background image

 

The Interface Solution Experts 

21

HIM

Smart HART

 Loop 

Interface and Monitor

Analog Outputs Tab

The HIM comes with either one (MB1AO), two (2AO) 
or three (3AO) analog outputs.  The 

Analog Outputs 

tab allows you to specify which HART variable is to 
be monitored as the source of the analog output, the 
input range and output range, and how the output will 
react when the variable input is out of range.  To pro-
gram the Analog Outputs parameters, change the set-
tings in the 

Output1/2/3 

boxes, then press 

Quick Set

.  

See the descriptions below of the various sections of 
the screen. 

 

Source

Source

 defines the variable that the analog output 

will monitor.  Notice that selecting one of the scaled 
outputs will require you to make changes to the 

Scaling

 tab, and selecting the Custom Curve option 

will require you to make changes to the 

Custom Curve

 

tab. 

Figure 14.

  Analog Outputs Tab 

Input/Output Range

The 

Input 

or

 Output Range

 defines the range of the 

source input and the range of the analog output.  
These two sets of fields can be used to scale the 
HIM’s output.
For example, you have a vortex flow meter with 
an imbedded RTD that measures the process 
temperature, and that temperature is assigned to 
the HART Secondary Variable.  The full range of the 
RTD sensor is from –400°F to +1760°F, but your flow 
stream will always be between 0° and 400°F.  To scale 
the analog output, for Output 1, set the 

Source

 as SV. 

Set the 

Input Range

 to 0° and 400°F, and the 

Output 

Range

 to 4mA to 20mA.  Click

 Quick Set

 to download 

the new configuration file to the HIM.

Output Current Box

The 

Output Current

 Box on the 

Analog Outputs

 Tab 

displays up-to-the-second information on the value, in 
mA, of the analog output.

Fail Mode

The 

Fail Mode 

setting determines how the HIM will 

respond when its monitored input fails.  If 

Fail Mode

 is 

set to

 High

 and the measured input goes out of range, 

or any detected error occurs in the HART transmitter, 
the analog output will output a 23.6mA signal.  If Fail 
Mode is set to 

Low 

and the measured input goes out 

of range, or any detected error occurs in the HART 
transmitter, the analog output will output a signal that 
is 90% of the lower range value below 4mA; it will 
output 0mA if the lower range is set to 0mA.

If 

Fail Mode 

is set to 

Hold Last

, the HIM will continue to 

output the last value it recorded before the input failed.  
If 

Fail Mode 

is set to 

Hold Last Then High 

or 

Hold Last 

Then Low

, the HIM will continue to output the last 

value recorded for a set amount of time (according to 
Hold Last Duration box), then either fail high or fail low, 
respectively.

Quick Set Button

The 

Quick Set

 button causes the software to configure 

the instrument’s analog output settings to match those 
currently entered in the PC Software. 

Trim Button

The 

Trim

 button brings up the Trim Menu, allowing 

you to set the device’s output to match the reading 
of the loop.  Refer to the 

Programming the Trimming 

Parameters 

section of this manual for more 

information.

Содержание HIM

Страница 1: ...D e m a n d M o o r e R e l i a b i l i t y All product names are registered trademarks of their respective companies User s Manual HIM No 224 778 00G November 2018 Smart HART Loop Interface and Moni...

Страница 2: ...s Europe Australia 16650 Schoenborn Street North Hills California 91343 6196 U S A Tel 818 894 7111 Fax 818 891 2816 E mail info miinet com TOLL FREE 1 800 999 2900 www miinet com 1 Lloyds Court Manor...

Страница 3: ...Inputs 5 Outputs 5 Options 5 TX Power Supply 5 HIM Dimensions 6 Specifications 7 Configuring the HIM 8 Terminal Designations 9 Installing the HIM 10 Installing the HIM into the Loop 10 Bench Checking...

Страница 4: ...nting 30 Making the Electrical Connections 30 Recommended Ground Wiring Practices 30 CE Conformity 30 Power Sourcing Parameters for General Locations Intrinsically Safe and Non Incendive Type N Applic...

Страница 5: ...es uses the model and serial numbers of our instruments to track information on each unit that we sell and service If a problem occurs with your HIM check for a tag affixed to the unit listing these n...

Страница 6: ...Quaternary Variable Process Data and Instrument Diagnostic Information HIM HART Interface Module Breaks Out Data from Smart HART Instruments HART Primary Master Smart HART Multivariable Mass Flow Tra...

Страница 7: ...nge Configurable from 1 to 247 Unit will assume a MODBUS address of 01 by default Baud Rate Interface supports the following 300 600 1200 4800 9600 19 2k MODBUS interface will support even odd and no...

Страница 8: ...folder 2 Double click the installation program located in the folder Follow the prompts to correctly install the program Once the Configuration Program is installed on the PC the unit can be connecte...

Страница 9: ...6 10 11 12 HART Input 2 MODBUS Outputs and 1 Analog Output MB1AO Dual Alarm 2PRG HIM 1 2 3 7 8 9 10 11 12 TX HIM 10 11 12 IN IN A MODBUS 2 1 2 3 4 5 6 10 11 12 HART Input 2 MODBUS Outputs MB No Alarm...

Страница 10: ...Computer Moore Industries PC Configuration Software Communication Cable 250 ohms 0 01 Accurate to 0 009 of span e g HP Model 3487A 24Vdc 10 Microsoft Windows based PC 16Mb free RAM 20MB free disk spa...

Страница 11: ...OM 0 ADDR COMMON NC normally closed NO normally open 4 20mA DCS Sensor Input NO NC 24Vdc Power Source R HART Multivariable Field Instrument Temperature Pressure Level and Flow Analog Output tied to An...

Страница 12: ...ADY INPUT TRIP 2 TRIP 1 COM 0 ADDR COMMON NC normally closed NO normally open 4 20mA DCS Sensor Input NO NC DC GND 24Vdc Power Source DCC R must be 250 and 1100 Ohms R HART Multivariable Field Instrum...

Страница 13: ...The Interface Solution Experts 13 HIM Smart HART Loop Interface and Monitor Figure 7 HIM Output Wiring with Active Output and Passive Output...

Страница 14: ...device was configured HIM Tag A phrase used to identify a HIM Figure 8 HIM PC Configuration Software Screen HIM Device Status Displays how the HIM is functioning giving a brief summary of any errors...

Страница 15: ...ing the HIM to function as the Primary HART Master in the application means that any other HART device in the loop must be configured either as a HART Secondary Master 1 per loop or as a HART Slave up...

Страница 16: ...9 HART Slave Device Long Format Address Settings Screen To convert HEX to Decimal code perform the following steps Access the Calculator feature in Microsoft Windows by opening the Start menu Next sel...

Страница 17: ...econd increments Directly below the Toggle checkbox are two list boxes to select the variables that you would like to be displayed Notice that if you select a scaled variable it is important to check...

Страница 18: ...r failure has occurred in the connected HART device Configuration Changed Bit 6 Relay trips whenever it detects that the connected HART device has had its configuration changed Cold Start Bit 5 Relay...

Страница 19: ...s information returned by certain HART instruments This provides flexibility to the requirement of alarming on additional status information Choosing this feature you are given the ability to spec ify...

Страница 20: ...n Custom Curve The middle section of the screen displays the custom curve table After enabling custom curve mode and setting the variable to be monitored continue by selecting the number of points for...

Страница 21: ...set the Source as SV Set the Input Range to 0 and 400 F and the Output Range to 4mA to 20mA Click Quick Set to download the new configuration file to the HIM Output Current Box The Output Current Box...

Страница 22: ...til the analog output matches the minimum point 4mA for a 4 20mA output when you click the Fix Output at Low Point button After the low point is trimmed press the Fix Output at High Point button Read...

Страница 23: ...to measure the level of a tank in either centimeters inches or PSI Since the tank is only 300 centimeters 10 feet high the full range of the primary variable PV output from the DP transmitter is 0 4 3...

Страница 24: ...ast significant bits in the first register Selecting Swapped MSW most significant word will reverse the order storing the most signifi cant bits in the first register and the least significant bits in...

Страница 25: ...erature Pressure Level Flow Multivariable HART Communicator can be connected anywhere on the loop COM IN TX IN MODBUS output with MODBUS option A B S RS485 RS232 Converter TO serial COM port of PC MOD...

Страница 26: ...it 1 EEPROM fail Bit 2 EEPROM configuration checksum error Bit 3 EEPROM calibration checksum error Bit 4 EEPROM blank Bit 5 Out of range error Bit 6 Division by zero error Bit 7 Configuration data bad...

Страница 27: ...te 1 Additional Status Byte 2 Additional Status Byte 3 Additional Status Byte 4 HART Primary variable float format HART Secondary variable float format HART Tertiary variable float format HART Quatern...

Страница 28: ...aming error Overrun error Parity error No error Undefined Invalid selection Passed parameter too large Passed parameter too small Too few bytes received Device specific command error In write protect...

Страница 29: ...nformation can be considered as valid Another example using Tables 4 and 5 the following value in MODBUS Register 13 0000 0000 0001 1001 binary or 19 hexadecimal or 25 decimal implies Primary variable...

Страница 30: ...eceiver and a transmitter SPA 2 HIM etc Hence your shield ground connections should be appropriate for the type of signal line being shielded The shield should be grounded at the receiver and not at t...

Страница 31: ...and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This policy shall not...

Отзывы: