Installing the HIM

 

There are two methods for connecting the HIM for 
configuration. The recommended method requires 
you to install the instrument into the loop before it 
is configured.  The secondary method allows you to 
bench check the HIM by attaching it to test equipment 
that will simulate the input and monitor the output. 
 

Installing the HIM into the Loop

 

To install the HIM into the loop for configuration, use 
the equipment shown in Table 2.   Refer to Figure 5 (to 
install without using the TX power supply) or Figure 6 
(to install using the TX power supply).

Bench Checking the HIM

 

If you would like to configure the HIM before attaching 
it to the loop, you need to hook it up with the 
equipment listed in Table 1.  Refer to Figures 3 and 4 
for instructions on how to bench check the HIM either 
with or without taking advantage of the Transmitter 
Excitation (+TX) terminal. If you need further 
descriptions of the terminals, see Table 2.  
 

Precision Load 

Resistor 

 

Multimeter or  

Ammeter 

 

Power  

Supply 

 
 

 

 
 

Personal Computer 

 
 
    

 

Moore Industries  

PC Configuration 

Software  

 

Communication 

Cable 

 

250 ohms, ±0.01% 
 

 

Accurate to ±0.009% of span,  
e.g. HP Model 3487A 
 

 

24Vdc, ±10% 
 

 

Microsoft Windows based PC;16Mb free 
RAM; 20MB free disk space on hard drive 
Microsoft Windows 7, 10

1 (one) serial port or one available USB 
port 

 
 
Version 1.0 or higher, successfully installed 
to the hard drive 
 
9-Pin Serial Cable Part# 803-053-26 or 
USB Cable Part# 804-030-26

              Device                                  Specifications

Table 2.

  Assembling the Necessary Equipment

Figure 3.

  Bench Checking the HIM Using the Transmitter Excitation 

(+TX) Terminal to Power a Transmitter

Figure 4.

  Bench Checking the HIM Using and External Power 

Source to Power a Transmitter

READY

INPUT

TRIP 2

TRIP 1

COM

0

ADDR

For a HART Transmitter, the 
resistor must be  >250

 

and <1100 ohms

.

For a HART Receiver, such as a 
valve positioner, no resistor is necessary.

HART

Field Device

or

Simulator

Sensor

Input

Optional

Optional

Checks for

continuity

24Vdc
Power

R

+IN

NO

NC

CO

M

–IN

+

+

+

+

Multimeter

Multimeter

24Vdc
Power

(+) DC

GND

(-) DCC

READY

INPUT

TRIP 2

TRIP 1

COM

0

ADDR

Optional

Checks for

continuity

NO

NC

COM

+

+

Multimeter

Multimeter

24Vdc
Power

HART

Field Device

or

Simulator

Sensor

Input

Equipment Hook-Up

for HART field device using

Transmitter Excitation

R

+TX

–IN

+IN

+

R must be > 250 and <1100 Ohms

(+) DC

GND

(-) DCC

Содержание HIM

Страница 1: ...D e m a n d M o o r e R e l i a b i l i t y All product names are registered trademarks of their respective companies User s Manual HIM No 224 778 00G November 2018 Smart HART Loop Interface and Moni...

Страница 2: ...s Europe Australia 16650 Schoenborn Street North Hills California 91343 6196 U S A Tel 818 894 7111 Fax 818 891 2816 E mail info miinet com TOLL FREE 1 800 999 2900 www miinet com 1 Lloyds Court Manor...

Страница 3: ...Inputs 5 Outputs 5 Options 5 TX Power Supply 5 HIM Dimensions 6 Specifications 7 Configuring the HIM 8 Terminal Designations 9 Installing the HIM 10 Installing the HIM into the Loop 10 Bench Checking...

Страница 4: ...nting 30 Making the Electrical Connections 30 Recommended Ground Wiring Practices 30 CE Conformity 30 Power Sourcing Parameters for General Locations Intrinsically Safe and Non Incendive Type N Applic...

Страница 5: ...es uses the model and serial numbers of our instruments to track information on each unit that we sell and service If a problem occurs with your HIM check for a tag affixed to the unit listing these n...

Страница 6: ...Quaternary Variable Process Data and Instrument Diagnostic Information HIM HART Interface Module Breaks Out Data from Smart HART Instruments HART Primary Master Smart HART Multivariable Mass Flow Tra...

Страница 7: ...nge Configurable from 1 to 247 Unit will assume a MODBUS address of 01 by default Baud Rate Interface supports the following 300 600 1200 4800 9600 19 2k MODBUS interface will support even odd and no...

Страница 8: ...folder 2 Double click the installation program located in the folder Follow the prompts to correctly install the program Once the Configuration Program is installed on the PC the unit can be connecte...

Страница 9: ...6 10 11 12 HART Input 2 MODBUS Outputs and 1 Analog Output MB1AO Dual Alarm 2PRG HIM 1 2 3 7 8 9 10 11 12 TX HIM 10 11 12 IN IN A MODBUS 2 1 2 3 4 5 6 10 11 12 HART Input 2 MODBUS Outputs MB No Alarm...

Страница 10: ...Computer Moore Industries PC Configuration Software Communication Cable 250 ohms 0 01 Accurate to 0 009 of span e g HP Model 3487A 24Vdc 10 Microsoft Windows based PC 16Mb free RAM 20MB free disk spa...

Страница 11: ...OM 0 ADDR COMMON NC normally closed NO normally open 4 20mA DCS Sensor Input NO NC 24Vdc Power Source R HART Multivariable Field Instrument Temperature Pressure Level and Flow Analog Output tied to An...

Страница 12: ...ADY INPUT TRIP 2 TRIP 1 COM 0 ADDR COMMON NC normally closed NO normally open 4 20mA DCS Sensor Input NO NC DC GND 24Vdc Power Source DCC R must be 250 and 1100 Ohms R HART Multivariable Field Instrum...

Страница 13: ...The Interface Solution Experts 13 HIM Smart HART Loop Interface and Monitor Figure 7 HIM Output Wiring with Active Output and Passive Output...

Страница 14: ...device was configured HIM Tag A phrase used to identify a HIM Figure 8 HIM PC Configuration Software Screen HIM Device Status Displays how the HIM is functioning giving a brief summary of any errors...

Страница 15: ...ing the HIM to function as the Primary HART Master in the application means that any other HART device in the loop must be configured either as a HART Secondary Master 1 per loop or as a HART Slave up...

Страница 16: ...9 HART Slave Device Long Format Address Settings Screen To convert HEX to Decimal code perform the following steps Access the Calculator feature in Microsoft Windows by opening the Start menu Next sel...

Страница 17: ...econd increments Directly below the Toggle checkbox are two list boxes to select the variables that you would like to be displayed Notice that if you select a scaled variable it is important to check...

Страница 18: ...r failure has occurred in the connected HART device Configuration Changed Bit 6 Relay trips whenever it detects that the connected HART device has had its configuration changed Cold Start Bit 5 Relay...

Страница 19: ...s information returned by certain HART instruments This provides flexibility to the requirement of alarming on additional status information Choosing this feature you are given the ability to spec ify...

Страница 20: ...n Custom Curve The middle section of the screen displays the custom curve table After enabling custom curve mode and setting the variable to be monitored continue by selecting the number of points for...

Страница 21: ...set the Source as SV Set the Input Range to 0 and 400 F and the Output Range to 4mA to 20mA Click Quick Set to download the new configuration file to the HIM Output Current Box The Output Current Box...

Страница 22: ...til the analog output matches the minimum point 4mA for a 4 20mA output when you click the Fix Output at Low Point button After the low point is trimmed press the Fix Output at High Point button Read...

Страница 23: ...to measure the level of a tank in either centimeters inches or PSI Since the tank is only 300 centimeters 10 feet high the full range of the primary variable PV output from the DP transmitter is 0 4 3...

Страница 24: ...ast significant bits in the first register Selecting Swapped MSW most significant word will reverse the order storing the most signifi cant bits in the first register and the least significant bits in...

Страница 25: ...erature Pressure Level Flow Multivariable HART Communicator can be connected anywhere on the loop COM IN TX IN MODBUS output with MODBUS option A B S RS485 RS232 Converter TO serial COM port of PC MOD...

Страница 26: ...it 1 EEPROM fail Bit 2 EEPROM configuration checksum error Bit 3 EEPROM calibration checksum error Bit 4 EEPROM blank Bit 5 Out of range error Bit 6 Division by zero error Bit 7 Configuration data bad...

Страница 27: ...te 1 Additional Status Byte 2 Additional Status Byte 3 Additional Status Byte 4 HART Primary variable float format HART Secondary variable float format HART Tertiary variable float format HART Quatern...

Страница 28: ...aming error Overrun error Parity error No error Undefined Invalid selection Passed parameter too large Passed parameter too small Too few bytes received Device specific command error In write protect...

Страница 29: ...nformation can be considered as valid Another example using Tables 4 and 5 the following value in MODBUS Register 13 0000 0000 0001 1001 binary or 19 hexadecimal or 25 decimal implies Primary variable...

Страница 30: ...eceiver and a transmitter SPA 2 HIM etc Hence your shield ground connections should be appropriate for the type of signal line being shielded The shield should be grounded at the receiver and not at t...

Страница 31: ...and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This policy shall not...

Отзывы: