ZX Fire Alarm Control Panels
Page 8
Document No. 996-174-000-1, Revision: 01
Installation Manual
3.3.1 CPU
Board
The CPU Board controls the operation of the ZX1Se, ZX2Se, ZX5Se and ZX10Se Fire Alarm
Control Panels. The operating program is stored in EPROM mounted in sockets on the board.
3.3.2 Display / Keyboard
The Display / Keyboard provides the user access to view alarms and control operation of the
system.
3.3.3 Base
Card
The base card provides control and wiring of all external connections to the system.
The base card can be augmented with one (ZX1Se), one to two (ZX2Se), one to five (ZX5Se) or
one to ten (ZX10Se) plug-in loop driver modules for connection to the signalling detectors.
The system can support addressable smoke detectors and loop devices through the use of loop
driver boards. The options are as follows:
Loop Device Manufacturer
Loop Card Part No.
Morley-IAS 795-072-100
System sensor
795-068-100
Hochiki 795-058-105
Apollo XP95 / Discovery
795-066-100
Nittan 795-044-001
Table 2 - Loop Driver Part Numbers
For details of the compatible signalling devices, refer to the relevant installation guide supplied
with the loop driver module. At least one loop driver board MUST be installed for the unit to
operate as a Fire Alarm Control Panel.
The base card may be augmented by one (ZX1Se), one or two (ZX2Se) or up to three (ZX5Se)
plug-in serial interface cards. Up to 6 may be fitted to the ZX10Se FACP – three per ZX5Se panel.
The serial interface cards provide for networking of panels and for connection of peripheral devices.
3.3.4 Zone Extender Card (ZX5Se Option Only)
The ZX5Se FACP may be augmented with an additional Zone LED Indicator card. The ZX10Se may
be augmented with two additional zone LED Indicators cards – one in the upper unit and the second
in the lower unit. This Zone Expander Card provides FIRE ALARM and FAULT LED indicators.
It is available in two options providing, a further 20 zones (40 zones in total) or a further 60 zones
(80 zones in total). The model numbers of the units are as follows:
1. 795-077-020
20 Zone LED Expander
2. 795-077-060
60 Zone LED Expander
Refer to the Zone Expander Installation Guide (P/N 996-137) for further information.
3.3.5 Internal Printer (ZX5Se /ZX10Se Option Only)
The ZX5Se and ZX10Se FACPs may be augmented by the addition of a printer module. This
provides printed records of FIRE ALARMS, FAULTS and EVENT LOG.
Refer to Section 3.5.4 and to the Commissioning Manual for further information.