Battery Configuration Specifications
Table B-2 shows the minimum number of battery strings required for
various system configurations. It is recommended to install the number
of batteries required to obtain an estimated 4 hours of backup time for
the SC4812ET RF Cabinet.
The backup durations presented within this table is an
estimated time based on 25 Deg C (77 Deg F) battery
temperature, actual backup duration may vary with system
configuration and loading.
NOTE
Table B-2: Minimum Battery Strings Required for Sector–Carrier Configurations
# of Battery
Strings
3 Rectifiers
(3 Sector–Carriers)
4 Rectifiers
(6 Sector–Carriers)
5 Rectifiers
(9 Sector–Carriers)
6 Rectifiers
(12 Sector–Carriers)
0
0
0
0
0
1
2
3
4
5
6
4.0 hrs
7
4.8 hrs
3.5 hrs
8
5.4 hrs
4.0 hrs
9
6.0 hrs
4.5 hrs
3.6 hrs
10
6.7 hrs
5.0 hrs
4.0 hrs
3.3 hrs
11
7.4 hrs
5.5 hrs
4.4 hrs
3.6 hrs
12
8.0 hrs
6.0 hrs
4.8 hrs
4.0 hrs
! CAUTION
The minimum number of battery strings presented in this table must be met or reduced backup time and
inadvertent tripping to the battery system breakers could result.