer).
A.
Oil Pressure Gauge
— During normal operation
this gauge should read between 57–100 psi.
(393–689 kPa). When starting the generator the
oil pressure may read a little higher, but after the
engine warms up the oil pressure should return to
the correct pressure range.
B.
Water Temperature Gauge
— During normal
operation this gauge should read between
167°–194°F (75°–90°C).
C.
Charging Voltmeter Gauge
— During normal
operation this gauge indicates a minimum of
26 VDC.
D.
Fuel Gauge
— Indicates the amount of diesel
fuel available.
E.
Tachometer
— Indicates engine speed in RPM
for 60 Hz operation. This meter should indicate
1,800 RPM when the rated load is applied.
Figure 9. Engine/Generator Control Panel (DCA400SSI4F)
PSI
OIL PRESS
0
25
50
75
100
°F
WATER TEMP
100
140
180
220
260
°F
FUEL
E
½
F
RPMX10
SPEED
0
120
150
180
210
60
1
ECU
Integrated Gauge Panel
A
B
C
D
E
2 3 4 5
6
7
8
9
10
12
13
11
14 15 16 17
18
19
20
2.
Coolant Level Alarm Lamp
— Lamp illuminates
when the coolant level has dropped below the normal
operating level. If the lamp turns on during normal
operation the engine will shut down automatically.
3.
Pre-Alarm Lamp
— Lamp illuminates when engine
failures occur during normal operation. Confirm the
alarm by pressing the “Alarm Acknowledge Button”
on the ECU controller.
4.
Engine Shutdown Alarm Lamp
— Lamp illuminates
when an engine failure occurs during normal operation.
If the lamp turns on during normal operation the engine
will shut down automatically.
5.
Panel Light
— For operation at night, the panel light
illuminates the control panel for ease of reading meters
and gauges. Make sure the panel light switch is in the
OFF position when the light is not in use.
6.
Pilot Lamp
— Illuminates when an engine fault has
been detected.
7.
Frequency Meter
— Indicates the output frequency
in hertz (Hz). Normally 60 Hz.
8.
AC Ammeter
— Indicates the amount of current the
load is drawing from the generator per leg selected by
the ammeter phase-selector switch.