background image

 
ZX Fire Alarm Control Panels 

 

MORLEY-IAS 

 

Installation Manual 

Document No. 996-174-000-1, Revision: 01 

Page 49 

 

Specification Item 

Values 

Operating Voltage 

230V 50Hz AC. 

(or 120V 60Hz AC). 

Incoming mains fuse (x2) 

FS1  T 3.15A 250V H 20 mm - Chassis mounted. 

Power supply card input 

16V AC (panel supply) from integral mains transformer. 

9V AC (charger & printer supply) from integral mains transformer. 

Power supply card fuses 

F1 

T 10A  250V H 20 mm 

F2 

T 6.3A  250V H 20 mm  

F3 

T 6.3A  250V H 20 mm 

Charger Rating (x2) 

1.00 Amp (min) – temperature-compensated, lead-acid battery 
charger. 

Continuous Power supply 
Output Rating (x 2) 

100W total available across 2 outputs: 

25V Supply (General System) 

2.25A (55W) max. 

1

35V Supply (Loop Driver feed only ) 2.50A 

(85W) 

max. 

0.75 Amps from the 25V supply is reserved for powering Internal 
circuits. The remainder of available power is for external loads 
(Conventional sounders, Aux supply & loop current). 

2

DC Output Voltage 

25.5V Max & 20V Min . 

Maximum Ripple Voltage 

<0.5V peak-peak on both 25V and 35V outputs. 

Battery Charger Outputs (x2) 

27.4 V nom at 20°C (temperature compensated). 

Quiescent current 

250mA + loop driver / option card c external circuits. 

Alarm current 

490mA + loop driver / option card c external circuits. 

3

Standby Batteries

24V sealed, lead acid. 

Minimum Capacity - 12 Ah (x4). 

Maximum Capacity - 24 Ah (x4). 

Printer Supply 

8-9V AC from integral mains transformer for optional panel-
mounted printer (to be supplied from upper ZX5Se unit only). 

 

Table 14 – ZX10Se Power Supply and Charger Specification 

 

                                                           

1

  Making use of the 35V output, to supply the loop driver cards directly, avoids the overall restrictions associated with loop 

supply on the ZX10Se. 

2

 Output = Battery voltage – 1.0 volts under mains power failure conditions. 

3

 Refer to Section 5.2.3 for a list of recommended batteries and suppliers. 

Содержание FW9003 Range

Страница 1: ...FW9003 Range Document No 996 174 000 1 Issue 01 installation manual This manual should not be left with the end user...

Страница 2: ...eral Introduction 11 3 4 2 2 ZX1Se ZX2Se Arrangement 11 3 4 2 3 ZX5Se Arrangement 12 3 4 2 4 General Battery Connection 12 3 4 3 Detection Loops 13 3 4 3 1 Loop Wiring Installation 14 3 4 3 2 EMC Comp...

Страница 3: ...ttention 36 5 1 2 Monthly Attention 36 5 1 3 Quarterly Attention 36 5 1 4 Yearly Attention 36 5 2 REPLACEMENT OF COMPONENTS 37 5 2 1 Lithium Standby battery 37 5 2 2 Liquid Crystal Alphanumeric Displa...

Страница 4: ...LOOP EMC ABSORBER INSTALLATION 24 FIGURE 25 RS485 SCREEN EARTH ARRANGEMENT 24 FIGURE 26 RECOMMENDED CABLE ROUTING ARRANGEMENT ZX1SE ZX2SE 26 FIGURE 27 RECOMMENDED CABLE ROUTING ARRANGEMENT ZX5SE 26 FI...

Страница 5: ...he ZX1Se ZX2Se ZX5Se and ZX10Se Fire Alarm Control Panels are 1 1 2 1 5 and 1 10 loop panels for use with analogue addressable devices from the following detector manufacturer ranges S90 Apollo Hochik...

Страница 6: ...al and local fire systems installation regulations specific to the country and location of the installation Consult with the appropriate Authority Having Jurisdiction AHJ for confirmation of the requi...

Страница 7: ...functions that are not required by EN54 These are outlined below Ancillary Function Manual Section Auxiliary supply output 3 4 6 Panel network output ports Port C 3 4 7 3 5 1 1 3 5 1 3 Master panel t...

Страница 8: ...Panel or 720 001 301 1 ZX1Se Fire Alarm Control Panel 722 001 301 1 2 Installation Manual 996 174 000 X 1 1 1 1 3 Commissioning Manual 996 175 000 X 1 1 1 1 4 User Manual 996 182 000 X 1 1 1 1 5 Refe...

Страница 9: ...tted When attaching the enclosure to a surface use mounting hardware capable of supporting this weight and reinforce the wall if necessary The ZX10Se can weigh in excess of 76 8kg with two 24Ah batter...

Страница 10: ...on the circuit boards 3 2 Dimensions and Fixing Points EARTH EARTH BATT MON AC MON 25V AUX O P RELAY 1 RELAY 1 RELAY 2 RELAY 2 SOUNDER OUTPUTS POWER LIMITED 24V 0V A A B B COM COM N C N C N O N O ZX2S...

Страница 11: ...e FS1 FS2 FS3 250V A S 250V A S 250V A S 3 15A 1 6A 5 0A FS1 FS2 FS3 ISOLATE ELSEWHERE F1 T 2A H 250V N L CPU Board Base card Transformer and Filter Assembly Power Supply Card AC Mains Terminal Block...

Страница 12: ...the loop driver module At least one loop driver board MUST be installed for the unit to operate as a Fire Alarm Control Panel The base card may be augmented by one ZX1Se one or two ZX2Se or up to thr...

Страница 13: ...errite Large Affix cable tie around wires below ferrite Maintain separation between the 120 230V and the low voltage wiring Do not route in the same trunking and keep apart in the enclosure For EMC Co...

Страница 14: ...h suitable earth fault protection incorporated in the building installation wiring The minimum cross sectional area of the mains cable should be 0 75mm and the supply should be fused with a 5A HRC ant...

Страница 15: ...commercially available silicon sealant 3 4 2 2 ZX1Se ZX2Se Arrangement Included in the packing is a battery cable kit Use the cable included in this kit to connect the negative terminal of battery No...

Страница 16: ...to allow a strap to be fitted 17Ah 17Ah Battery stop For battery sizes greater then 12Ah it may be necessary to cut off the spade terminals connected to the battery cables These should be replaced by...

Страница 17: ...f recommended cables The core size length of wiring run and detection circuit loading will produce a voltage drop along the length of the cable To determine if the installed loop driver can fully supp...

Страница 18: ...re made on the terminal blocks at the top of the base card 3 4 3 1 Loop Wiring Installation Data Power OUT Data Power OUT RETURN RETURN Form the loop by taking wires from the positive and negative ter...

Страница 19: ...ing is broken at each isolation point 3 4 3 2 EMC Compliance For EMC Compliance fit the Ferrite Absorbers supplied with the loop driver board around the SLC Loop cables Cables should be screened and s...

Страница 20: ...uired for the last Loop driver card and the supplied cable can be discarded ZX5Se 25V RELAY 1 RELAY 1 RELAY 2 RELAY 2 COM COM N C N C N O N O ZX2Se ZX1Se Figure 13 Adding Loop Driver Cards ZX1Se ZX2Se...

Страница 21: ...and must be verified by the Loop Battery Calculator Each sounder output is monitored for open and short circuits An end of line EOL resistor 6k8 0 5W minimum P N 170 073 682 must be fitted to the las...

Страница 22: ...the top cover of the back box Refer to the figure at the top of the previous page for wiring connection details to the Filter PCB Cable runs in excess of 1km 3200 are not recommended Otherwise the ca...

Страница 23: ...r fault conditions Terminate the Auxiliary Relay circuit wiring at the Filter PCB installed at the left hand side of the inside of the top cover of the back box Refer to the figure below for wiring co...

Страница 24: ...alled at the left hand side of the inside of the top cover of the back box Refer to the figure below for wiring connection details to the Filter PCB 24V 0V A A B B PL_LOOP2 RL2 RL1 To Filter PCB Facto...

Страница 25: ...5 Interface card in each panel using the Port C interface position For detailed information on networking and wiring installation for a panel network refer to document P N 996 075 3 4 7 2 Master Panel...

Страница 26: ...supplied with the RS485 Interface Card Refer to document 996 067 Each supervised peripheral device must be given an address The address can be in the range 1 126 Refer to the Installation Guide for ea...

Страница 27: ...t device on the link Continue wiring to all the units to be connected to the link connecting A to A and B to B EOL EOL B A B A Install EOL 150R 0 5W minimum P N 170 073 151 resistors in the spare term...

Страница 28: ...gether must be considered When wiring between RS485 cards and or peripherals if a drain earth wire is available it should not be bonded to the chassis at both ends of the link The drain earth wire sho...

Страница 29: ...X5Se or ZX10Se Fire Alarm Control Panels should be of an approved fire resistant type The drain earth wire where available should be connected to the earth tag on the cable entry gland and to a suitab...

Страница 30: ...O Sounder and AUX Power Power Limited Relay Outputs Not Power Limited RS485 RS232 Power Limited SLC Circuits Power Limited AC Mains Input Sounder Relay and AUX cables routed to factory fitted Filter...

Страница 31: ...ing any of the internal circuit boards Follow the specific instructions supplied with each item of additional equipment At least one loop driver board MUST be installed for the unit to operate as a Fi...

Страница 32: ...rd Card Figure 28 Positions for Additional Boards ZX2Se 3 5 1 3 ZX5Se Arrangement Serial Interface Cards Port D Port C Port B J1 Loop Driver Modules J2 Loop 1 Loop 2 Loop 3 Loop 4 Loop 5 TB10 TB7 TB8...

Страница 33: ...orrectly aligned and pushed fully home onto the pin headers The ZX2Se and ZX5Se Fire Alarm Control Panels only supports one manufacturer loop type at a time DO NOT install loop drivers of different ty...

Страница 34: ...ve the required transmission path integrity The system can be expanded to provide a data interface between the panel and control centres peripheral devices repeaters and annunciators and to network wi...

Страница 35: ...re to be installed on top of the loop driver boards loops 3 5 in the ZX5Se or ZX10Se panel Use the four nylon spacers M3 x 30mm supplied with the RS485 module to mount the loop driver card to the base...

Страница 36: ...ctor on the CPU Board Fasten down the cable along the inner lid using tie wraps and adhesive bases Connect the transformer 8 volt secondary winding leads to the 2 way connector on the printer driver b...

Страница 37: ...uxiliary 24V DC supply 4 4 ZXR5B Active 0 1252 0 1593 ZXR4B Passive 0 1252 0 1503 4 Way Relay EXP 014 0 0802 0 1603 8 Way Input EXP 029 0 0652 0 0972 4 way sounder EXP 015 0 1202 3 2203 40 way Event M...

Страница 38: ...y 24V DC supply 4 4 ZXR5B Active 0 1252 0 1503 ZXR4B Passive 0 1252 0 1503 4 Way Relay EXP 014 0 0802 0 1603 8 Way Input EXP 029 0 0652 0 0972 4 way sounder EXP 015 0 1202 3 2203 40 way Event Mimic LE...

Страница 39: ...to all signalling loops This should be based on the quantity of each device installed and the supply current required for the device 4 1 2 Alarm Load Refer to the manufacturer s published data sheets...

Страница 40: ...uld arrange to test the following 1 Check entries in the logbook inspect the panel s log taking appropriate remedial action where necessary 2 Examine all battery connections 3 Check the alarm fault an...

Страница 41: ...gives a life that is significantly better than most other display technologies The contrast of the LCD will gradually deteriorate as this part ages This item should therefore be changed when normal co...

Страница 42: ...rent 1mA Auxiliary Relay 2 volt free changeover outputs Relay 1 configured as Fault output Relay 2 configured as Fire output Contacts rated at 24V AC DC 1 Amp 0 6pF maximum Minimum switched load 1mA 5...

Страница 43: ...Relay 2 volt free changeover outputs Relay 1 configured as Fault output Relay 2 configured as Fire output Contacts rated at 30V AC DC 1 Amp maximum Minimum switched load 1mA 5V Sensor Circuit 1 to 5 p...

Страница 44: ...ature compensated 36mV C Quiescent current 90mA Loop driver option card current external circuits Alarm current 310mA Loop driver option card current external circuits 3 Standby Batteries 24V sealed l...

Страница 45: ...wering Internal circuits The remainder of available power is for external loads Conventional sounders Aux supply loop current 2 D C Output Voltage 25 5V Max 20V Min Maximum Ripple Voltage 0 5V peak pe...

Страница 46: ...y boxes 797 077 The ZX10Se contains two PSUs and each must be provided with separate mains supply wiring from separate isolators 7 2 Warnings and Cautions Refer to Section 1 2 Warnings and Cautions be...

Страница 47: ...S Installation Manual Document No 996 174 000 1 Revision 01 Page 43 7 6 Dimensions and Fixing Points The ZX10Se FACP has the following physical dimensions and fixing positions 500 215 180 35 1000 930...

Страница 48: ...board Zone Extender Card option upper unit Zone Extender Card option lower unit Lower Display Keyboard Lower ZX5Se unit CPU card upper unit CPU card lower unit Figure 34 Enclosure Arrangement ZX10Se 7...

Страница 49: ...Blue Green Yellow Green Yellow Brown Brown To Upper ZX5Se Panel Display Board To Lower ZX5Se Panel Display Board The drawing at right provides guidance on the routing of the separate mains wiring with...

Страница 50: ...e backed up with two sets of batteries If the size of these batteries is calculated to be in excess of 17Ah then they must be installed in two battery boxes suitable for Fire protection use such as ba...

Страница 51: ...ion 3 4 5 4 Auxiliary Supply Outputs Section 3 4 6 5 Panel Networking Graphics PC Interface Section 3 4 7 6 Peripheral Loop Section 3 4 8 7 RS485 Wiring Arrangements Section 3 4 9 8 High Integrity Loo...

Страница 52: ...uts 20mm 24 top 24 bottom Sounder Output 4 programmable outputs x2 Open and short circuit monitored 6k8 EOL resistors P N 170 073 682 1A maximum output current Minimum switched current 1mA Auxiliary R...

Страница 53: ...s The remainder of available power is for external loads Conventional sounders Aux supply loop current 2 DC Output Voltage 25 5V Max 20V Min Maximum Ripple Voltage 0 5V peak peak on both 25V and 35V o...

Страница 54: ...ZX Fire Alarm Control Panels Page 50 Document No 996 174 000 1 Revision 01 Installation Manual NOTES...

Страница 55: ......

Отзывы: