background image

HIM

16 

The Interface Solution Experts

Smart HART

 Loop 

Interface and Monitor

It then takes the HART master five seconds to repeat 
the poll to the one device being monitored by the HIM.  
the HIM 

Timeout Period

 must be set at a value greater 

than five seconds.  In this example, we will use seven 
seconds.  The HIM then sees its slave device speak 
and waits seven seconds for it to speak again.  As long 
as the HIM sees a new message from its slave device 
its outputs are updated based upon the measured 
variables.  If the slave device does not speak within the 
seven second period, the HIM declares a “No HART” 
situation and sends its outputs to the failed communi-
cations values.

To use this feature, proceed with the following steps:

1.  Select the 

Listen (Specified Slave) 

button.

2.  Enter your desired value into the 

Timeout Period(s)

 

text box.

Factory default is 5 seconds.  The maximum Timeout 
Period is 30 seconds.

3.  Set the exact slave address of the instrument you 
wish to monitor.  Click the 

Set Slave Address

 button.  

This brings up the 

HART Slave Device Long Format 

Address Settings

 screen (Figure 8).  Enter the required 

information into the appropriate text boxes.  

 

 
The 

Manufacturer’s ID

 and 

Device Type ID

 for the 

instrument that the HIM will listen to are available from 
the HART Foundation website at 

www.hartcomm.org

 

and/or the instrument manufacturer.

Values obtained from the HART website are in HEX 
code.  The HIM does not use HEX code; you must 
convert this value to Decimal code.

Figure 9.

  HART Slave Device Long Format Address Settings 

Screen

 

To convert HEX to Decimal code, perform the  

 

following steps:

 

Access the Calculator feature in Microsoft    

 

Windows® by opening the 

Start

 menu.  Next,  

  select 

Programs

 then 

Accessories

 and finally  

 

 Calculator

.

 

Ensure that the Calculator is in 

Scientific

 mode.    

     To do this, select the 

View

 dropdown menu    

 

and choose 

Scientific

.

 

Click the 

Hex

 radio button and enter the HEX     

  code 

value.

 

Next, click the 

Dec

 button and the value will be  

 

converted into the Decimal value.

 

Enter the converted value into the proper param 

 eter.

 The 

Device ID Number

 is the serial number of  

 

the exact device to which the HIM will listen.  

4.  Once complete, press 

OK

.

Download the information to your instrument once you 
are finished.

Auto Clear Status Bit

Most HART instruments indicate when a device’s 
configuration has been changed.  This indication 
(status bit) can be reset by sending HART command 
38–reset configuration changed.  Checking the 

Auto Clear Status Bit

 box causes the HIM to issue 

this command whenever the HART instrument it is 
monitoring has its configuration changed.  However, 
the HIM can also be set to alarm on this bit (see 

Programming the Alarm Parameters

).  If the HIM is 

both set to alarm and to auto clear, then it will do both–
going into alarm mode and resetting that indication.
 

Quick Read/Set

The 

Quick Read

 button causes the PC Configuration 

Software to read the communications information 
from the attached HIM; the 

Quick Set

 button causes 

the software to configure the HIM’s communications 
settings to match those of the PC Software.

HART Device Info

This box displays the identification and revision 
information of the monitored HART instrument.

Содержание HIM

Страница 1: ...D e m a n d M o o r e R e l i a b i l i t y All product names are registered trademarks of their respective companies User s Manual HIM No 224 778 00G November 2018 Smart HART Loop Interface and Moni...

Страница 2: ...s Europe Australia 16650 Schoenborn Street North Hills California 91343 6196 U S A Tel 818 894 7111 Fax 818 891 2816 E mail info miinet com TOLL FREE 1 800 999 2900 www miinet com 1 Lloyds Court Manor...

Страница 3: ...Inputs 5 Outputs 5 Options 5 TX Power Supply 5 HIM Dimensions 6 Specifications 7 Configuring the HIM 8 Terminal Designations 9 Installing the HIM 10 Installing the HIM into the Loop 10 Bench Checking...

Страница 4: ...nting 30 Making the Electrical Connections 30 Recommended Ground Wiring Practices 30 CE Conformity 30 Power Sourcing Parameters for General Locations Intrinsically Safe and Non Incendive Type N Applic...

Страница 5: ...es uses the model and serial numbers of our instruments to track information on each unit that we sell and service If a problem occurs with your HIM check for a tag affixed to the unit listing these n...

Страница 6: ...Quaternary Variable Process Data and Instrument Diagnostic Information HIM HART Interface Module Breaks Out Data from Smart HART Instruments HART Primary Master Smart HART Multivariable Mass Flow Tra...

Страница 7: ...nge Configurable from 1 to 247 Unit will assume a MODBUS address of 01 by default Baud Rate Interface supports the following 300 600 1200 4800 9600 19 2k MODBUS interface will support even odd and no...

Страница 8: ...folder 2 Double click the installation program located in the folder Follow the prompts to correctly install the program Once the Configuration Program is installed on the PC the unit can be connecte...

Страница 9: ...6 10 11 12 HART Input 2 MODBUS Outputs and 1 Analog Output MB1AO Dual Alarm 2PRG HIM 1 2 3 7 8 9 10 11 12 TX HIM 10 11 12 IN IN A MODBUS 2 1 2 3 4 5 6 10 11 12 HART Input 2 MODBUS Outputs MB No Alarm...

Страница 10: ...Computer Moore Industries PC Configuration Software Communication Cable 250 ohms 0 01 Accurate to 0 009 of span e g HP Model 3487A 24Vdc 10 Microsoft Windows based PC 16Mb free RAM 20MB free disk spa...

Страница 11: ...OM 0 ADDR COMMON NC normally closed NO normally open 4 20mA DCS Sensor Input NO NC 24Vdc Power Source R HART Multivariable Field Instrument Temperature Pressure Level and Flow Analog Output tied to An...

Страница 12: ...ADY INPUT TRIP 2 TRIP 1 COM 0 ADDR COMMON NC normally closed NO normally open 4 20mA DCS Sensor Input NO NC DC GND 24Vdc Power Source DCC R must be 250 and 1100 Ohms R HART Multivariable Field Instrum...

Страница 13: ...The Interface Solution Experts 13 HIM Smart HART Loop Interface and Monitor Figure 7 HIM Output Wiring with Active Output and Passive Output...

Страница 14: ...device was configured HIM Tag A phrase used to identify a HIM Figure 8 HIM PC Configuration Software Screen HIM Device Status Displays how the HIM is functioning giving a brief summary of any errors...

Страница 15: ...ing the HIM to function as the Primary HART Master in the application means that any other HART device in the loop must be configured either as a HART Secondary Master 1 per loop or as a HART Slave up...

Страница 16: ...9 HART Slave Device Long Format Address Settings Screen To convert HEX to Decimal code perform the following steps Access the Calculator feature in Microsoft Windows by opening the Start menu Next sel...

Страница 17: ...econd increments Directly below the Toggle checkbox are two list boxes to select the variables that you would like to be displayed Notice that if you select a scaled variable it is important to check...

Страница 18: ...r failure has occurred in the connected HART device Configuration Changed Bit 6 Relay trips whenever it detects that the connected HART device has had its configuration changed Cold Start Bit 5 Relay...

Страница 19: ...s information returned by certain HART instruments This provides flexibility to the requirement of alarming on additional status information Choosing this feature you are given the ability to spec ify...

Страница 20: ...n Custom Curve The middle section of the screen displays the custom curve table After enabling custom curve mode and setting the variable to be monitored continue by selecting the number of points for...

Страница 21: ...set the Source as SV Set the Input Range to 0 and 400 F and the Output Range to 4mA to 20mA Click Quick Set to download the new configuration file to the HIM Output Current Box The Output Current Box...

Страница 22: ...til the analog output matches the minimum point 4mA for a 4 20mA output when you click the Fix Output at Low Point button After the low point is trimmed press the Fix Output at High Point button Read...

Страница 23: ...to measure the level of a tank in either centimeters inches or PSI Since the tank is only 300 centimeters 10 feet high the full range of the primary variable PV output from the DP transmitter is 0 4 3...

Страница 24: ...ast significant bits in the first register Selecting Swapped MSW most significant word will reverse the order storing the most signifi cant bits in the first register and the least significant bits in...

Страница 25: ...erature Pressure Level Flow Multivariable HART Communicator can be connected anywhere on the loop COM IN TX IN MODBUS output with MODBUS option A B S RS485 RS232 Converter TO serial COM port of PC MOD...

Страница 26: ...it 1 EEPROM fail Bit 2 EEPROM configuration checksum error Bit 3 EEPROM calibration checksum error Bit 4 EEPROM blank Bit 5 Out of range error Bit 6 Division by zero error Bit 7 Configuration data bad...

Страница 27: ...te 1 Additional Status Byte 2 Additional Status Byte 3 Additional Status Byte 4 HART Primary variable float format HART Secondary variable float format HART Tertiary variable float format HART Quatern...

Страница 28: ...aming error Overrun error Parity error No error Undefined Invalid selection Passed parameter too large Passed parameter too small Too few bytes received Device specific command error In write protect...

Страница 29: ...nformation can be considered as valid Another example using Tables 4 and 5 the following value in MODBUS Register 13 0000 0000 0001 1001 binary or 19 hexadecimal or 25 decimal implies Primary variable...

Страница 30: ...eceiver and a transmitter SPA 2 HIM etc Hence your shield ground connections should be appropriate for the type of signal line being shielded The shield should be grounded at the receiver and not at t...

Страница 31: ...and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This policy shall not...

Отзывы: