DCA400SSI4F/DCA400SSI4F3 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (04/18/22) — PAGE 23
9.
AC Voltmeter
— Indicates the output voltage present
at the U,V, and W Output Terminal Lugs.
10.
Voltage Regulator Control Knob
— Allows ± 15%
manual adjustment of the generator’s output voltage.
11.
Ammeter Change-Over Switch
— This switch allows
the AC ammeter to indicate the current flowing to the
load connected to any phase of the output terminals,
or to be switched off. This switch does not affect the
generator output in any fashion, it is for current reading
only.
12.
Voltmeter Change-Over Switch
— This switch allows
the AC voltmeter to indicate phase-to-phase voltage
between any two phases of the output terminals or to
be switched off.
13.
Voltage Change-Over Board
— 6 jumper plates that
allow the generator to be configured for either 240 or
480 VAC output.
14.
Panel Light Switch
— When activated will turn on the
control panel light.
15.
Hour Check Button
— With the engine stopped, press
and hold this button. The total running hours, fuel level,
and battery voltage will be displayed.
16.
Auto/Start Switch
— This switch selects either manual
or automatic operation. Center position is OFF (reset).
17.
Engine Speed Switch
— This switch controls the
speed of the engine, low or high.
18.
Emergency Stop Switch Button
— In the event
of an emergency press this button to shut down the
generator.
19.
Main Circuit Breaker
— This 3-pole, 1000-amp main
circuit breaker is provided to protect the U,V, and W
Output Terminal Lugs from overload.
20.
Battery Switch
— Connects and disconnects the
battery. Place the switch in the
ON
position prior to
starting the generator. When the generator is not in
use, place the switch in the
OFF
position.
NOTICE
NEVER
set the battery switch to the
OFF
position
while
the engine is running
. The engine may not be able to
be stopped by normal operation, and damage to the
equipment may result.
ENGINE/GENERATOR CONTROL PANEL (DCA400SSI4F)