DEFAULT
1510
Reserved
...
157F
Reserved
THERMAL
1580
Curve Style
0
2
1
-
FC128
0
MODEL
1581
Overload Pickup Level
101
125
1
x FLA
F3
101
1582
Unbalance k Factor
0
12
1
-
F1
0
1583
Cool Time Constant Running
1
1000
1
min
F1
15
1584
Cool Time Constant Stopped
1
1000
1
min
F1
30
1585
Hot/Cold Safe Stall Ratio
1
100
1
-
F3
100
1586
RTD Biasing
0
1
1
-
FC103
0
1587
RTD Bias Minimum
0
250
1
o
C
F1
40
1588
RTD Bias Center Point
0
250
1
o
C
F1
130
1589
RTD Bias Maximum
0
250
1
o
C
F1
155
158A
Thermal Capacity Alarm
0
2
1
-
FC115
0
158B
Thermal Capacity Alarm Relays
0
6
1
-
FC113
0
158C
Thermal Capacity Alarm Level
10
100
1
% used
F1
75
158D
Thermal Capacity Alarm Events
0
1
1
-
FC103
0
158E
Overload Trip Relays
0
3
1
-
FC111
0
158F
Reserved
...
15AE
Reserved
O/L CURVE
15AF
Standard Overload Curve Number
1
15
1
-
F1
4
SETUP
15B0
Time to Trip at 1.01 x FLA
5
999999
1
s
F10
174145
15B2
Time to Trip at 1.05 x FLA
5
999999
1
s
F10
34149
15B4
Time to Trip at 1.10 x FLA
5
999999
1
s
F10
16667
15B6
Time to Trip at 1.20 x FLA
5
999999
1
s
F10
7954
15B8
Time to Trip at 1.30 x FLA
5
999999
1
s
F10
5072
15BA
Time to Trip at 1.40 x FLA
5
999999
1
s
F10
3646
15BC
Time to Trip at 1.50 x FLA
5
999999
1
s
F10
2800
15BE
Time to Trip at 1.75 x FLA
5
999999
1
s
F10
1697
15C0
Time to Trip at 2.00 x FLA
5
999999
1
s
F10
1166
15C2
Time to Trip at 2.25 x FLA
5
999999
1
s
F10
861
15C4
Time to Trip at 2.50 x FLA
5
999999
1
s
F10
666
15C6
Time to Trip at 2.75 x FLA
5
999999
1
s
F10
533
15C8
Time to Trip at 3.00 x FLA
5
999999
1
s
F10
437
15CA
Time to Trip at 3.25 x FLA
5
999999
1
s
F10
366
15CC
Time to Trip at 3.50 x FLA
5
999999
1
s
F10
311
15CE
Time to Trip at 3.75 x FLA
5
999999
1
s
F10
268
15D0
Time to Trip at 4.00 x FLA
5
999999
1
s
F10
233
15D2
Time to Trip at 4.25 x FLA
5
999999
1
s
F10
205
15D4
Time to Trip at 4.50 x FLA
5
999999
1
s
F10
182
15D6
Time to Trip at 4.75 x FLA
5
999999
1
s
F10
162
Содержание SR469
Страница 7: ......
Страница 19: ...2 INSTALLATION MECHANICAL 2 5 2 1 5 TERMINAL LOCATIONS Figure 2 11 TERMINAL LAYOUT...
Страница 21: ...2 INSTALLATION ELECTRICAL 2 7 Figure 2 12 TYPICAL WIRING DIAGRAM...
Страница 32: ...ELECTRICAL 2 INSTALLATION 2 18 2 2 14 TYPICAL 2 SPEED MOTOR WIRING...
Страница 39: ...OVERVIEW 3 SR469 OPERATION 3 6 yy SETPOINTS yy S1 SR469 SETUP...
Страница 104: ...4 SETPOINT PROGRAMMING S11 MONITORING 4 65 Figure 4 24 TRIP COIL SUPERVISION...
Страница 113: ...S12 ANALOG I O 4 SETPOINT PROGRAMMING 4 74...
Страница 244: ...8 469PC PROGRAM WAVEFORM CAPTURE 8 13 Figure 8 11 WAVEFORM CAPTURE...