ZX Fire Alarm Control Panels
Page 38
Document No. 996-174-000-1, Revision: 01
Installation Manual
6 Specifications
6.1 Functional
Specifications
Specification Item
Values
Enclosure
400mm wide, 400mm high, 135 mm deep
Sealed to IP30.
Weight
10 kg without batteries.
18.5 kg with 12Ah batteries fitted.
Operating Temperature
0 C to +40 C
Relative Humidity
85%
(non-condensing)
Knockouts (20mm)
14 (Top), 2 (Bottom)
Sounder (NAC) Output
2 programmable outputs.
Open- and short-circuit monitored.
6k8, EOL resistors (P/N 170-073-682).
1A maximum output current.
Minimum switched current – 1mA
Auxiliary Relay
2 volt-free, changeover outputs. Relay 1 configured as Fault
output. Relay 2 configured as Fire output.
Contacts rated at 24V AC/DC, 1 Amp, 0.6pF maximum.
Minimum switched load – 1mA @ 5V
Sensor Circuit
ZX1Se – 1 plug-in loop driver module per panel.
ZX2Se – 1 to 2 plug-in loop driver modules per panel.
Supports Analogue Addressable devices over a 2-wire,
combined-power and digital-data, transmission loop.
Loop Output Voltage and Signalling depends on the loop
driver installed – refer to documentation supplied with the
loop driver.
Maximum Loop Loading is 460mA per loop.
Monitoring zones
Up to 20 zones with individual LED indicators.
Maximum 120 zones – up to 200 software zones (no LED
indicators).
Table 9 – ZX1Se / ZX2Se Functional Specifications