PAGE 48 — DCA400SSI4F/DCA400SSI4F3 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (04/18/22)
Table 13. Inspection/Maintenance
10 Hrs
DAILY
250 Hrs
500 Hrs
or Every
12 Months
3,000 Hrs
or Every
36 Months
OTHER
Engine
Check Engine Oil and Coolant Levels
X
Check Fuel Filter/Water Separator Bowl
X
Check Air Cleaner
X
Check Air Cleaner Element
X
Check for Leaks/Hoses/Clamps*
4
X
Check for Loosening of Parts
X
Change Engine Oil and Oil Filter*
1
X
Clean Unit, Inside and Outside
X
Replace Fuel Filter Elements
X
Check Engine Mounts
X
Service Battery
X
Check Air Intake Hoses
X
Check Fan Belt Condition
X
Check Automatic Belt Tensioner
X
Check Electrical Ground Connection
X
Clean Radiator, Check Cooling System
X
Coolant Solution Analysis, Add SCAs as Required
X
Pressure Test Cooling System
X
Check Engine Speed
X
Test Thermostats
X
Check and Adjust Engine Valve Clearance
X
Test Glow Plugs
X
Replace DEF Filter (Supply Module)
3,000 hrs.
Check SCR System*
2
X
4,500 hrs.
Inspect Dosing Module (SCR System)
4,500 hrs.
Flush and Refill Cooling System*
3
2 yrs. or 2,000 hrs.
Clean Inside of Fuel Tank
1,000 hrs.
Clean DEF Tank
As Required
Replace Air Cleaner Elements*
5
As Required
Generator
Measure Insulation Resistance Over 3M Ohms*
6
X
Check Rotor Rear Support Bearing
X
*
1
During initial operation of a new engine, change oil and filter between a minimum of 100 hours and a maximum of 250 hours. Service interval
depends on type of oil.
*
2
Perform inspection and maintenance of urea SCR system every 4,500 hours. The SCR system does not need to be replaced if no problems are
found. DO NOT make modifications/changes or remove the emission control system and related parts. Please contact your nearest dealer or
Multiquip for SCR maintenance.
*
3
Please use fully formulated antifreeze/coolant.
*
4
If blowby hose needs to be replaced, make sure that the slope of the blowby hose is at least 1/2 inch per foot, with no sags or dips that could
collect moisture and oil.
*
5
Replace the primary air filter element when the restriction indicator shows a vacuum of 625 mm (25 in. H
2
0).
*
6
DCA400SSI4F3 only:
Make sure to disconnect the O–Ground line and CN11–CN12 before performing the measurement. Refer to the Generator
Wiring Diagram (DCA400SSI4F3).
MAINTENANCE