3 Product description
Maschinenfabrik Reinhausen GmbH 2020
26
4983703/01 EN
VACUTAP
®
VV-Ex
Depending on the order, some or all of these pipe connections are fitted with
pipe bends ex factory. All pipe bends can be freely swiveled once the pres-
sure ring is loosened.
Figure 5: Pipe connections with pipe bends
Pipe connection Q
The pipe connection Q is closed with a blank cover.
The functions of the R and Q pipe connections can be interchanged.
Pipe connection S
The pipe bend on pipe connection S features a vent screw and can be con-
nected to a pipe that ends with a drain valve on the side of the transformer
tank at operating height. If the on-load tap-changer is fitted with an oil suc-
tion pipe, the on-load tap-changer can be completely emptied via pipe con-
nection S.
Pipe connection R
Pipe connection R is intended for attachment of the protective relay and con-
nection of the on-load tap-changer oil conservator and can be interchanged
with pipe connection Q.
Pipe connection E2
Pipe connection E2 is sealed off with a blank cover. It leads into the oil tank
of the transformer, directly under the on-load tap-changer head and can be
connected to a collective pipe for the Buchholz relay, if necessary. This pipe
connection serves a further purpose, namely to equalize the pressure be-
tween the transformer tank and oil compartment of the on-load tap-changer,
which is necessary for drying, filling with insulating fluid and transportation of
the transformer.
Содержание VACUTAP VV-Ex
Страница 1: ...On load tap changer VACUTAP VV Ex Installation and commissioning instructions 4983703 01 EN ...
Страница 135: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 135 4983703 01 EN VACUTAP VV Ex 9 Drawings 9 1 External view 737774 ...
Страница 138: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 138 4983703 01 EN VACUTAP VV Ex 9 4 Installation drawing 738902 ...
Страница 139: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 139 4983703 01 EN VACUTAP VV Ex 9 5 Oil suction pipe 739172 ...
Страница 142: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 142 4983703 01 EN VACUTAP VV Ex 9 8 Mounting drawing 898866 ...
Страница 149: ......