5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
75
4983703/01 EN
VACUTAP
®
VV-Ex
2.
NOTICE!
An open kerosene drain plug leads to oil escaping from the oil
compartment and therefore to damage to the on-load tap-changer. Close
kerosene drain plug counter-clockwise (tightening torque 39 Nm).
3. Insert on-load tap-changer insert.
5.4.9 Filling the oil compartment of the on-load tap-changer with
insulating fluid
NOTICE
Damage to the on-load tap-changer!
Unsuitable insulating fluids cause damage to the on-load tap-changer.
► Use insulating fluids that meet the requirements in accordance with IEC
60296.
► If approved by the transformer manufacturer, you can use synthetic es-
ters in accordance with IEC 61099 approved by Maschinenfabrik Rein-
hausen GmbH.
After drying, completely fill the oil compartment (diverter switch insert fitted)
with oil again as soon as possible so that an impermissible amount of humid-
ity is not absorbed from the surroundings.
1. Establish a connecting lead between pipe connection E2 and one of the
pipe connections R, S or Q to ensure equal pressure in the oil compart-
ment and transformer during evacuation.
Figure 55: Connecting lead between E2 and Q
Содержание VACUTAP VV-Ex
Страница 1: ...On load tap changer VACUTAP VV Ex Installation and commissioning instructions 4983703 01 EN ...
Страница 135: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 135 4983703 01 EN VACUTAP VV Ex 9 Drawings 9 1 External view 737774 ...
Страница 138: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 138 4983703 01 EN VACUTAP VV Ex 9 4 Installation drawing 738902 ...
Страница 139: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 139 4983703 01 EN VACUTAP VV Ex 9 5 Oil suction pipe 739172 ...
Страница 142: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 142 4983703 01 EN VACUTAP VV Ex 9 8 Mounting drawing 898866 ...
Страница 149: ......