AirWorks AWK-1131A
Additional Consoles
5-3
3.
In the
Communication Parameter
tab of the
Property
window that opens, select the appropriate COM
port for console connection using
115200
for Baud Rate,
8
for Data Bits,
None
for Parity, and
1
for Stop
Bits. Click on the
Terminal
tab, and select
VT100 (or ANSI)
for Terminal Type. Click on
OK
to continue.
4.
The console login screen is displayed. Log into the RS-232 console with the login name (default:
admin
)
and password (default:
moxa
, if no new password is set).
5.
The AWK-1131A’s device information and Main Menu will be displayed. Follow the instructions on the screen
to select the administration task that you want to perform.
NOTE
To modify the appearance of the PComm Terminal Emulator window, select
Edit
Font
and then choose the
desired formatting options.
ATTENTION
If you unplug the RS-232 cable or trigger
DTR
, a disconnection event will be evoked to enforce logout for
network security. You will need to log in again to resume operation.