SC 4812ET/SC 614 BTS DC Power Sharing
– continued
Apr 2001
V0D.03
SC
TM
4812ET RF and Power Cabinet Hardware Installation Manual
DRAFT
149
Table D-3: SC 614 DC Power Cabling
Step
Action
8
Pull the exposed end of the cold shrink tubing until it begins to unravel. Make sure that the tubing is
positioned over the proper location on the lug. Pull the tube until the cold shrink is attached.
9
Loosen the two (2) screws that retain the BBI (Battery Backup Interface) cover (see Figure D-4 for
location). Slide cover towards the back of the BTS and remove it.
10
Attach the RED 28V feed power cable to the exposed studs on the BBI with the lock nuts supplied
with the installation hardware (see Figure D-2). Torque to 5 N–m (45 in–lbs).
11
Reinstall the BBI cover and slide it towards the front of the BTS. Torque to 2 N–m (15 in–lbs).
Figure D-2: SC 614 Backup DC Power Cable Routing
DC CONDUIT LOCATION
MOUNTING STUDS
2910262D12
(SHOWN INSTALLED)
D