Installation Quickstart
– continued
Apr 2001
V0C.03
SC
TM
4812ET RF and Power Cabinet Hardware Installation Manual
DRAFT
141
Table C-5: Alarm, Span Line Cabling, and Remote GPS Cable Install
Step
Action
5
Route the Power Cabinet Alarm Cable from the RF Cabinet to the Power Cabinet (in 3” DC conduit)
and through the Power I/O Boot to the Punch Block.
6
Connect the Power Cabinet Alarm cable pairs to each punch block per the pin–callouts in Chapter 5 of
this manual.
7
Strain relief the cable by tie wrapping it to the punch block as shown in Chapter 5 of the manual.
Main RF Cabling
RF cabling depends upon system configuration, see site documentation
and chapter 5 of the manual for details regarding RF cabling.
DC Power Cabling
Table C-6 describes the procedure for connecting DC Power Cabling.
Do NOT wear a wrist strap when servicing the power
supplies or power distribution cabling. Serious personal
injury can result.
WARNING
Before starting the procedure, ensure that the Power
Cabinet main DC breakers are turned ”OFF”.
CAUTION
The hole in the I/O panel of the cabinets is the proper size
for a US Standard 3” conduit fitting.
NOTE
Figure C-1: Connecting Power Cables
CABLE
GROMMET
LUG COVER
M10 NUT
M10 LOCK WASHER
M10 FLAT WASHER
CRIMP LUG
FEED COVER (Do not remove)
ENCLOSURE BASE
POWER INPUT STUD
C