ZX Fire Alarm Control Panels
Page 22
Document No. 996-174-000-1, Revision: 01
Installation Manual
3.4.8 Peripheral
Loop
EN54
!
EN54-2 12.5
Integrity of
transmission paths:
The network does
not provide the
required
transmission path
integrity.
The ZX1Se, ZX2Se, ZX5Se and ZX10Se Fire Alarm Control Panels
can be connected to a range of serial interface devices via the
peripheral loop.
The peripheral loop interface uses the Port D position on the base
card.
A peripheral loop requires the installation of an Isolated RS485
Interface card in the panel.
The RS485 peripheral communications link should be installed in a
‘daisy chain’ or ‘loop’ type wiring arrangement. For further details,
refer to the Installation Guide supplied with the RS485 Interface
Card. Refer to document 996-067.
Each supervised peripheral device must be given an address. The
address can be in the range 1 – 126. Refer to the Installation Guide
for each peripheral type for details on the allowed address range.
The maximum number of physical devices that can be connected
to the peripheral loop is 31.
Part Number
Device Description
Supervised
709-601-001
ZXr-A Active Remote Annunciator (Repeater)
YES
709-701-001
ZXr-P Passive Remote Annunciator (Repeater). Not
supervised if set to address 0.
Optional
709-001 ZXR5B
Active
Remote
Annunciator (Repeater)
YES
709-101
ZXR4B Passive Remote Annunciator (Repeater)
NO
795-015
EXP-015
4-Way Sounder Module
YES
795-065 EXP-065
40-Way
Remote
Mimic (LED Driver)
YES
795-014 EXP-014
4-Way
Relay
Module
YES
795-029
EXP-029
8-Way Input Module
YES
795-057
MODBUS interface unit
YES
Table 4 – List of Compatible Peripheral Devices