HIM

Smart HART

 Loop 

Interface and Monitor

HART Tab

To program the HART parameters, change the settings 
in the 

Communications Settings

 box, then press 

Quick Set

.  See the descriptions below of the various 

sections of the screen.  
 

HART Address

The 

HART Address

 is the address of the HART device 

that the HIM will be monitoring.  
 

Number of Retries

 

The 

Number of Retries

 can be set between 1 and 

9, and will determine how many times the HIM will 
attempt to poll the HART transmitter (without success), 
before it indicates a HART Fault condition.
 

Normal/Burst/Listen (Passive) Modes

The HIM can operate in one of four modes: 

Normal

Burst

, or 

Listen (Passive)

 and 

Listen (Specified Slave)

In each of these modes, the HIM attempts to find a 
HART transmitter. 

In 

Normal

 mode, the HIM polls the HART loop for a 

transmitter, then polls the HART instrument twice per 
second, requesting the current process status and 
the HART instrument’s diagnostic status. The HART 
instrument responds with the requested data.

In 

Burst

 mode, the monitored HART instrument is 

programmed to continuously transmit its process 
variable and health status. The HIM samples the 
continuous HART data three times per second.

Listen (Passive)

 mode allows the HIM to operate 

on a loop that already has primary and secondary 
HART masters. In 

Listen

 

(Passive)

 mode, the monitor 

connects passively, continuously sampling HART data 
from a smart instrument without affecting normal loop 
operation.  When using this mode, either the monitored 
smart HART instrument must be set in 

Burst Mode

 or 

a HART master must be continuously polling the smart 
HART slave device.

The HART protocol  allows for two communications 
masters on the loop, a Primary and a Secondary. 
Setting the HIM to function as the Primary HART 
Master in the application means that any other HART 
device in the loop must be configured either as a 
HART Secondary Master (1 per loop) or as a HART 
Slave (up to 16 per loop). Conversely, setting the HIM 
to function as the Secondary HART Master allows 
other HART devices to function either as a Primary 
Master or as slaves. Configuring more than one device 
on a single loop as a Primary or Secondary HART 
Master will cause a communications failure.

Listen (Specified Slave)

 When multiple HART instruments are present, the 

Listen (Passive)

 mode cannot be used because data 

returned from one instrument will overwrite the data 
previously stored in the HIM.  If multiple HART slave 
instruments are communicating on the loop, the HIM 
will overwrite its internal HART data sets with the latest 
device read from the bus, no matter where the data 
originates.  To allow selective monitoring on a multi-
instrument loop, and to allow multiple HIMs to be used 
on a digital loop, the 

Listen (Specified Slave)

 feature is 

used.

If the HIM is in “Listen” mode it is not a HART com-
munication master and therefore is not in control of 
communication.  Other HART masters are controlling 
the polling of slaves and the HIM can only “Listen”.

The HIM must be able to detect when it has not heard 
from its assigned slave device so that it can declare 
a “No HART” input and force outputs to the values 
specified by the user.  The HIM must therefore be told 
to wait an appropriate amount of time for the slave 
device to send its message before the HIM declares 
“No HART”.  This timing coordination is accomplished 
with 

Timeout Period

.

Timeout Period

 is a value between 3 and 30sec and 

must be greater than the period between polls by the 
HART master of the Specified Slave.  For example, 
assume that there are five HART transmitters on the 
same multi-drop loop as the HIM.  The HART master is 
configured to poll each device every second.   

Содержание HIM

Страница 1: ...D e m a n d M o o r e R e l i a b i l i t y All product names are registered trademarks of their respective companies User s Manual HIM No 224 778 00G November 2018 Smart HART Loop Interface and Moni...

Страница 2: ...s Europe Australia 16650 Schoenborn Street North Hills California 91343 6196 U S A Tel 818 894 7111 Fax 818 891 2816 E mail info miinet com TOLL FREE 1 800 999 2900 www miinet com 1 Lloyds Court Manor...

Страница 3: ...Inputs 5 Outputs 5 Options 5 TX Power Supply 5 HIM Dimensions 6 Specifications 7 Configuring the HIM 8 Terminal Designations 9 Installing the HIM 10 Installing the HIM into the Loop 10 Bench Checking...

Страница 4: ...nting 30 Making the Electrical Connections 30 Recommended Ground Wiring Practices 30 CE Conformity 30 Power Sourcing Parameters for General Locations Intrinsically Safe and Non Incendive Type N Applic...

Страница 5: ...es uses the model and serial numbers of our instruments to track information on each unit that we sell and service If a problem occurs with your HIM check for a tag affixed to the unit listing these n...

Страница 6: ...Quaternary Variable Process Data and Instrument Diagnostic Information HIM HART Interface Module Breaks Out Data from Smart HART Instruments HART Primary Master Smart HART Multivariable Mass Flow Tra...

Страница 7: ...nge Configurable from 1 to 247 Unit will assume a MODBUS address of 01 by default Baud Rate Interface supports the following 300 600 1200 4800 9600 19 2k MODBUS interface will support even odd and no...

Страница 8: ...folder 2 Double click the installation program located in the folder Follow the prompts to correctly install the program Once the Configuration Program is installed on the PC the unit can be connecte...

Страница 9: ...6 10 11 12 HART Input 2 MODBUS Outputs and 1 Analog Output MB1AO Dual Alarm 2PRG HIM 1 2 3 7 8 9 10 11 12 TX HIM 10 11 12 IN IN A MODBUS 2 1 2 3 4 5 6 10 11 12 HART Input 2 MODBUS Outputs MB No Alarm...

Страница 10: ...Computer Moore Industries PC Configuration Software Communication Cable 250 ohms 0 01 Accurate to 0 009 of span e g HP Model 3487A 24Vdc 10 Microsoft Windows based PC 16Mb free RAM 20MB free disk spa...

Страница 11: ...OM 0 ADDR COMMON NC normally closed NO normally open 4 20mA DCS Sensor Input NO NC 24Vdc Power Source R HART Multivariable Field Instrument Temperature Pressure Level and Flow Analog Output tied to An...

Страница 12: ...ADY INPUT TRIP 2 TRIP 1 COM 0 ADDR COMMON NC normally closed NO normally open 4 20mA DCS Sensor Input NO NC DC GND 24Vdc Power Source DCC R must be 250 and 1100 Ohms R HART Multivariable Field Instrum...

Страница 13: ...The Interface Solution Experts 13 HIM Smart HART Loop Interface and Monitor Figure 7 HIM Output Wiring with Active Output and Passive Output...

Страница 14: ...device was configured HIM Tag A phrase used to identify a HIM Figure 8 HIM PC Configuration Software Screen HIM Device Status Displays how the HIM is functioning giving a brief summary of any errors...

Страница 15: ...ing the HIM to function as the Primary HART Master in the application means that any other HART device in the loop must be configured either as a HART Secondary Master 1 per loop or as a HART Slave up...

Страница 16: ...9 HART Slave Device Long Format Address Settings Screen To convert HEX to Decimal code perform the following steps Access the Calculator feature in Microsoft Windows by opening the Start menu Next sel...

Страница 17: ...econd increments Directly below the Toggle checkbox are two list boxes to select the variables that you would like to be displayed Notice that if you select a scaled variable it is important to check...

Страница 18: ...r failure has occurred in the connected HART device Configuration Changed Bit 6 Relay trips whenever it detects that the connected HART device has had its configuration changed Cold Start Bit 5 Relay...

Страница 19: ...s information returned by certain HART instruments This provides flexibility to the requirement of alarming on additional status information Choosing this feature you are given the ability to spec ify...

Страница 20: ...n Custom Curve The middle section of the screen displays the custom curve table After enabling custom curve mode and setting the variable to be monitored continue by selecting the number of points for...

Страница 21: ...set the Source as SV Set the Input Range to 0 and 400 F and the Output Range to 4mA to 20mA Click Quick Set to download the new configuration file to the HIM Output Current Box The Output Current Box...

Страница 22: ...til the analog output matches the minimum point 4mA for a 4 20mA output when you click the Fix Output at Low Point button After the low point is trimmed press the Fix Output at High Point button Read...

Страница 23: ...to measure the level of a tank in either centimeters inches or PSI Since the tank is only 300 centimeters 10 feet high the full range of the primary variable PV output from the DP transmitter is 0 4 3...

Страница 24: ...ast significant bits in the first register Selecting Swapped MSW most significant word will reverse the order storing the most signifi cant bits in the first register and the least significant bits in...

Страница 25: ...erature Pressure Level Flow Multivariable HART Communicator can be connected anywhere on the loop COM IN TX IN MODBUS output with MODBUS option A B S RS485 RS232 Converter TO serial COM port of PC MOD...

Страница 26: ...it 1 EEPROM fail Bit 2 EEPROM configuration checksum error Bit 3 EEPROM calibration checksum error Bit 4 EEPROM blank Bit 5 Out of range error Bit 6 Division by zero error Bit 7 Configuration data bad...

Страница 27: ...te 1 Additional Status Byte 2 Additional Status Byte 3 Additional Status Byte 4 HART Primary variable float format HART Secondary variable float format HART Tertiary variable float format HART Quatern...

Страница 28: ...aming error Overrun error Parity error No error Undefined Invalid selection Passed parameter too large Passed parameter too small Too few bytes received Device specific command error In write protect...

Страница 29: ...nformation can be considered as valid Another example using Tables 4 and 5 the following value in MODBUS Register 13 0000 0000 0001 1001 binary or 19 hexadecimal or 25 decimal implies Primary variable...

Страница 30: ...eceiver and a transmitter SPA 2 HIM etc Hence your shield ground connections should be appropriate for the type of signal line being shielded The shield should be grounded at the receiver and not at t...

Страница 31: ...and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This policy shall not...

Отзывы: