6. COMMUNICATIONS
MEMORY MAP
6-56
GROUP
ADDR
(hex)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
1DFE
Reserved
SPEED2
1DFF
Speed2 Standard Overload Curve Number
1
15
1
-
F1
4
O/L SETUP
1E00
Speed2 Time to Trip at 1.01 x FLA
5
999999
1
s
F10
174145
1E02
Speed2 Time to Trip at 1.05 x FLA
5
999999
1
s
F10
34149
1E04
Speed2 Time to Trip at 1.10 x FLA
5
999999
1
s
F10
16667
1E06
Speed2 Time to Trip at 1.20 x FLA
5
999999
1
s
F10
7954
1E08
Speed2 Time to Trip at 1.30 x FLA
5
999999
1
s
F10
5072
1E0A
Speed2 Time to Trip at 1.40 x FLA
5
999999
1
s
F10
3646
1E0C
Speed2 Time to Trip at 1.50 x FLA
5
999999
1
s
F10
2800
1E0E
Speed2 Time to Trip at 1.75 x FLA
5
999999
1
s
F10
1697
1E10
Speed2 Time to Trip at 2.00 x FLA
5
999999
1
s
F10
1166
1E12
Speed2 Time to Trip at 2.25 x FLA
5
999999
1
s
F10
861
1E14
Speed2 Time to Trip at 2.50 x FLA
5
999999
1
s
F10
666
1E16
Speed2 Time to Trip at 2.75 x FLA
5
999999
1
s
F10
533
1E18
Speed2 Time to Trip at 3.00 x FLA
5
999999
1
s
F10
437
1E1A
Speed2 Time to Trip at 3.25 x FLA
5
999999
1
s
F10
366
1E1C
Speed2 Time to Trip at 3.50 x FLA
5
999999
1
s
F10
311
1E1E
Speed2 Time to Trip at 3.75 x FLA
5
999999
1
s
F10
268
1E20
Speed2 Time to Trip at 4.00 x FLA
5
999999
1
s
F10
233
1E22
Speed2 Time to Trip at 4.25 x FLA
5
999999
1
s
F10
205
1E24
Speed2 Time to Trip at 4.50 x FLA
5
999999
1
s
F10
182
1E26
Speed2 Time to Trip at 4.75 x FLA
5
999999
1
s
F10
162
1E28
Speed2 Time to Trip at 5.00 x FLA
5
999999
1
s
F10
146
1E2A
Speed2 Time to Trip at 5.50 x FLA
5
999999
1
s
F10
120
1E2C
Speed2 Time to Trip at 6.00 x FLA
5
999999
1
s
F10
100
1E2E
Speed2 Time to Trip at 6.50 x FLA
5
999999
1
s
F10
85
1E30
Speed2 Time to Trip at 7.00 x FLA
5
999999
1
s
F10
73
1E32
Speed2 Time to Trip at 7.50 x FLA
5
999999
1
s
F10
63
1E34
Speed2 Time to Trip at 8.00 x FLA
5
999999
1
s
F10
56
1E36
Speed2 Time to Trip at 10.0 x FLA
5
999999
1
s
F10
56
1E38
Speed2 Time to Trip at 15.0 x FLA
5
999999
1
s
F10
56
1E3A
Speed2 Time to Trip at 20.0 x FLA
5
999999
1
s
F10
56
1E3C
Reserved
...
1E4F
Reserved
1E50
Speed2 Minimum Allowable Line Voltage
70
95
1
% Rated
F1
80
1E51
Speed2 Stall Current at Min Vline
200
1500
1
x FLA
F3
480
1E52
Speed2 Safe Stall Time at Min Vline
5
9999
1
s
F2
200
1E53
Speed2 Accel. Intersect at Min Vline
200
1500
1
x FLA
F3
380
1E54
Speed2 Stall Current at 100 % Vline
200
1500
1
x FLA
F3
600
1E55
Speed2 Safe Stall Time at 100 % Vline
5
9999
1
s
F2
100
1E56
Speed2 Accel. Intersect at 100 % Vline
200
1500
1
x FLA
F3
500
Содержание SR469
Страница 7: ......
Страница 19: ...2 INSTALLATION MECHANICAL 2 5 2 1 5 TERMINAL LOCATIONS Figure 2 11 TERMINAL LAYOUT...
Страница 21: ...2 INSTALLATION ELECTRICAL 2 7 Figure 2 12 TYPICAL WIRING DIAGRAM...
Страница 32: ...ELECTRICAL 2 INSTALLATION 2 18 2 2 14 TYPICAL 2 SPEED MOTOR WIRING...
Страница 39: ...OVERVIEW 3 SR469 OPERATION 3 6 yy SETPOINTS yy S1 SR469 SETUP...
Страница 104: ...4 SETPOINT PROGRAMMING S11 MONITORING 4 65 Figure 4 24 TRIP COIL SUPERVISION...
Страница 113: ...S12 ANALOG I O 4 SETPOINT PROGRAMMING 4 74...
Страница 244: ...8 469PC PROGRAM WAVEFORM CAPTURE 8 13 Figure 8 11 WAVEFORM CAPTURE...