ZX Fire Alarm Control Panels
MORLEY-IAS
Installation Manual
Document No. 996-174-000-1, Revision: 01
Page 21
3.4.7 Panel Networking / Graphics PC Interface
EN54
!
EN54-2 12.5
Integrity of
transmission paths:
The network does
not provide the
required
transmission path
integrity.
The Panel Network (Master to Slave panel) interface uses Port ‘C’
position on the base card.
A Master Panel (ZX5Se and ZX10Se only) can also be connected
either to a Superior Master or to a Graphics PC using the Port ‘B’
position on the base card.
3.4.7.1
Local Panel Network
The ZX1Se, ZX2Se, ZX5Se and ZX10Se Fire Alarm Control Panels can be connected in a
network of panels with other panels in the ZX Series FACP range.
The panels can be connected in two types of configuration: A Shared Zone Network in which
panels share common zones and function as one system; a Report and Control Network in which
individual panels or subsystems are networked for reporting and control purposes only.
A panel network requires the installation of an Isolated RS485 Interface card in each panel, using
the Port ‘C’ interface position.
For detailed information on networking and wiring installation for a panel network, refer to
document P/N 996-075.
3.4.7.2
Master Panel to Superior Master Panel
The network can be further extended, by connecting Network Master Panels to a Superior
Master Panel (ZX5Se and ZX10Se only).
The network master panels are connected via an Isolated RS485 Interface Card in the Port ‘B’
position to the Superior Master panel containing an Isolated RS485 Interface Card in the Port ‘C’
position.
For detailed information on networking and wiring installation for a panel network, refer to
document P/N 996-075.
3.4.7.3
Panel to Graphics PC
A Network Master panel or a Superior Master Panel may be connected to a Graphics PC for
additional reporting and control purposes (ZX5Se and ZX10Se only).
The Graphics PC interface requires the installation of either an Isolated RS232 interface or an
Isolated RS485 interface card using the Port ‘B’ position.
The ZX1Se and ZX2Se panel may be connected to a Graphics PC but may then not be
connected in a network of panels.
For detailed information on connecting and using a Graphics PC, refer to documents P/N 996-
046 and 996-047.