5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
46
4983703/01 EN
VACUTAP
®
VV-Ex
For design without oil suction pipe, the on-load tap-changer head can be
turned towards the supporting flange in 15° steps. For design with oil suc-
tion pipe, turning at 15° increments is not possible.
When positioning the on-load tap-changer head, do however note that the
tap-change supervisory control restricts the swivel range of the upper gear
unit.
5.3.1.3 Connecting on-load tap-changer to top part of on-load tap-changer
head
NOTICE
Damage to the on-load tap-changer!
A missing or damaged o-ring as well as unclean sealing surfaces lead to in-
sulating fluid escaping and therefore to damage to the on-load tap-changer.
► Ensure that the o-ring is positioned untwisted in the on-load tap-changer
head cover.
► Ensure that the o-ring does not become damaged when mounting the
cover.
► Ensure that the sealing surfaces on the on-load tap-changer head cover
and on-load tap-changer head are clean.