Moog ACV with CANopen bus interface
8 Diagnostics
Troubleshooting
B99224-DV018-D-211, Rev. A, October 2018
294
8.4.1.53 0x74: EtherCAT TPDO time out
8.4.1.54 0x75: EtherCAT TPDO data
8.4.1.55 0x76: PROFIBUS general fault
8.4.1.56 0x77: I2C_general_fault
Error Code:
0x74
Error Name:
EtherCAT TPDO time out
Description:
A timeout on EtherCAT Transmit PDO occurred.
Severity of error:
Application specific
Action:
• Check cable and cable connection
• Check EtherCAT communication interface settings
Error Code:
0x75
Error Name:
EtherCAT TPDO data
Description:
A problem with the parametrization on EtherCAT Transmit PDO was detected.
Severity of error:
Application specific
Action:
• Check cable and cable connection
• Check EtherCAT communication interface settings
Error Code:
0x76
Error Name:
PROFIBUS general fault
Description:
A problem with the Profibus communication occurred.
Severity of error:
Application specific
Action:
• Check cable and cable connection
• Check Profibus communication interface settings
Error Code:
0x77
Error Name:
I2C_general_fault
Description:
An error while reading the setting of the DIP switches occurred.
Severity of error:
Major
Action:
• Check the DIP switches for correct positioning
• Restart the valve
If the error still occurs after restarting the valve, send the valve back to factory for
service.
This fault reaction is available for valves with DIP switches only.