Moog ACV with CANopen bus interface
8 Diagnostics
Troubleshooting
B99224-DV018-D-211, Rev. A, October 2018
287
8.4.1.30 0x3A: Factory data memory corrupted
8.4.1.31 0x3C: Diagnosis data memory corrupted
8.4.1.32 0x3D: Position control monitoring
Error Code:
0x3A
Error Name:
Factory data memory corrupted
Description:
Internal error during initialization of factory parameter settings occurred
Severity of error:
Major
Action:
• Restart the valve
If the error still occurs after restarting the valve, send the valve back to factory for
service.
Error Code:
0x3C
Error Name:
Diagnosis data memory corrupted
Description:
Internal error during initialization of diagnose parameter settings occurred
Severity of error:
Minor
Action:
• Restart the valve
If the error still occurs after restarting the valve, send the valve back to factory for
service.
Error Code:
0x3D
Error Name:
Position control monitoring
Description:
An axis position control monitoring fault is detected. The current axis position control
deviation exceeds the adjusted limits.
Severity of error:
Application specific
Action:
• Check adjusted deviation limits
• Check position
• Check sensor adjustments and settings
• Check interface configuration
This fault reaction is available for Axis Control Valves (ACV) only.
In order to make a customer configured fault reaction working, the axis position monitoring must
be switched on.
Chapter "7.15.3 Axis position control deviation monitoring", page 237