7

 

 

Use wood pellets with a diameter of 6mm, average length of 30mm, 

with humidity characteristics in compliance with the EN PLUS

-

UNI 

EN 14961

-

2 standard, class A1.

 

 

Warning: 

Before filling the tank, make sure that at the bottom there are 

no odd materials.

 

    

 

Ignition mode

 

Make  sure  that the  boiler  is connected  to the  electrical  power  and  that 

the switch on the back is on position 

I

 

 

 

FUSIBILE

 

INTERRUTTORE

 

CONNETTORE

 

 

satisfied, the boiler goes into Modulation phase, phase in which the fuel 

consumption will be minimal.

 

Combustion power setting

 

 

It is possible to modify the combustion power level at any time, but the 

change is effective only in Run Mode. The power level ranges from 1 to 

5. Increasing the power equals to a high pellet consumption.

 

 

Note: Turn off the stove in case of damage or malfunction.

 

 

COMBUSTION

 

The  combustion  is  a chemical  reaction  in  which  a  fuel  (pellets)  and  an 

oxidiser (air) are combined, thanks to an ignition (resistance), in order to 

produce heat. They should be dosed in suitable proportions so that the 

combustion  can  take  place.  Following  are  some  examples  with  a  de-

scription  and  adjustment  procedure  to  obtain  an  optimal 

combustion.

 

 

Automatic combustion regulation by FCS 

 

 

The  FCS  (Fire  Control  System)  is  an  automatic  combu-

stion control system that always keeps the product efficiency high. 

 

 

The system self

-

adjusts the dosage of fuel (pellets) and combustion air 

based on the draft read by a flow meter sensor located inside the boiler..

 

 

The FCS system is therefore able to maintain an optimal flame even in 

the event of imperfect conditions (aspiration, flue draft, etc.), when these 

occur occasionally. 

 

 

ATTENTION: 

the FCS system  does  not compensate  for structural  and 

continuous conditions of use and installation that are not up to standard, 

or in any case do not comply with the instructions given in the following 

manual regarding the quality of the pellets, flue or combustion air intake. 

 

 

Therefore, it is advisable to check the quality of the flame by comparing it 

to the images in the examples above, since certain conditions of use and 

installation could in any case lead to machine malfunctions. 

 

 

In  any  case,  in  the  presence  of 

NOT  OPTIMAL 

combustion  with  the 

automatic combustion regulation system activated, it is recommended to 

contact an authorized 

MORETTI DESIGN 

technician. 

 

 

Calibration

 (Item: Customizations 

-

 Service)

 

 

Note

: On models where the FCS is installed, the automatic combustion 

correction range can be adjusted in the 

FCS

 item. 

 

On  models  without  the  system,  combustion  can  be  adjusted  manually 

using the 

Auger Calibration 

and 

Fan Calibration 

functions. 

 

Fill the auger by using the 

LOAD

 function. During the ignition or even in 

run mode, the front door must always be kept closed.

 

 

Check  TOUCH  DISPLAY  (pag.  9)  and/or  RADIO  DISPLAY  (pag.18) 

sections  for  ignition,  room  temperature  and  combustion  power 

setting and for any further information.

 

 

OPERATING STATUS

 

 

Check Up

 

This  phase  starts  as  soon  as  the  the  On/Off  button  is  pressed.  During 

this phase the exhaust fan goes at maximum rpm, at the same time the 

system checks the probes and the safety devices.

 

Ignition

 

 

Once  the  Check  Up  phase  is  over,  the  system  switches  to  the  ignition 

phase. The system automatically cleans the brazier, at the end of which 

the cochlea loads a certain quantity of pellets and the ignition resistance 

turns  on.  The  system  waits  for  the  combustion  to  start,  after  which  it 

starts  dosing  small  quantities  of  pellets  to  raise  the  temperature  of  the 

fumes.

 

Run Mode

 

After the ignition, the system goes into Run Mode. During this phase the 

heating fan is activated and the system operates on the set combustion 

power level.

 

 

Modulation

 

 

During  the  working  phase  in  Run mode,  the  purpose  of  the  boiler is to 

reach the boiler temperature set; when the set is 

 

NON

-

OPTIMAL combustion, the flame is high and weak and of an oran-

ge color with a high quantity of unburnt pellets in the brazier. 

 

 

NO

 

 

 

 

Pellet loading

 

 

Fill the fuel tank with wooden pellets available on the market. Open the 

lid on the top and then pour the fuel in. It is recommended to close the 

pellet tank lid properly.

 

EN

 

Содержание ALADINO

Страница 1: ...1 USER MANUAL Installation use and maintenance ALADINO CLESSIDRA ELEGANCE ERGONOMIC PRESTIGE TURBO TOP TURBO GLASS TURBO COMPACT VISION SLOT VISION DOLBY TECNIKA FOR HOME TECNIKA GLASS 2022 AQUA Off...

Страница 2: ...tting COMBUSTION Automatic combustion regulation by FCS Calibration FIRE PROTECTION TOUCH DISPLAY RADIO DISPLAY Introduction Button description OPERATING STATUS Check Up Ignition Normal Modulation Com...

Страница 3: ...horough reading of the user and maintenance manual and scru pulously observe the indications and signs located on the hydro stove The plug of the power cable must be connected only AFTER the installa...

Страница 4: ...ation in small rooms or bedrooms can take place only if the stove is her metic hermetic system and air required for the combustion must be drawn directly from the outside through a tube All local regu...

Страница 5: ...CURVE PROTECTION CAP INSULATED FLUE ASH DEPOSIT IN THE CURVE CHIMNEY FLUE INSIDE AN OLD CHIMNEY CORRECT INSTALLATION CHIMNEY WITH COVER PLATE INSULATION OPEN 45 CURVE OLD CHIMNEY FLUE T WITH INSPECTIO...

Страница 6: ...the boiler straight under the power connector it has a two pin connector coupling with two buttons one black and one red The connection to the thermo stat assures the function that the boiler can go i...

Страница 7: ...a properly sized system to dispose of the power generated by the appliance For the sizing of the system it is recommended to rely on a thermo technician To dissipate excess heat the boiler must be co...

Страница 8: ...to check the quality of the flame by comparing it to the images in the examples above since certain conditions of use and installation could in any case lead to machine malfunctions In any case in th...

Страница 9: ...used to avoid them Owners managers and users of buildings and facilities must ensure the safety of people animals and objects Owners managers and users of buildings and facilities are responsible for...

Страница 10: ...h your finger and swipe vertically Press to Confirm Press to Cancel Press to Edit Press to go back to the previous page Press to go back to the Homepage To unlock the standby screen press on the displ...

Страница 11: ...eful Hydraulic System Configuration P26 2 3 10 11 are active The Maximum value can be programmed by setting Thermostat Th83 Delivery Thermostat It can be viewed if the Return Delivery Probe and the us...

Страница 12: ...e or deactivate the automatic burn pot cleaning system this process takes place during the ignition phase It is recommended to keep it activated Mixing Valve It appears only if an output is configured...

Страница 13: ...ect the day of the week you want to program press on the on off times and scroll up or down to change them There are 3 time slots for each day Brightness Minimum Brightness Standby display Control pan...

Страница 14: ...ed with a and the rela tive error code Select between the periods Monday Friday and Saturday Sunday There are 3 phases for Monday Friday and 3 phases for Saturday Sunday The three types of programs ar...

Страница 15: ...seconds P6 Decrease power Scroll through Menu Decrease parame ter values DESCRIPTION OF THE MENUS The boiler is equipped with various functions available in the individual programming menus Some of th...

Страница 16: ...es use the keys P4 and P6 to increase or decrease the value and confirm the setting by pressing P3 Press P1 to exit the menu Chrono This menu allows you to set the switch on and switch off time slots...

Страница 17: ...ch on the boiler using the Chrono function Tuesday Wednesday Thursday Friday Monday Weekly senai Week end Daily Monday ON OFF 00 00 00 00 V 00 00 00 00 00 00 00 00 Mon Sun ON OFF 00 00 00 00 V 00 00 0...

Страница 18: ...lows you to read the system error list Attention to be used only by an authorized MORETTI DESIGN techni cian Auger Calibration This item allows you to adjust auger rotation speed Attention to be used...

Страница 19: ...Room Temperature measured by the remote Chrono Activation Current time Descrizione Tasti Tasto Funzione Descrizione Sleeping Mode By pressing the button when the main screen is displayed the radio dis...

Страница 20: ...t is possible to change the combustion power level at any time but the change is effective only during Normal mode The power level ranges from 1 to 5 Increasing the power level increases the pellet co...

Страница 21: ...e items of the menu use the keys To confirm the data press SET To exit press ESC Daily Select the day of the week you want to program and set the switch on and switch off times There are 3 time slots...

Страница 22: ...T Recipe Power Thermostats Chrono Settings Informations Radio Standby Menu to switch off the radio display completely To switch on the radio display again To reactivate the remote control press first...

Страница 23: ...t Key Tone Date and Time Secondary Information This menu allows you to view some of the system operating para meters To scroll through the menu use the keys press ESC to exit Radio Test This menu allo...

Страница 24: ...ower Thermostats Chrono Information Settings Service WiKey Thermostat Secondary Information Radio Test Change Code Reset Cleaning Screw Feeder Calibra Screw Feeder Calibration Max 7 Set 0 Min 7 Automa...

Страница 25: ...e available values E g 1 2 3 Minimum Average Maximum After 3 seconds the value is saved and the normal display reappears WIFI CONFIGURATION To configure thermo stoves equipped with a WiFi module it is...

Страница 26: ...If the domestic hot water kit is installed it is not necessary to change the setting on the hydro stove Connections on the control unit Connections on the heating system the following figure is only...

Страница 27: ...s the hydro stove Boiler Probe S the hydro stove Pump P1 Valve P2 Boiler Puffer Probe S3 Electrovalve P2 17 towards heating system 18 towards domestic hot water Probe ACS DHW S3 17 vers l installation...

Страница 28: ...tem includes the hydro stove Boiler Probe S1 the hydro stove Pump P1 Boiler Puffer Probe S1 the heating system pump Pump P2 Probe Puffer Boiler S1 Probe Puffer Boiler S1 Pump P2 For models ALADINO ELE...

Страница 29: ...s only illustrative The system includes the hydro stove Boiler Probe S1 the hydro stove Pump P1 Boiler Puffer Probe S1 the heating system pump Pump P2 For models ALADINO ELEGANCE CLESSIDRA ERGONOMIC C...

Страница 30: ...uffer Probe S1 Electrovalve P2 DHV probe S3 17 towards heating system 18 towards domestic hot water Electrovalve Probe S1 Puffer Boiler Pump P3 For models ALADINO ELEGANCE CLESSIDRA ERGONOMIC COMPACT...

Страница 31: ...Pump P1 heating system Pump P3 Puffer Probe S1 Electrovalve P2 DHV probe S3 Electrovalve P2 Probe S1 Puffer Boiler Pump P3 17 towards heating system 18 towards domestic hot water For models ALADINO EL...

Страница 32: ...be installed according to standard regulations and directions contained in this manual PRESSURE SWITCH BROKEN Unblock and turn on the stove if the error occurs immediately it is likely that the pressu...

Страница 33: ...echnician Er11 The error occurs due to problems with the internal clock CLOCK ERROR Turn off the main switch reset the time and date page 11 then unblock If the error persists replace the battery on t...

Страница 34: ...front door or open pellet door FRONT DOOR OR PELLET DOOR OPEN FOR MORE THAN 120 SE CONDS Unlock and check if the doors have been closed correctly If the error persists contact an authorised technician...

Страница 35: ...IN11 Input IN12 Input IN11 Storage Tank Probe Flowmeter Room Thermostat OPTIONAL Limit Switch Micro Burn Pot Cleaning ALL CLEAN MODELS ONLY Flowmeter Sensor Pressure Sensor Combustion Fan Encoder Wat...

Страница 36: ...35 Remote Control Cod PSYSI04000005 Off Output to be configured Output to be configured Output to be configured Output to be configured ELECTRONIC CONTROL UNIT Code PSYSS04000003 EN...

Страница 37: ...I FI 4HEAT system Code PSYSF09000002 EN LINE Combustion Fan Burn Pot Cleaning Motor Tube Bundle Cleaning Motor Spark plug Screw Feeder Safety Thermostat Pressure Switch Pump Tube Bundle Cleaning Motor...

Страница 38: ...e Exaust Probe 32 Rosso 33 IN2 Auger Motor Encoder 34 GND 35 IN3 Micro Switch Pellet door and Front door 36 GND 37 IN4 Water probe 38 GND 39 IN5 Encoder Sensor Exaust Ventilator 40 GND 41 V 42 Vc Flow...

Страница 39: ...e diluents can damage the stove s surfaces To ensure that the hydro stove always has an optimal combustion and to avoid malfunctions frequent cleaning operations must be carried out The frequency of t...

Страница 40: ...EV 07 2022 ENG Moretti Fire s r l ITALY www morettidesign it The Moretti fire s r l assumes no responsibility for any errors in this manual and the right to modify without notice features of its produ...

Отзывы: