background image

 

The Interface Solution Experts 

7

HIM

Smart HART

 Loop 

Interface and Monitor

Performance 

Indicators 

(Continued)

Performance 

(Continued)

 

Specifications

Input Accuracy:

  Reflects the 

accuracy of the HART field 

device 

Input Impedance:

  Transmit 

Mode:  150 ohms;  

Receive Mode:  Less than 

 

5 kohms 

 

ANALOG OUTPUTS

 

Output Accuracy:

 ±0.015% 

of maximum output  span 

(20mA).  Includes the 

combined effects of linearity, 

hysteresis, repeatability and 

adjustment resolution) 

Output Response Time: 

 

<120msec, 10-90%

 

Isolation:

  500Vrms 

channel-to-channel isolation; 

1000Vrms between case, 

input, outputs and power 

terminals, and will withstand 

1500Vac dielectric strength 

test for one minute with no 

breakdown 

Ripple: 

 Less than 10mV 

peak-to-peak when measured 

across a 250 ohm resistor

 

Output Limiting:

  130% of 

span maximum; 125% of 

span typical 

Output Protection:

  

Transient protection on output 

Load Capability: 

  

0-20mA, 1100 ohms 

maximum

 

Load Effect:

  ±0.01% of 

span from 0 to maximum load 

resistance 

Line Voltage Effect:

  

±0.005% of output span for a 

1% change in line voltage 

Input Fail Modes: 

 PC 

programmable to fail high, fail 

low, hold last, hold last then 

fail high, or hold last then fail 

low (configurable hold time, 

 

0-60 seconds) 

Output Limits on Input 

Failure:  

 

0-20mA:  Fail Low to 0mA or 

Fail High to 23.6mA

 

4-20mA:  Fail Low to 3.6mA 

or Fail High to 23.6mA

 

X-20mA (0<X<4):  Fail Low to 

90% of XmA or Fail High to 

23.6mA

 

 

+TX Power Supply: 

24.0Vdc 

±10%@24mA

 

ALARM OUTPUTS 

Digital Response Time:  

Defined by HART protocol as 

500msec maximum in Normal 

HART Mode; 

 

333msec maximum in HART 

Burst Mode 

 

Alarm Response Time:  

Digital Response Time + 

150msec (Defined as time 

from the field instrument’s 

reporting a fault until the HIM 

alarm is tripped) 

Alarm Trip Delay:  

Programmable from 0-120 

seconds 

 

MODBUS OUTPUTS 

Type: 

 Standard MODBUS 

RTU protocol interface over 

RS-485 (parameters as 

specified in U.S. Standard 

EIA-RS485)

 

Address Range:

  

Configurable from 1 to 247.  

Unit will assume a MODBUS 

address of 01 by default 

Baud Rate: 

 Interface 

supports the following:  300, 

600, 1200, 4800, 9600, 

19.2k.  MODBUS interface 

will support even, odd and 

no parities.  Unit will assume 

a baud rate of 9600 and no 

parity by default 

Character Format: 

 One 

start bit, 8 data bits and one 

stop bit 

Data Format:  

User-

selectable Standard LSW 

(Least Significant Word) 

or Swapped MSW (Most 

Significant Word).  Unit will 

assume Standard LSW by 

default 

Transmission Range:

  Using 

24AWG twisted pair wiring, 

maximum of 2 mi. (3.2km)@ 

4800 baud or less; maximum 

of 1 mi. (1.6km)@9600 baud; 

maximum of 0.5 mi. (0.8km) 

@19200 baud

 

Power Consumption:  

 

2-3.5W, nominal; 

4.5W@24Vdc maximum 

for units using transmitter 

excitation to supply loop 

power a 2-wire instrument

 

 

LCD Type:

   Two-line LCD; 

Top Row, 10mm (0.4 in) high 

black digits on a reflective 

background; Bottom Row, 

Indicators

 

Ambient 

Conditions

Weight

6mm (0.225 in) high digits on 

a reflective background; two-

digit HART address indicator

 

Format: 

 Top row is five 

alphanumeric characters, 

plus sign and decimal 

point; bottom row is five 

alphanumeric characters 

Decimal Points:

  User-

selectable for 0, 1, 2 or 3 

places after the decimal point 

or automatically adjusting 

with a four decimal point 

maximum

 

Range: 

 -99999 to 99999 

Minimum Display Span:

  

1.00 

Display Update Rate:

  

100msec 

LED Type:  

Dual color 

 

red/green indicate: 

INPUT LED:  Whether 

(green) or not (red) the 

HART input is connected and 

functioning properly 

READY LED:  Whether 

(green) or not (red) the HIM 

is initialized and operating 

properly 

TRIP 1 and 2 LED:  Shows 

the status of alarm off (green) 

or alarm on (red)     

 

Operating & Storage 

Range:

  

-40°C to +85°C 

 

(-40°F to +185°F)

 

Display Range:

 

-25°C to +85°C

 

(-13°F to +185°F)

 

Relay Range:

 

-25°C to +70°C 

 

(-13°F to +158°F)    

 

Relative Humidity:

  

0-95%, non-condensing

 

Ambient Temperature 

Effect: 

 ±0.0065% of  

span/°C maximum

 

RFI/EMI Immunity: 

STANDARD: 

 

10V/m@80-1000MHz, 1kHz 

AM, when tested according 

to IEC61000-4-3

 

WITH -RF OPTION

  

20V/m@80-1000MHz, 1kHz, 

when tested according to 

IEC61000-4-3

 

Noise Rejection:

 Common 

Mode: 100dB@50/60Hz  

 

567 grams (16 ounces) 

Содержание HIM

Страница 1: ...D e m a n d M o o r e R e l i a b i l i t y All product names are registered trademarks of their respective companies User s Manual HIM No 224 778 00G November 2018 Smart HART Loop Interface and Moni...

Страница 2: ...s Europe Australia 16650 Schoenborn Street North Hills California 91343 6196 U S A Tel 818 894 7111 Fax 818 891 2816 E mail info miinet com TOLL FREE 1 800 999 2900 www miinet com 1 Lloyds Court Manor...

Страница 3: ...Inputs 5 Outputs 5 Options 5 TX Power Supply 5 HIM Dimensions 6 Specifications 7 Configuring the HIM 8 Terminal Designations 9 Installing the HIM 10 Installing the HIM into the Loop 10 Bench Checking...

Страница 4: ...nting 30 Making the Electrical Connections 30 Recommended Ground Wiring Practices 30 CE Conformity 30 Power Sourcing Parameters for General Locations Intrinsically Safe and Non Incendive Type N Applic...

Страница 5: ...es uses the model and serial numbers of our instruments to track information on each unit that we sell and service If a problem occurs with your HIM check for a tag affixed to the unit listing these n...

Страница 6: ...Quaternary Variable Process Data and Instrument Diagnostic Information HIM HART Interface Module Breaks Out Data from Smart HART Instruments HART Primary Master Smart HART Multivariable Mass Flow Tra...

Страница 7: ...nge Configurable from 1 to 247 Unit will assume a MODBUS address of 01 by default Baud Rate Interface supports the following 300 600 1200 4800 9600 19 2k MODBUS interface will support even odd and no...

Страница 8: ...folder 2 Double click the installation program located in the folder Follow the prompts to correctly install the program Once the Configuration Program is installed on the PC the unit can be connecte...

Страница 9: ...6 10 11 12 HART Input 2 MODBUS Outputs and 1 Analog Output MB1AO Dual Alarm 2PRG HIM 1 2 3 7 8 9 10 11 12 TX HIM 10 11 12 IN IN A MODBUS 2 1 2 3 4 5 6 10 11 12 HART Input 2 MODBUS Outputs MB No Alarm...

Страница 10: ...Computer Moore Industries PC Configuration Software Communication Cable 250 ohms 0 01 Accurate to 0 009 of span e g HP Model 3487A 24Vdc 10 Microsoft Windows based PC 16Mb free RAM 20MB free disk spa...

Страница 11: ...OM 0 ADDR COMMON NC normally closed NO normally open 4 20mA DCS Sensor Input NO NC 24Vdc Power Source R HART Multivariable Field Instrument Temperature Pressure Level and Flow Analog Output tied to An...

Страница 12: ...ADY INPUT TRIP 2 TRIP 1 COM 0 ADDR COMMON NC normally closed NO normally open 4 20mA DCS Sensor Input NO NC DC GND 24Vdc Power Source DCC R must be 250 and 1100 Ohms R HART Multivariable Field Instrum...

Страница 13: ...The Interface Solution Experts 13 HIM Smart HART Loop Interface and Monitor Figure 7 HIM Output Wiring with Active Output and Passive Output...

Страница 14: ...device was configured HIM Tag A phrase used to identify a HIM Figure 8 HIM PC Configuration Software Screen HIM Device Status Displays how the HIM is functioning giving a brief summary of any errors...

Страница 15: ...ing the HIM to function as the Primary HART Master in the application means that any other HART device in the loop must be configured either as a HART Secondary Master 1 per loop or as a HART Slave up...

Страница 16: ...9 HART Slave Device Long Format Address Settings Screen To convert HEX to Decimal code perform the following steps Access the Calculator feature in Microsoft Windows by opening the Start menu Next sel...

Страница 17: ...econd increments Directly below the Toggle checkbox are two list boxes to select the variables that you would like to be displayed Notice that if you select a scaled variable it is important to check...

Страница 18: ...r failure has occurred in the connected HART device Configuration Changed Bit 6 Relay trips whenever it detects that the connected HART device has had its configuration changed Cold Start Bit 5 Relay...

Страница 19: ...s information returned by certain HART instruments This provides flexibility to the requirement of alarming on additional status information Choosing this feature you are given the ability to spec ify...

Страница 20: ...n Custom Curve The middle section of the screen displays the custom curve table After enabling custom curve mode and setting the variable to be monitored continue by selecting the number of points for...

Страница 21: ...set the Source as SV Set the Input Range to 0 and 400 F and the Output Range to 4mA to 20mA Click Quick Set to download the new configuration file to the HIM Output Current Box The Output Current Box...

Страница 22: ...til the analog output matches the minimum point 4mA for a 4 20mA output when you click the Fix Output at Low Point button After the low point is trimmed press the Fix Output at High Point button Read...

Страница 23: ...to measure the level of a tank in either centimeters inches or PSI Since the tank is only 300 centimeters 10 feet high the full range of the primary variable PV output from the DP transmitter is 0 4 3...

Страница 24: ...ast significant bits in the first register Selecting Swapped MSW most significant word will reverse the order storing the most signifi cant bits in the first register and the least significant bits in...

Страница 25: ...erature Pressure Level Flow Multivariable HART Communicator can be connected anywhere on the loop COM IN TX IN MODBUS output with MODBUS option A B S RS485 RS232 Converter TO serial COM port of PC MOD...

Страница 26: ...it 1 EEPROM fail Bit 2 EEPROM configuration checksum error Bit 3 EEPROM calibration checksum error Bit 4 EEPROM blank Bit 5 Out of range error Bit 6 Division by zero error Bit 7 Configuration data bad...

Страница 27: ...te 1 Additional Status Byte 2 Additional Status Byte 3 Additional Status Byte 4 HART Primary variable float format HART Secondary variable float format HART Tertiary variable float format HART Quatern...

Страница 28: ...aming error Overrun error Parity error No error Undefined Invalid selection Passed parameter too large Passed parameter too small Too few bytes received Device specific command error In write protect...

Страница 29: ...nformation can be considered as valid Another example using Tables 4 and 5 the following value in MODBUS Register 13 0000 0000 0001 1001 binary or 19 hexadecimal or 25 decimal implies Primary variable...

Страница 30: ...eceiver and a transmitter SPA 2 HIM etc Hence your shield ground connections should be appropriate for the type of signal line being shielded The shield should be grounded at the receiver and not at t...

Страница 31: ...and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This policy shall not...

Отзывы: