26

 

 

 

 

CONFIGURATION 2

 

 

The configuration shown in the figure is set. 

 

 

Connections on the control unit 

 

 

 

 

 

 

 

 

 

 

 

Connections on stove

s rear panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connections on the heating system 

(the following schematic is only illustrative)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The system includes: the hydro stove Boiler Probe (

S

), the hydro stove Pump (

P1

), Valve (

P2

), Boiler/Puffer Probe (

S3

).

 

 

 

Electrovalve (P2)

 

17: towards heating system 18: towards domestic hot water

 

Probe ACS/

DHW (S3)

 

17: vers l'installation            18: vers Boiler ACS/DHW

 

Probe ACS/DHW 

(S3)

 

 

Electrovalve (P2)

 

For the models: TECNIKA TURBO GLASS, TECNIKA FOR HOME, TURBO TOP, TURBO GLASS, PRESTIGE

 

For the models: ALADINO, ELEGANCE, CLESSIDRA, ERGONOMIC, COMPACT, VISION, SLOT VISION, DOLBY

 

EN

 

Содержание ALADINO

Страница 1: ...1 USER MANUAL Installation use and maintenance ALADINO CLESSIDRA ELEGANCE ERGONOMIC PRESTIGE TURBO TOP TURBO GLASS TURBO COMPACT VISION SLOT VISION DOLBY TECNIKA FOR HOME TECNIKA GLASS 2022 AQUA Off...

Страница 2: ...tting COMBUSTION Automatic combustion regulation by FCS Calibration FIRE PROTECTION TOUCH DISPLAY RADIO DISPLAY Introduction Button description OPERATING STATUS Check Up Ignition Normal Modulation Com...

Страница 3: ...horough reading of the user and maintenance manual and scru pulously observe the indications and signs located on the hydro stove The plug of the power cable must be connected only AFTER the installa...

Страница 4: ...ation in small rooms or bedrooms can take place only if the stove is her metic hermetic system and air required for the combustion must be drawn directly from the outside through a tube All local regu...

Страница 5: ...CURVE PROTECTION CAP INSULATED FLUE ASH DEPOSIT IN THE CURVE CHIMNEY FLUE INSIDE AN OLD CHIMNEY CORRECT INSTALLATION CHIMNEY WITH COVER PLATE INSULATION OPEN 45 CURVE OLD CHIMNEY FLUE T WITH INSPECTIO...

Страница 6: ...the boiler straight under the power connector it has a two pin connector coupling with two buttons one black and one red The connection to the thermo stat assures the function that the boiler can go i...

Страница 7: ...a properly sized system to dispose of the power generated by the appliance For the sizing of the system it is recommended to rely on a thermo technician To dissipate excess heat the boiler must be co...

Страница 8: ...to check the quality of the flame by comparing it to the images in the examples above since certain conditions of use and installation could in any case lead to machine malfunctions In any case in th...

Страница 9: ...used to avoid them Owners managers and users of buildings and facilities must ensure the safety of people animals and objects Owners managers and users of buildings and facilities are responsible for...

Страница 10: ...h your finger and swipe vertically Press to Confirm Press to Cancel Press to Edit Press to go back to the previous page Press to go back to the Homepage To unlock the standby screen press on the displ...

Страница 11: ...eful Hydraulic System Configuration P26 2 3 10 11 are active The Maximum value can be programmed by setting Thermostat Th83 Delivery Thermostat It can be viewed if the Return Delivery Probe and the us...

Страница 12: ...e or deactivate the automatic burn pot cleaning system this process takes place during the ignition phase It is recommended to keep it activated Mixing Valve It appears only if an output is configured...

Страница 13: ...ect the day of the week you want to program press on the on off times and scroll up or down to change them There are 3 time slots for each day Brightness Minimum Brightness Standby display Control pan...

Страница 14: ...ed with a and the rela tive error code Select between the periods Monday Friday and Saturday Sunday There are 3 phases for Monday Friday and 3 phases for Saturday Sunday The three types of programs ar...

Страница 15: ...seconds P6 Decrease power Scroll through Menu Decrease parame ter values DESCRIPTION OF THE MENUS The boiler is equipped with various functions available in the individual programming menus Some of th...

Страница 16: ...es use the keys P4 and P6 to increase or decrease the value and confirm the setting by pressing P3 Press P1 to exit the menu Chrono This menu allows you to set the switch on and switch off time slots...

Страница 17: ...ch on the boiler using the Chrono function Tuesday Wednesday Thursday Friday Monday Weekly senai Week end Daily Monday ON OFF 00 00 00 00 V 00 00 00 00 00 00 00 00 Mon Sun ON OFF 00 00 00 00 V 00 00 0...

Страница 18: ...lows you to read the system error list Attention to be used only by an authorized MORETTI DESIGN techni cian Auger Calibration This item allows you to adjust auger rotation speed Attention to be used...

Страница 19: ...Room Temperature measured by the remote Chrono Activation Current time Descrizione Tasti Tasto Funzione Descrizione Sleeping Mode By pressing the button when the main screen is displayed the radio dis...

Страница 20: ...t is possible to change the combustion power level at any time but the change is effective only during Normal mode The power level ranges from 1 to 5 Increasing the power level increases the pellet co...

Страница 21: ...e items of the menu use the keys To confirm the data press SET To exit press ESC Daily Select the day of the week you want to program and set the switch on and switch off times There are 3 time slots...

Страница 22: ...T Recipe Power Thermostats Chrono Settings Informations Radio Standby Menu to switch off the radio display completely To switch on the radio display again To reactivate the remote control press first...

Страница 23: ...t Key Tone Date and Time Secondary Information This menu allows you to view some of the system operating para meters To scroll through the menu use the keys press ESC to exit Radio Test This menu allo...

Страница 24: ...ower Thermostats Chrono Information Settings Service WiKey Thermostat Secondary Information Radio Test Change Code Reset Cleaning Screw Feeder Calibra Screw Feeder Calibration Max 7 Set 0 Min 7 Automa...

Страница 25: ...e available values E g 1 2 3 Minimum Average Maximum After 3 seconds the value is saved and the normal display reappears WIFI CONFIGURATION To configure thermo stoves equipped with a WiFi module it is...

Страница 26: ...If the domestic hot water kit is installed it is not necessary to change the setting on the hydro stove Connections on the control unit Connections on the heating system the following figure is only...

Страница 27: ...s the hydro stove Boiler Probe S the hydro stove Pump P1 Valve P2 Boiler Puffer Probe S3 Electrovalve P2 17 towards heating system 18 towards domestic hot water Probe ACS DHW S3 17 vers l installation...

Страница 28: ...tem includes the hydro stove Boiler Probe S1 the hydro stove Pump P1 Boiler Puffer Probe S1 the heating system pump Pump P2 Probe Puffer Boiler S1 Probe Puffer Boiler S1 Pump P2 For models ALADINO ELE...

Страница 29: ...s only illustrative The system includes the hydro stove Boiler Probe S1 the hydro stove Pump P1 Boiler Puffer Probe S1 the heating system pump Pump P2 For models ALADINO ELEGANCE CLESSIDRA ERGONOMIC C...

Страница 30: ...uffer Probe S1 Electrovalve P2 DHV probe S3 17 towards heating system 18 towards domestic hot water Electrovalve Probe S1 Puffer Boiler Pump P3 For models ALADINO ELEGANCE CLESSIDRA ERGONOMIC COMPACT...

Страница 31: ...Pump P1 heating system Pump P3 Puffer Probe S1 Electrovalve P2 DHV probe S3 Electrovalve P2 Probe S1 Puffer Boiler Pump P3 17 towards heating system 18 towards domestic hot water For models ALADINO EL...

Страница 32: ...be installed according to standard regulations and directions contained in this manual PRESSURE SWITCH BROKEN Unblock and turn on the stove if the error occurs immediately it is likely that the pressu...

Страница 33: ...echnician Er11 The error occurs due to problems with the internal clock CLOCK ERROR Turn off the main switch reset the time and date page 11 then unblock If the error persists replace the battery on t...

Страница 34: ...front door or open pellet door FRONT DOOR OR PELLET DOOR OPEN FOR MORE THAN 120 SE CONDS Unlock and check if the doors have been closed correctly If the error persists contact an authorised technician...

Страница 35: ...IN11 Input IN12 Input IN11 Storage Tank Probe Flowmeter Room Thermostat OPTIONAL Limit Switch Micro Burn Pot Cleaning ALL CLEAN MODELS ONLY Flowmeter Sensor Pressure Sensor Combustion Fan Encoder Wat...

Страница 36: ...35 Remote Control Cod PSYSI04000005 Off Output to be configured Output to be configured Output to be configured Output to be configured ELECTRONIC CONTROL UNIT Code PSYSS04000003 EN...

Страница 37: ...I FI 4HEAT system Code PSYSF09000002 EN LINE Combustion Fan Burn Pot Cleaning Motor Tube Bundle Cleaning Motor Spark plug Screw Feeder Safety Thermostat Pressure Switch Pump Tube Bundle Cleaning Motor...

Страница 38: ...e Exaust Probe 32 Rosso 33 IN2 Auger Motor Encoder 34 GND 35 IN3 Micro Switch Pellet door and Front door 36 GND 37 IN4 Water probe 38 GND 39 IN5 Encoder Sensor Exaust Ventilator 40 GND 41 V 42 Vc Flow...

Страница 39: ...e diluents can damage the stove s surfaces To ensure that the hydro stove always has an optimal combustion and to avoid malfunctions frequent cleaning operations must be carried out The frequency of t...

Страница 40: ...EV 07 2022 ENG Moretti Fire s r l ITALY www morettidesign it The Moretti fire s r l assumes no responsibility for any errors in this manual and the right to modify without notice features of its produ...

Отзывы: